Rosemount 3490 Controller

Emerson, 3490, Controller, HART, 4–20 mA, 4-20, 4-20mA, Level, Flow, Differential level, Volume, Transmitter, Control unit, water and wastewater, channel flow, open channel, volume flow

Rosemount - Emerson

quick-start-guide-rosemount-3490-controller-en- ...

2023-11-02 — Use the controller only as specified in this Quick Start Guide and the. Reference Manual. The controller must be installed, connected, commissioned, operated, ...

Rosemount 3490 Controller Quick Start Guide (7.7 MB)

Rosemount 3490 Controller | Process Controllers | Instrumart


File Info : application/pdf, 32 Pages, 7.71MB

PDF preview unavailable. Download the PDF instead.

quick-start-guide-rosemount-3490-controller-en-9344952
Quick Start Guide 00825-0100-4843, Rev AF
November 2023
RosemountTM 3490 Controller

Quick Start Guide

November 2023

Contents About this guide........................................................................................................................... 3 Installation considerations......................................................................................................... 5 Components of the controller.................................................................................................... 7 Mount the controller................................................................................................................. 10 Prepare the electrical connections.......................................................................................... 14 Connect wiring and power up.................................................................................................. 21 Configure controller.................................................................................................................. 27 Web interface............................................................................................................................. 30

2

Emerson.com/Rosemount

November 2023

Quick Start Guide

1 About this guide
This Quick Start Guide provides basic guidelines for the Rosemount 3490 Controller. Refer to the Rosemount 3490 Reference Manual for more instructions.
1.1 Safety messages
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
Use the controller only as specified in this Quick Start Guide and the Reference Manual.
The controller must be installed, connected, commissioned, operated, and maintained by suitably qualified personnel only, observing national and local requirements that may apply.
The controller must be installed according to the Rosemount 3490 Product Certifications document.
Before commissioning the controller, ensure that the supply voltage matches the voltage specifications on the main label.
Repair, e.g. substitution of components, etc. may jeopardize safety and is under no circumstances allowed.
Electrical shock could cause death or serious injury.
Ensure that the controller is not powered when opening the lid and making terminal connections.
If the controller is installed in a high voltage environment and a fault condition or installation error occurs, high voltage may be present on leads and terminals.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users' equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental in protecting your system. Restrict physical access by unauthorized personnel to protect end users' assets. This is true for all systems used within the facility.

Quick Start Guide

3

Quick Start Guide

November 2023

CAUTION
Pollution protection Ensure that during installation or maintenance no moisture or dirt can get inside the instrument. To maintain the housing protection, ensure that the housing lid is closed during operation and locked, if necessary.

4

Emerson.com/Rosemount

November 2023

Quick Start Guide

2 Installation considerations
General
· The controller is classified type A in accordance with European EMC directive 2014/30/EU. To ensure electro-magnetic compatibility, in any member country, the controller should not be installed in a residential area.
· Supply circuits must be limited to Overvoltage category II, according to IEC 60664-1.
· Ambient temperature range: -40 to +140 °F (-40 to +60 °C)(1)
Mounting and installation
· Do not mount the controller on a structure that is subject to vibration, or in a position where damage may be caused by impact, thermal stress or liquid ingress.
· Do not mount the controller in a position where it might come into contact with aggressive substances, e.g. acidic liquids or gases that may attack metals or solvents that may affect polymeric materials.
· The controller housing is rated IP66/IP67 and Type 4X. It is suitable for mounting outside, but this should be above any flood level, away from any overflow path, and away from direct sunlight.
· The mass of the unit is 3.7 lb (1.7 kg). To conform with safety requirements, the wall on which the unit is mounted should be capable of supporting four times this weight.
· Do not mount the controller in a position where it might be exposed to mechanical damage or friction. The controller can withstand an impact of maximum 2 Joule, level of protection: IK07.
Wiring
· Ensure that cable glands and connections to the controller are done in accordance with local and national standards. To maintain the type 4X rating of the enclosure, type 4X connections must be used.
· Cable runs should be separate from any high voltage or mains cables to avoid crosstalk or interference.

(1) Display reading: -4 to +140 °F (-20 to +60 °C).

