Instruction Manual for BEKA models including: BA367E-SS Counters Intrinsically safe, BA367E-SS, Counters Intrinsically safe, Intrinsically safe

BA367E-SS

Abbreviated Instruction manuals


File Info : application/pdf, 2 Pages, 794.25KB

PDF preview unavailable. Download the PDF instead.

ba367e-ss short form
1. DESCRIPTION The BA367E-SS is an intrinsically safe, one input Counter housed in a rugged 316 stainless steel panel mounting enclosure which can operate with a wide range of sensors.
This abbreviated instruction sheet is intended to assist with installation, a comprehensive instruction manual describing safety certification, system design and configuration may be downloaded from the BEKA website or may be requested from the BEKA sales office. The BA367E-SS has IECEx, ATEX and UKEX intrinsic safety certification for use in flammable gas and dust atmospheres. ETL and cETL approval permits installation in the USA and Canada. The certification information label, which is located on the top of the instrument enclosure, shows the certification number and codes. Other certifications may be shown. Copies of certificates may be downloaded from the BEKA website.
Typical certification information label Special conditions for safe use The IECEx, ATEX and UKEX intrinsic safety certificate numbers have an `X' suffix indicating that for some applications special conditions apply for safe use.
a. When installed in an Ex e, Ex p or Ex t panel enclosure all connections to the BA367E-SS must be made by appropriately rated Zener barriers or galvanic isolators.
This means that when installed in an Ex e, Ex p or Ex t panel enclosure the BA367E-SS remains an intrinsically safe instrument.
b. The front of the stainless steel enclosure complies with the requirements for Ex e, Ex p & Ex t type of protection.
Therefore when correctly installed the BA367E-SS Counter will not invalidate the Ex e, Ex p or Ex t panel enclosure certification. Use in combustible dust atmospheres See full instruction manual for installation information requirements and special conditions for safe use in combustible dust atmospheres.

2. INSTALLATION
Cut-out dimensions Mandatory to achieve an IP66 seal between instrument and panel and to maintain certification of panel enclosure in which it is mounted.
Panel cut-out 90 +0.5 / -0.0 x 43.5 +0.5 / -0.0 Typical
terminals shown
Maximum panel thickness 8 mm
Captive gasket 105
DISPLAY

80

13

60

A1 A2
+ Alarm 1

A3 A4
+ Alarm 2

Terminals for optional dual alarms

OR P1 P2 OR C1 C2 C3 C4

+

+

Terminals for optional pulse
output

Terminals for optional 4/20mA output

12
+ Power supply 10 to 28V dc

RS1 RS2 3 4 5 6
+ Reset Add link Pulse
to energise input pulse input

E
Connect M4 earth stud to panel
enclosure in which instrument is mounted

Support panel wiring to prevent vibration damage Fig 1 Cut-out dimensions and terminals

Abbreviated instructions for
BA367E-SS Rugged one input intrinsically safe Counter

BA367E-SS

Issue 4 24th November 2022
BEKA associates Ltd. Old Charlton Rd, Hitchin, Hertfordshire, SG5 2DA, UK Tel: +44(0)1462 438301 e-mail: sales@beka.co.uk
web: www.beka.co.uk

Captive gasket
Optional stainless steel support plate
Panel enclosure

Slide a panel clamp into the two grooves at each corner of the instrument

Secure each clamp with a stainless steel washer and wing nut, tighten 22cNm (1.95lbf in) min. Finally fit protective caps.
Fig 2 Installation procedure
EMC For specified immunity all wiring should be in screened twisted pairs with screens earthed at one point within the safe area.

Hazardous area

Safe area

DISPLAY

RS2 RS1

Proximity detector

65 43 +

21 +

Switch contact/ open collector
OR Voltage pulse
N
S Magnetic pick-off

65 43 +
No link

External reset

Single channel positive polarity 28V: 93mA Zener Barrier
+ Power supply
Single channel positive polarity 28V: 93mA Zener Barrier
Remote reset in safe area

Fig 3 Use with Zener barriers
Scale card The Counters units of measurement are shown on a printed scale card visible through a window at the right hand side of the display. The scale card is mounted on a flexible strip that is inserted into a slot at the rear of the instrument as shown below
Unlock

Insert
Lock
Fig 4 Inserting flexible strip carrying scale card into slot at the rear of Counter.

Thus the scale card can easily be changed without removing the Counter from the panel or opening the instrument enclosure.

New Counters are supplied with a printed scale card showing the requested units of measurement, if this information is not supplied when the Counter is ordered a blank card will be fitted. A pack of self-adhesive scale cards printed with common units of measurement is available as an accessory from BEKA associates. Custom printed scale cards can also be supplied.

To change a scale card, unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of the enclosure. Peel the existing scale card from the flexible strip and replace it with a new printed card, which should be aligned as shown below. Do not fit a new scale card on top of an existing card.

Align on these edges

Scale card

Align the self-adhesive printed scale card onto the flexible strip and insert the strip into the Counter as shown.

Fig 5 Fitting scale card to flexible strip

3. OPERATION The Counter is controlled by four front panel push buttons. When in the operating mode they have the following functions:

( + ) Access to configuration menu.

& + *

If Local Total Reset CLr tot in the instrument configuration menu has been activated, operating the & and * buttons simultaneously for three seconds
will reset the total display to zero and clear any pulses
stored in the optional pulse output.

