User Manual for NUMERIC models including: 1 kVA FM, 1 kVA FMI, 2 kVA FM, 2 kVA FMI, 3 kVA FM, 3 kVA FMI, ONFINITI plus 1-3 kVA Online UPS Uninterruptible Power Supply System, ONFINITI plus, ONFINITI plus Power Supply System, 1-3 kVA Online UPS Uninterruptible Power Supply System, 1-3 kVA Online UPS Power Supply System, Online UPS Uninterruptible Power Supply System, Online UPS Power Supply System, Online Power Supply System, UPS Power Supply System, Power Supply System, Power Supply

1-3 kVA

Onfiniti⁺ | Numeric UPS

USER AND INSTALLATION MANUAL - Numeric UPS

5 1-4. Operation • Do not disconnect the mains cable in the UPS system or the building wiring outlet (shock-proof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.

USER AND INSTALLATION MANUAL


File Info : application/pdf, 24 Pages, 1.16MB

PDF preview unavailable. Download the PDF instead.

20240412-13260B ONFINITI 1-3kVA UM MidRes
USER AND INSTALLATION MANUAL

NEW ENERGY TO POWER

ONFINITI+
1-3 kVA Online UPS
Uninterruptible Power Supply System

www.numericups.com

PREFACE.
Congratulations, We are delighted to welcome you to our family of customers. Thank you for choosing Numeric as your power backup solution provider; you now have access to our widest network of 254 service centres in the country. Since 1984, Numeric has been enabling its clients to optimize their business with top notch power solutions that promise seamless and clean power with controlled environmental footprints. We look forward to your continued patronage in the years to come! This manual provides general information regarding installation and operation of Onfiniti+.
Disclaimer · The contents of this manual are bound to change without prior
notice. · We have exercised reasonable care to give you an error-free
manual. Numeric disclaims liability for any inaccuracies or omissions that may have occurred. If you find information in this manual that is incorrect, misleading or incomplete, we would appreciate your comments and suggestions. · Before you begin the installation of the UPS system, please read this manual thoroughly. The warranty of this product is null and void, if the product is abused/misused.
2

TABLE OF CONTENTS
Index
Introduction
1. Important Safety Warning 1-1. Transportation 1-2. Preparation 1-3. Installation 1-4. Operation 1-5. Maintenance, service and faults
2. Installation and setup 2-1. Rear panel view 2-2. Setup the UPS
3. Operations 3-1. Button operation 3-2. LCD panel 3-3. Audible alarm 3-4. LCD display wordings index 3-5. UPS setting 3-6. Charging current setting 3-7. Operating mode description 3-8. Faults reference code 3-9. Warning indicator
4. Troubleshooting
5. Storage and Maintenance 5.1 Operation 5.2 Storage 5.3 Disposal
6. Specifications 6-1. UPS without ISO transformer 6-2. UPS with ISO transformer

Page
4
4 4 4 4 5 5
6 6 7
8 8 9 11 11 11 15 16 17 17
18
20 20 20 20
21 21 22
3

Introduction
Onfiniti+ from Numeric is a true on-line double conversion UPS available from a range of 1-3kVA, with and without a transformer. Onfiniti+ is easy to install and is a reliable power solution backed by the widest service support. This user manual covers the UPS listed below:
1. Onfiniti+ 1 kVA FM and Onfiniti+ 1 kVA FMI 2. Onfiniti+ 2 kVA FM and Onfiniti+ 2 kVA FMI 3. Onfiniti+ 3 kVA FM and Onfiniti+ 3 kVA FMI Please verify the model of the UPS you have purchased before you begin your installation.
1. Important Safety Warning
Please comply strictly with all warnings and operating instructions in this manual. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.
1-1. Transportation
· Please transport the UPS system only in the original package to protect against shock and impact.
1-2. Preparation
· Condensation may occur if the UPS system is moved directly from cold to warm environments. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate to the environment.
· Do not install the UPS system near water or in moist environments. · Do not install the UPS system near a heater or where it would be exposed to direct sunlight. · Do not block ventilation holes in the UPS housing.
1-3. Installation
· Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
· Place cables in such a way that no one can step on or trip over them. · Do not connect domestic appliances such as hair dryers to UPS output sockets.
· The UPS can be operated by any individual with no previous experience. · Connect the UPS system only to an earthed shock-proof outlet which must be easily accessible and close to the UPS system. · Please use only VDE-tested, CE-marked, ISI-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shock-proof outlet). · Please use only VDE-tested, CE-marked, ISI-marked power cables to connect the loads to the UPS system. · When installing the equipment, it should be ensured that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5 mA. · The UPS is designed for linear load applications.
4