Quick Start Guide

5

Quick Start Guide

November 2023

· A switch or circuit-breaker must be included in the installation, suitable located and easily reached. It must be marked as the disconnecting device for the controller.
· Wires for mains connection should be tied together to prevent from accidental loosening.
· Field wiring shall be rated for 38 °F (21 °C) above maximum ambient temperature.
Maintenance
· To ensure the controller functionality, periodic visual inspection is recommended for: -- Secure mounting
-- No mechanical damages or corrosion
-- Worn or otherwise damaged cables

6

Emerson.com/Rosemount

November 2023

Quick Start Guide

3 Components of the controller
Figure 3-1 shows the various parts of the controller. Figure 3-1: Rosemount 3490 Components

A

B

C

D E

F

G

A. Light Emitting Diode (LED) for status and error information B. Display C. Keypad D. Sealing arc E. Cable entries F. Lid G. Terminal board and ports

Quick Start Guide

7

Quick Start Guide

November 2023

3.1

Display
The controller display serves as an interface for the user to visualize measured values and status of inputs and outputs. Depending on the selected application, different calculated values will also be presented on the display.

Figure 3-2: Typical Display Presentation

A

B

D

C E
A

F

G

A. Selected application B. Digital input status C. Bar graph of calculated value D. Relay status E. Calculated value F. Totalizer 1 value (accumulated) G. Totalizer 2 value (daily)

8

Emerson.com/Rosemount

November 2023

Quick Start Guide

3.2

Keypad

The keypad function buttons are used to navigate through the software menu system, to configure and setup the controller.
Table 3-1: Keypad Function Buttons

Button

Action

The enter button is used to access the menu system, select a menu option, or to confirm settings.

The up arrow button is used to move upwards when navigating the menu system, or to scroll through a list of options. When editing a parameter value, the up arrow button is used to increase a digit.
The down arrow button is used to move downwards when navigating the menu system, or to scroll through a list of options. When editing a parameter value, the down arrow button is used to decrease a digit.
The left arrow button is used to move left when navigating the menu system. When editing a parameter value, the left arrow button is used to move left to another digit.

The right arrow button is used to move right when navigating the menu system. When editing a parameter value, the right arrow button is used to move right to another digit.

When navigating the menu system, the back button is used to return to a previous menu level or the main screen. At other times, e.g. while editing, the button is used to restore a setting that is being edited.

Quick Start Guide

9

Quick Start Guide

4 Mount the controller

4.1 Bracket hole pattern

Figure 4-1: Hole Pattern for Wall Mounting

3.23 (82)

Ø 0.28 (7)

November 2023

2.44 (62)

Dimensions are in inches (millimeters).

4.2

Mount the controller on pipe/wall
The mounting instruction includes the wall and pipe mounting kit and the weather protection accessories. Both items are ordered separately, refer to the Rosemount 3490 Product Data Sheet.

10

Emerson.com/Rosemount

November 2023
Procedure 1. Mount the bracket on the pipe/wall. On pipe:

Quick Start Guide

13 mm or

On wall:

Quick Start Guide

11

Quick Start Guide

November 2023

2. Mount the weather protection, using the enclosed screws.

3. Loosen the four screws on the lid.

12

Emerson.com/Rosemount

November 2023 4. Mount the controller.

Quick Start Guide

5. Close the lid and tighten the four screws to torque 0.7 lb-ft (1 Nm).

Quick Start Guide

13

Quick Start Guide

November 2023

5 Prepare the electrical connections

5.1 5.2

Cable selection
The cable diameter must be suitable for the cable gland used to ensure the seal effect of the cable gland (IP protection).

Cable glands
The controller housing has seven entries for M20 cable glands. Table 5-1: Tightening Torque for Cable Glands, lb-ft (Nm)

Item
Cable gland Top nut

Cable gland
3.0 (4.0) 2.2 (3.0)

Ethernet cable gland(1) 3.3 (4.5) 3.3 (4.5)

(1) Only supplied with accessory gland kit.

Table 5-2: Cable Diameter for Glands, in. (mm)

Cable Ø

Cable gland 0.16-0.51 (4-13)

Ethernet cable gland(1) 0.27 (6.9)

(1) Only supplied with accessory gland kit.