) + & Grand total - shows Lo followed by least significant 8 digits of the 16 digit grand total.

) + *

Grand total - shows Hi followed by the most significant 8 digits of the 16 digit grand total. If Local Grand Total Reset Clr Gtot in the instrument configuration menu has been activated, operating the ) and * buttons simultaneously for ten seconds will
result in Clr . no being displayed with the no flashing. Operating the * or & button will change the display
to Clr . YE5, the ) button will then reset the grand
total to zero which will be confirmed by a brief display of Gt Clrd.

( + &

Shows in succession, firmware version number, instrument function counter and any output accessories that are fitted:
- A Dual Alarm Outputs - P Pulse output - C 4/20mA output.

( + *

When optional alarms are fitted provides direct access to the alarm setpoints if A5CP (access setpoints) has been enabled in the configuration menu.

4. CONFIGURATION Counters are supplied configured as requested at time of ordering, if not specified default configuration will be supplied but can easily be changed on-site.
Fig 6 shows the location of each function within the configuration menu with a brief summary of the function. Please refer to the full instruction manual for detailed configuration information and optional outputs.
Access to the configuration menu is obtained by pressing the ( and ) buttons simultaneously. If the Counter's security code is set to default 0000 the first parameter input will be displayed. If the instrument is protected by a security code, code will be displayed. The four digit code must be entered to gain access to the menu.

Display mode

DISPLAY

( )

)

code

(

0000

Security Code
Enter code by pressing
& or * & (
to move to next digit. Code 0000
allows direct access to the menu

Unless otherwise specified menu functions are shown on the upper display

Optional pulse output, alarms or 4/20mA output appear here

()

)

)

)

)

)

)

)

)

)

)

)

)

)

)

)

& input *

&

cntedg

* &

update

* &

di5p-1

* &

di5p-2

* &

dP

* &

5cale . t

* &

5cale . r

* &

t-ba5e

* &

filter

* &

up or dn

* &

clr val

* &

Loc clr

*

&

clr gtot

* &

code

* &

r5et def

*

()

)

()

()

()

()

()

()

()

()

()

()

()

()

)

()

()

()

inp . type

* &

debounce

edge1

0 . 5

total

on

00000000

001 . 00

001 . 00

tb-01

24

up

0000000

clr tot

* &

clr gtot

clr . no

0000

0000

()

()

()

()

()

op . col

default

off

off

0000

Input
& or *
to select
Input type
op . col Open Collector.
volt5 l Pulse <1V >3V
volt5 h Pulse <3V >10V
coil Magnetic pick-off.
pr. det Proximity detector.
contact Switch contact.

Debounce
& or *
to select
level of debounce.
default heavy light

Counting edge

Update

& or *
to toggle between
edge1 volts rising edge
and
edge2 volts falling edge

& or *
to select interval between display updates, may be set to 0 . 5, 1, 2, 3, 4 or 5 seconds.

Upper Display
& or *
to select display whether total or rate is shown on upper display

Lower Display
& or *
to turn lower display
on or off

Decimal point
& or *
to select position of
decimal point and
( to toggle
between rate and total displays.

Total scale factor
Dividing factor which defines total display.
& or *
to adjust value
and ( to
move to next digit or decimal point.

Rate scale factor
Dividing factor which defines rate display.
& or *
to adjust value
and ( to
move to next digit or decimal point.

Timebase
& or *
to select rate display timebase.
tb-01 for pulses/sec
tb-60 for pulses/min

Filter input
& or *
to adjust value of each digit
and ( to
transfer control to the next digit.
First digit: filter magnitude

tb-3600

Second digit:

for pulses/hour step response

Note:
While making adjustments the filtered rate display is
shown on lower display so stability can be assessed

Direction of count
& or *
to toggle between up and dn

Reset value
& or *
to adjust value of each digit
and ( to
transfer control to the next digit.

Local total

Local grand

reset

total reset

& or * & or *

to turn the

to turn the

local total

local grand

reset function total reset

on or off.

function

When on is

on or off.

selected, Total

When on,

may be

grand total

reset when

display may

& and * be reset when are pressed ) and *

simultaneously are pressed

for more than 3 simultaneously

seconds in the for more than 10

display mode. seconds in the

display mode.

Grand total reset Press
& or *
to select clr . ye5 to reset grand total to zero
Confirm instruction by entering 5ure.
Press
& or *
to adjust each
digit and (
to move to next digit

Define Security Code
Enter by pressing
& or * and (
to move to next digit.
Default code 0000 allows direct access to configuration
menu

Reset configuration
to factory defaults
Confirm instruction by entering 5ure.
Press
& or *
to adjust each
digit and (
to move to next digit

Fig 6 Configuration menu

Manuals, certificates and datasheets can be downloaded from http://www.beka.co.uk/ba367e-ss

The BA367E-SS is CE marked to show compliance with the European Explosive Atmospheres Directive 2014/34/EU and the European EMC Directive 2014/30/EU.
It is also UKCA marked to show compliance with UK statutory requirements Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations UKSI 2016:1107 (as amended) and with the Electromagnetic Compatibility Regulations UKSI 2016:1091 (as amended).
Fig 6 Configuration menu