1-4. Operation
· Do not disconnect the mains cable in the UPS system or the building wiring outlet (shock-proof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
· The UPS system features its own current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
· In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains. · Prevent fluids or other foreign objects from entering into the UPS system.
1-5. Maintenance, service and faults
· The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. CAUTION - Risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system still connected to the battery may be electrically live and dangerous.
· Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as bus capacitors.
· Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries. CAUTION - Risk of electric shock. If the battery circuit is not isolated from the input voltage, hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present.
· Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries: - remove wristwatches, rings and other metal objects - use only tools with insulated grips and handles..
· When changing batteries, install the same number and same type of batteries. · Do not attempt to dispose off batteries by burning them. This could cause battery explosion. · Do not open or destroy batteries. Escaping electrolyte may be toxic and can cause injury to the skin and eyes. · Please replace the fuse only with the same type and amperage in order to avoid fire hazards. · Do not dismantle the UPS system. · Connect UPS to short circuit protected building wiring. · The UPS system has internal fuses on both DC & AC inputs. Those devices do not protect the upstream
cables connected to DC & AC inputs and upstream breakers or fuses shall be set up in accordance with AC & DC wires ratings to meet the local national electrical code standard.
5

2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.
2-1. Rear panel view
UPS without ISO transformer:

3

5

3

5

3

5

4

4

4

6

6

6

2 7
1

1 kVA FM Onfiniti+

UPS with ISO transformer:

USB

RS232

3

5

DANGEROUS DO NOT OPERATE EXCEPT QUALIFIED TECHNICIAN

6 4

2

CIRCUIT BREAKER

7

1

AC INPUT

AC OUTPUT 6A Max

INTELLIGENT SLOT EXTERNAL BATTERY
36Vdc, 50A Max INTELLIGENT SLOT
EXTERNAL BATTERY INTELLIGENT SLOT
EXTERNAL BATTERY

2 7
1
2 kVA FM Onfiniti+

USB

RS232

3

4

DANGEROUS DO NOT OPERATE EXCEPT QUALIFIED TECHNICIAN

6 4

7

2

CIRCUIT BREAKER

1

AC INPUT

AC OUTPUT 6A Max

8

2

7

1

3 kVA FM Onfiniti+

USB

RS232

3

5

DANGEROUS DO NOT OPERATE EXCEPT QUALIFIED TECHNICIAN

6 4

AC OUTPUT 6A Max.

8

LN

CIRCUIT

2

BREAKER

7

1

LN AC INPUT

AC OUTPUT 6A Max

1KVA FMI Onfiniti+

2KVA FMI Onfiniti+

3KVA FMI Onfiniti+

 AC input  Input circuit breaker  USB communication port  RS-232 communication port

 SNMP intelligent slot (optional)  External battery connection  Output receptacles  Output terminal

6

2-2. Setup the UPS

Step 1 UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Please use the below recommended cable & breaker for input.

Model 1 kVA ­ FM/FMI 2 kVA ­ FM/FMI 3 kVA ­ FM/FMI

Wire size in sq. mm./No. of runs 1/3 2.5/3 4/3

Recommended input breaker 10 A (C Curve) 20 A (C Curve) 32 A (C Curve)

Step 2 UPS output connection · For socket-type outputs, simply connect the devices to the outlets. · For terminal-type input or outputs, please follow the steps below, for the wiring configuration: a) Remove the small cover of the terminal block. b) Use AWG14 or 2.1 mm2 power cords. c) Upon completion of the wiring configuration, please check whether the wires are securely affixed. d) Put the small cover back to the rear panel.
Step 3 Communication connection
Communication port:

USB port

RS-232 port

Intelligent slot

To allow for unattended UPS shutdown/start-up and status monitoring, connect one end of the communication cable to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC. The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options.
Note: USB port and RS-232 port can't work at the same time.
Step 4 Turn on the UPS Press the ON/Mute button on the front panel for two seconds to power on the UPS. Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.
Step 5 Install software For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert the provided CD into CD-ROM to install the monitoring software. If not, please follow the on-screen instructions to install the software. When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.

