The PowerWalker VFI 1000-3000 CG PF1 is a professional series for commercial applications featuring Unity Power Factor (PF=1.0). A unique feature is the support of loads with half-wave imbalance (e.g., laser printers and ultrasound systems). They are also equipped with a very strong adjustable charger.
Multiple accessories, including battery packs and communication cards, enhance the functionality of the UPS and allow a greater backup time. The system can be monitored locally via the LCD panel or remotely via the PowerWalker ViewPower software.
Key Features:
- Unity Power Factor 1.0 (kVA = kW)
- Strong charger with adjustable current
- Ext. Battery Connector for EBM
- Support for laser printers and ultrasound systems
- Supports AC Generators
- Includes an Intelligent Slot
- Includes a Programmable Segment
General Features
| 1000VA/1000W | 1500VA/1500W | 2000VA/2000W | 3000VA/3000W | |
|---|---|---|---|---|
| Output Power Factor | 1.0 | 1.0 | 1.0 | 1.0 |
| LINE Mode Full Load Efficiency | 89.0% | 91.0% | 91.0% | 91.0% |
| Charger | 1A/[2A]/4A/6A/8A/10A/12A | 1A/[2A]/4A/6A/8A | 1A/[2A]/4A/6A/8A | 1A/[2A]/4A/6A/8A |
Input Specifications
| 1000VA/1500W | 2000VA/3000W | |
|---|---|---|
| Input Voltage Range | 160-276 VAC at 100% Load | 110-160 VAC at 50% Load | 160-276 VAC at 100% Load | 110-160 VAC at 50% Load |
| Frequency (Synchronized Range) | 47Hz-53Hz or 57Hz - 63Hz | 47Hz-53Hz or 57Hz - 63Hz |
| Input Type | IEC C14 or IEC C14UK | IEC C20 or IEC C20UK |
Output Specifications
| 1000VA | 1500VA | 2000VA | 3000VA | |
|---|---|---|---|---|
| Nominal Output Voltage | 200/208/220/230/240 VAC | 200/208/220/230/240 VAC | 200/208/220/230/240 VAC | 200/208/220/230/240 VAC |
| Voltage Regulation | +/-1% | +/-1% | +/-1% | +/-1% |
| Frequency (Battery Mode) | +/- 0.1Hz | +/- 0.1Hz | +/- 0.1Hz | +/- 0.1Hz |
| Outlets | IEC C13 (4) | IEC C13 (8) | IEC C13 (8) + IEC C19 (1) | IEC C13 (8) + IEC C19 (1) |
Battery Specifications
| 1000VA/1000W | 1500VA/1500W | 2000VA/2000W | 3000VA/3000W | |
|---|---|---|---|---|
| Batteries | 3 x 12V/7Ah | 3 x 12V/9Ah | 6 x 12V/7Ah | 6 x 12V/7Ah |
| DC Voltage | 3 x 12V | 3 x 12V | 6 x 12V | 6 x 12V |
| Recharge Time | 3h to 90% | 3h to 90% | 3h to 90% | 3h to 90% |
| Full Load Backup Time | 4.5 min | 13 min | 3 min | 10.5 min |
| Half Load Backup Time | 13 min | 10.5 min | 13 min | 10 min |
| Transfer Time [AC to Battery] | 0 ms | 0 ms | 0 ms | 0 ms |
| Transfer Time [Inverter to Bypass] | 4 ms | 4 ms | 0 ms | 0 ms |
VFI 6K-10K CG PF1
[Image: A BlueWalker UPS unit from the VFI 6K-10K CG PF1 series.]
The PowerWalker VFI 6k-10k CG PF1 is a professional series for commercial applications featuring unity Power Factor (PF=1.0). The wide input voltage and frequency ranges allow operation in unstable networks and provide generator support. They can present very low harmonic distortions (<1%) and high efficiency (up to 94%).
Multiple accessories, including battery packs and communication cards, enhance the functionality of the UPS and allow a greater backup time. The system can be monitored locally via the LCD panel or remotely via the PowerWalker ViewPower software.
Key Features:
- Unity Power Factor 1.0 (kVA = kW)
- Ext. Battery Connector for EBM
- High-Efficiency in Line Mode
- Includes an Intelligent Slot
- Includes a Programmable Segment
- Parallel Operation, up to 2 units
General Features
| 6000VA/6000W | 10000VA/10000W | |
|---|---|---|
| Output Power Factor | 1.0 | 1.0 |
| LINE Mode Full Load Efficiency | 94.0% | 94.0% |
| Charger | 1A / 2A / 4A | 1A / 2A / 4A |
Input Specifications
| Values | |
|---|---|
| Input Voltage Range | 176-300 VAC at 100% Load | 110-300 VAC at 0-60% Load |
| Frequency (Synchronized Range) | 46Hz - 54Hz or 56Hz - 64Hz |
| Input Type | Terminal |
Output Specifications
| Values | |
|---|---|
| Nominal Output Voltage | 208/220/230/240 VAC |
| Voltage Regulation | +/-1% |
| Frequency (Battery Mode) | +/- 0.1Hz |
| Outlets | Terminal |
Battery Specifications
| Values | |
|---|---|
| Batteries | 20 x 12V/9Ah |
| DC Voltage | 20 x 12V |
| Recharge Time | 9h to 90% |
| Full Load Backup Time | 6.5 min |
| Half Load Backup Time | 17 min |
| Transfer Time [AC to Battery] | 0 ms |
| Transfer Time [Inverter to Bypass] | 0 ms |