5.3

Conduit hubs
The controller can be installed with conduit hubs. The conduit hub must be installed with a M20 to ½ NPT adapter mounted to the support plate. The adapter is available as accessories.
Table 5-3: Tightening Torque for Adapter supplied by Emerson, lb-ft (Nm)

Item Adapter, M20 thread

Torque 5.2 (7.0)

5.4 Terminal connection type
Spring loaded terminals
5.5 Conductors
Ensure that you use cables suitable for the terminal blocks.

14

Emerson.com/Rosemount

November 2023

Quick Start Guide

Table 5-4: Cables Suitable for Rosemount 3490 Terminal Blocks

Conductor connection

Maximum (mm2)

AWG

Solid

4

12

Flexible

2.5

13

Flexible, Ferrule with plastic 1.5

16

collar

Figure 5-1: Conductor Stripping Length and Cross-Sectional Area
A

B

A. Stripping length: 0.4 in. (10 mm) B. Cross-sectional area, see Table 5-4

5.6

Power supply
The Rosemount 3490 accepts supply voltage 100-240 Vac 50/60 Hz (-15% to +10%)

5.7 Power consumption
Maximum 12 W

5.8

Grounding
Make sure grounding is done according to national and local electrical codes. Failure to do so may impair the protection provided by the equipment. Grounding requirements are dependent on application type:

Shielded cables
· Connect cable shield to terminal 42 (terminal 71 for sensor input 2)
· Connect terminal 41 to instrument earth/ground point

Unshielded cables
Grounding is not necessary for unshielded sensor cables. Leave terminals 41, 42 and 71 unconnected.

Quick Start Guide

15

Quick Start Guide

November 2023

5.9

Protective earth
The metal support plate should always be grounded in accordance with national and local electrical codes. Failure to do so may impair the protection provided by the equipment. The most effective grounding method is direct connection to earth ground with minimal impedance. There is a grounding screw connection on the metal support plate.

5.10 Sensor wire cross-section
Appropriate cross-sectional area of wires must be used in order to prevent a too high voltage drop to the connected sensor. Use 0.75 mm2 to 2.5 mm2 (18 AWG to 13 AWG) in order to minimize the voltage drop.

16

Emerson.com/Rosemount

November 2023

Quick Start Guide

5.11 Terminal board and ports
Figure 5-2: Ports and Terminals - Rosemount 3490A E
D

ETHERNET

DIGITAL INPUT

I.E. EARTH

POWER
A

RELAY OUTPUT
B

A. Power supply B. Relay outputs C. Analog output D. Ethernet E. Digital inputs F. Sensor input 1

ANALOG OUTPUT
C

SENSOR INPUT 1
F

Figure 5-3: Ports and Terminals - Rosemount 3490C

E

G

D

ETHERNET

DIGITAL INPUT

SENSOR INPUT 2

I.E. EARTH

POWER
A

RELAY OUTPUT
B

A. Power supply B. Relay outputs C. Analog outputs D. Ethernet E. Digital inputs F. Sensor input 1 G. Sensor input 2

ANALOG OUTPUT
C

SENSOR INPUT 1
F

Quick Start Guide

17

Quick Start Guide

November 2023

5.12 Wiring diagrams
5.12.1 Sensor input connections Loop-powered sensors are connected as shown in Figure 5-4.
Figure 5-4: Sensor Input - Loop Powered
3490

I IN

+24V

See Figure 5-5 for an example where the Rosemount 1208C is connected to the Rosemount 3490C sensor input 1.
Figure 5-5: Example: 1208C Connected to 3490C Sensor Input 1

L-

L+

-

+

I.E. EARTH

SENSOR INPUT 1

1208C

18

Emerson.com/Rosemount

November 2023

Quick Start Guide

5.12.2 Analog output connections
The analog output may be connected in internally-powered or looppowered mode. In loop-powered mode, an external power source is required.