7

Step 6 External battery connection
This UPS series is not including batteries. Batteries are connected in a separate cabinet with protection. Please connect external batteries as per the below chart.

Recommended External Breaker Rating

S. No.

Rating of UPS

Battery Breaker

1

1 kVA - FM/FMI

50 Adc (C Curve)

2

2 kVA - FM/FMI

3

3 kVA - FM/FMI

50 Adc (C Curve) 50 Adc (C Curve)

+
TO EXTERNAL BATTERY

3. Operations
3-1. Button operation

Button
ON/Mute button
OFF/ Enter button
Select button
ON/Mute + Select button

Function
· Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.
· Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system. But it's not applied to the situations when warnings or errors occur.
· Up key: Press this button to display previous selection in UPS setting mode. · Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds
to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
· Turn off the UPS: Press and hold this button for at least 2 seconds to turn off the UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.
· Confirm selection key: Press this button to confirm selection in UPS setting mode.
· Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery voltage, output voltage and output frequency. It will return back to default display when pausing for 10 seconds.
· Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby or Bypass mode.
· Down key: Press this button to display next selection in UPS setting mode.
· Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS will enter Bypass mode. This action will be ineffective when the input voltage is out of acceptable range.

8

3-2. LCD Panel

Input & Battery Voltage Info Battery Info

Remaining Fault Backup Time Info Info

Mute Operation

BATT. FAULT

8 8 H
M S

X

8 8 8 8 8 8 Vac

Vac OVER LOAD

Vdc

Vdc

Hz

Hz

INPUT

OUTPUT

LOW BATT.
I/P

BYPASS

SHORT
O/P

Mode Operation Info

Output & Battery Voltage Info Load Info

Display

Function

Remaining backup time information

Indicates the remaining backup time in pie chart.
Indicates the remaining backup time in numbers. H: hours, M: minute, S: second
Fault information
Indicates the warning and fault occurrences. Indicates the warning and fault codes. The codes are listed in details in section 5-5 .
Mute operation
Indicates that the UPS alarm is disabled.

Output & battery voltage information
Indicates the output voltage, frequency or battery voltage. Vac: output voltage, Vdc: battery voltage, Hz: frequency

9

Display

Function

Load information

Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.

Indicates overload. Indicates the load or the UPS output is short circuit. Mode operation information Indicates the UPS connects to the mains. Indicates the battery is working. Indicates the bypass circuit is working. Indicates the ECO mode is enabled. Indicates the inverter circuit is working. Indicates the output is working. Battery information Indicates the battery level by 0-25%, 26-50%, 51-75%, and 76-100%.

Indicates the battery is fault.
Indicates low battery level and low battery voltage.
Input & battery voltage information Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery voltage, Hz: input frequency

10

3-3. Audible Alarm

Battery Mode Low Battery Overload Fault Bypass Mode

Sounds every 4 seconds Sounding every second Sounding twice every second Sounds continuously Sounds every 10 seconds

3-4. LCD display wordings index

Abbreviation ENA DIS ESC HLS LLS BAT CF TP CH FU EE
3-5. UPS Setting

Display content
EnA dI S ESC HLS LLS bA CF P CH FU EE

Meaning Enable Disable Escape High loss Low loss Battery Converter Temperature Charger Bypass frequency unstable EEPROM error

Parameter 1
88 888 888

Parameter 2

Parameter 3

There are three parameters to set up the UPS.
Parameter 1: It's for program alternatives. Refer to the below table.
Parameter 2 and parameter 3 are the setting options or values for each program.

11

01: Output voltage setting Interface
0 1 2 3 0 Vac
OUTPUT
02: Frequency converter enable/disable Interface
02 CF EnA

Setting
Parameter 3: Output voltage For 200/208/220/230/240 Vac models, you may choose the following output voltage: 200: Presents output voltage is 200 Vac 208: Presents output voltage is 208 Vac 220: Presents output voltage is 220 Vac 230: Presents output voltage is 230 Vac (Default) 240: Presents output voltage is 240 Vac
Setting
Parameter 2 & 3: Enable or disable converter mode. You may choose the following two options: CF ENA: Converter mode enable CF DIS: Converter mode disable (Default)

03: Output frequency setting Interface
03 C F 5 O O Hz
OUTPUT

Setting
Parameter 2 & 3: Output frequency setting. You may set the initial frequency on battery mode: BAT 50: Presents output frequency is 50 Hz BAT 60: Presents output frequency is 60 Hz If converter mode is enabled, you may choose the following output frequency: CF 50: Presents output frequency is 50 Hz CF 60: Presents output frequency is 60 Hz