Figure 5-6: Analog Output

A

B

3490

3490

I OUT

24V

0V

I OUT

A. Internal power B. Loop power
5.12.3 Relay output connections The controller relay outputs are available for normally closed and normally open relay connections. Limit range: 250 Vac 8 A/24 Vdc 8 A resistive load. Figure 5-7: Relay Output
3490
A B
C

A. Normally open B. Normally closed C. Common

Quick Start Guide

19

Quick Start Guide

November 2023

5.12.4 Digital input connections The digital potential-free contact inputs are connected as shown in Figure 5-8. Limit range: Output voltage 14 V, Output current 6 mA.
Figure 5-8: Digital Input
3490

IN

0V

20

Emerson.com/Rosemount

November 2023

Quick Start Guide

6 Connect wiring and power up
Procedure 1. Ensure the power supply is disconnected. 2. Unscrew the four screws on the lid.

3. Open the lid.

Quick Start Guide

21

Quick Start Guide 4. Remove the plastic plugs.

November 2023

5. Place the support plate into position. 6. Mount the cable glands.

22

Emerson.com/Rosemount

November 2023

Quick Start Guide

7. Pull the power cable through the cable gland.

8. Connect the protective earth ground to the support plate with the ring terminal(2) and grounding screw (M4) included in the delivery.

(2) 14 AWG (2.1 mm2) or smaller wire.

Quick Start Guide

23

Quick Start Guide

November 2023

9. Connect the power supply wires to the terminal compartment.

Note When connecting a flexible (stranded) conductor, use a small flat head screwdriver to press down and hold the terminal connection open.
10. Connect the cables to the terminal compartments suitable for your application (see Prepare the electrical connections).
11. Ensure proper grounding (see Grounding). 12. Tighten the cable glands.

24

Emerson.com/Rosemount

November 2023

Quick Start Guide

13. Seal any unused port with the enclosed plugs.

14. Close the lid and tighten the four screws to torque 0.7 lb-ft (1 Nm).

Quick Start Guide

25

Quick Start Guide

November 2023

15. Connect the power supply.
During start-up, approximately 30 seconds, the display prompts the following screen:

Once the start-up procedure is finished, the display prompts the following screen:

Postrequisites The controller is now ready to be configured.

26

Emerson.com/Rosemount

November 2023

Quick Start Guide

7 Configure controller
The Rosemount 3490 can easily be configured using the controllers display and keypad.
7.1 Set up controller
Procedure 1. Press the enter key button to access the main menu.

2. From the Main menu, select Settings.

3. From the Settings menu, select desired settings option and follow the on-screen instructions.

Option Date/Time Display
IP setting Pin security
Remote services

Description
Select date format and set date/time
Set screen saver timeout and display brightness
Set device IP address
Set pin codes for device and web interface access
Settings for remote services access

Quick Start Guide

27

Quick Start Guide

November 2023

7.2

Run application setup wizard
The application setup wizard is the recommended tool to configure the controller. The four setup wizards provide detailed guidance for each application type.
Procedure
1. Press the enter key button to access the main menu.

2. From the Main menu, select Setup wizard.

28

Emerson.com/Rosemount

November 2023

Quick Start Guide

3. From the Select application menu, select appropriate application:

Option

Application

Level and pump control

Open channel flow

Differential level (3490C only)

Tank volume
4. Follow the on-screen instructions to configure the controller according to your application.

Quick Start Guide

29

Quick Start Guide

November 2023

8 Web interface
The Rosemount 3490 has a web-based graphical user interface that provides the following functions: · Firmware upgrade · Managing log files
Figure 8-1: Web Interface Menus

Refer to the Rosemount 3490 Reference Manual for detailed information about the web interface service functions.
8.1 Access the web interface
To access the controller´s web interface:
Procedure 1. Connect a laptop to the controller´s Ethernet port. 2. Set your laptop Ethernet port to a static IP address on the same subnet as the controller. 3. Enter the controller´s IP address into your web browser. IP address from factory: 192.168.4.10
4. Enter the requested pin code. Pin code from factory: 0000
5. Once you are logged in, the web interface appears with a number of service menus.

30

Emerson.com/Rosemount

November 2023

Quick Start Guide

Quick Start Guide

31

*00825-0100-4843* Quick Start Guide 00825-0100-4843, Rev. AF November 2023
For more information: Emerson.com/global ©2023 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.