12

04: ECO enable/disable Interface
04 EnA

Setting
Parameter 3: Enable or disable ECO function. You may choose the following two options: ENA: ECO mode enable DIS: ECO mode disable (Default)

05: ECO voltage range setting Interface
05 H L S 2 6 0 Vac
INPUT
06: Bypass enable/disable when UPS is off Interface

Setting
Parameter 2 & 3: Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key. HLS: High Loss Voltage in ECO mode in parameter 2. For 200/208/220/230/240 Vac models, the setting range inparameter 3 is from +7 V to +24 V of the nominal voltage. (Default: +12 V) LLS: Low Loss Voltage in ECO mode in parameter 2. For 200/208/220/230/240 Vac models, the setting range in parameter 3 is from -7 V to -24 V of the nominal voltage. (Default: -12 V)
Setting

06 EnA
BYPASS

Parameter 3: Enable or disable Bypass function. You may choose the following two options: ENA: Bypass enable DIS: Bypass disable (Default)

13

07: Bypass voltage range setting Interface
07 H L S 2 6 0 Vac
INPUT BYPASS
08: Autonomy limitation setting Interface
M 08 999
09: Battery minimum cut-off voltage setting Interface

Setting
Parameter 2 & 3: Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key. HLS: Bypass high voltage point For 200/208/220/230/240 Vac models: 230-264: Setting the high voltage point in parameter 3 from 230 Vac to 264 Vac. (Default: 264 Vac) LLS: Bypass low voltage point For 200/208/220/230/240 Vac models: 170-220: Setting the low voltage point in parameter 3 from 170 Vac to 220 Vac. (Default: 170 Vac)
Setting
Parameter 3: Set backup time on battery mode for general outlets. 0-999: Setting the backup time in minutes from 0-999 for general outlets on battery mode. 0: When setting as "0", the backup time will be only 10 seconds. 999: When setting as "999", the backup time setting will be disabled. (Default)
Setting

09 b C 0 1 6 7 Vdc

Parameter 3: Set the acceptable battery minimum cut-off voltage point by pressing the Down key or Up key. 167-190: Setting the minimum battery cut-off voltage point in parameter 3 from 167 to 190. Unit: 0.01 V/CELL (Default: 175)

14

10: Charger boost voltage setting Interface
10 C b u 2 3 6 Vdc

Setting
Parameter 3: Set up the charger boost voltage. 225-240: Setting the charger boost voltage point in parameter 3 from 225 to 240. Unit: 0.01 V/CELL (Default: 236)

11: Charger float voltage setting Interface
1 1 C F u 2 2 8 Vdc

Setting
Parameter 3: Set up the charger float voltage. 220-233: Setting the charger float voltage point in parameter 3 from 220 to 233. Unit: 0.01 V/CELL (Default: 228)

00: Exit setting
3-6. Charging current setting

3 bat (36 V)/6 bat (72 V)/8 bat (96 V) J1 J2 J3 J4 (Default)

For 10 A Model 1 Adc 2 Adc 5 Adc 10 Adc

15

3-7. Operating mode description

Operating mode

Description

LCD display

Online mode

When the input voltage is within the acceptable range, UPS will provide pure and stable AC power to output. The UPS will also charge the battery at online mode.

2 3 0 2 3 0 Vac

Vac

INPUT

OUTPUT

I/P

O/P

ECO mode
Frequency converter mode
Battery mode

Energy saving mode: When the input voltage is within the voltage regulation range, UPS will bypass voltage to output for energy saving.
When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge the battery under this mode.
When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 seconds, UPS will backup power from battery.

2 3 0 2 3 0 Vac

Vac

INPUT

OUTPUT

I/P

BYPASS

O/P

CF

2 3 0 2 3 0 Vac

Vac

INPUT

OUTPUT

I/P

O/P

M 4.8
72.0 2 3 0 Vac Vac OUTPUT
O/P

Bypass mode

When input voltage is within the acceptable range but UPS is overloaded, UPS will enter Bypass mode or Bypass mode can be set by front panel. Alarm sounds every 10 seconds.

2 3 0 2 3 0 Vac

Vac

INPUT

OUTPUT

I/P

BYPASS

O/P

Standby mode

UPS is powered off and no output supply power, but still can charge batteries.

2 3 0 0 Vac

Vac

INPUT

OUTPUT

I/P

16

3-8. Fault reference codes

Fault event Bus start fail Bus over Bus under Bus unbalance Inverter soft start fail Inverter voltage high Charger fail

Fault code 01 02 03 04 11 12 45

3-9. Warning indicator

Fault event Inverter voltage low Inverter output short Battery voltage too high Battery voltage too low Over temperature Overload

Fault code 13 14 27 28 41 43

Warning Low Battery Overload Battery is not connected

Icon (flashing)

Alarm Sounding every second Sounding twice every second Sounding every second

Over charge

Sounding every second

Over temperature Charger failure Battery fault Out of bypass voltage range Bypass frequency unstable EEPROM error

Sounding every second Sounding every second Sounding every second Sounding every second Sounding every second Sounding every second

17

4. Troubleshooting

If the UPS system does not operate correctly, please solve the problem by using the table below.

Symptom

Possible cause

The AC input power is not No indication and alarm even connected well. though the mains is normal.
The AC input is connected to the UPS output.

Remedy
Check if input power cord firmly connected to the mains.
Plug AC input power cord to AC input correctly.

The icon and flashing The external or internal

on LCD display and alarm is battery is incorrectly

sounding every second.

connected.

Check if all batteries are connected well.

Fault code is shown as

27 and the icon

is

lighting on LCD display

and alarm is continuously

sounding.

Fault code is shown as

28 and the icon

is

lighting on LCD display

and alarm is continuously

sounding.

Battery voltage is too high or the charger is fault.

Contact your dealer.

Battery voltage is too low or the charger is faulty.

Contact your dealer.

UPS is overloaded.

Remove excess loads from UPS output.

The icon and is flashing on LCD display and alarm is sounding twice every second.

UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass.

Remove excess loads from UPS output.

After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains.

Remove excess loads from UPS output first. Then shut down the UPS and restart it.

Fault code is shown as

43 and the icon

is

lighting on LCD display

and alarm is continuously

sounding.

The UPS shutdown automatically because of overload at the UPS output.

Remove excess loads from UPS output and restart it.

Fault code is shown as

14 and the icon

is

lighting on LCD display

and alarm is continuously

sounding.

The UPS shutdown automatically because short circuit occurs on the UPS output.

Check output wiring and if connected devices are in short circuit status.

18

Symptom

Possible cause

Fault code is shown as 45 on LCD display and alarm is continuously sounding.

Charger is faulty.

Remedy Contact your dealer.

Fault code is shown as 01, 02, 03, 04, 11, 12, 13 and 41 on LCD display and alarm is continuously sounding.

A UPS internal fault has occurred. There are two possible results:

1. The load is still supplied, but directly from AC

Contact your dealer

power via Bypass.

2. The load is no longer supplied by power.

Battery backup time is shorter than nominal value

Batteries are not fully charged

Batteries defect

Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer.
Contact your dealer to replace the battery.

If the problem persists, visit www.numericups.com to register your service request and contact our nearest after sales service department; or contact us.: 0484-3103266 / 4723266 with the below details:.
1 Model number, Serial number 2. Date on which the problem occurred 3. LCD/LED display status, Buzzer alarm status 4. Utility power condition, load type and capacity, environment temperature, ventilation condition 5. The information (battery capacity, quantity) of external battery pack if the UPS is with external battery 6. Other information for complete description of the problem

19

5. Storage and Maintenance
5.1 Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
Be sure to deliver the used battery to a recycling facility or ship it to your dealer in the replacement battery packing material.

5.2 Storage

Before storing, charge the UPS for 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:

Storage temperature -25°C to 40°C 40°C to 45°C

Recharge frequency Every 3 months Every 2 months

Charging duration 1-2 hours 1-2 hours

5.3 Disposal
Ref standard: ISO 14001: 2015
· After unpacking the UPS & Battery, the removed packaging materials like polythene paper, thermocole/ polyethylene, carton box, nylon belt, nylon thread shall be collected and disposed through authorized recycler.
· Batteries when found faulty/damaged must be handed over to identified authorized recycler or to Numeric, where it is disposed properly.
· Battery contains harmful metals and chemicals such as nickel-cadmium, alkaline, mercury, nickel-metal hydride and lead acid, which contaminates if it is not disposed properly.
· When batteries containing cadmium is used in fills, they will eventually dissolve and release the toxic substance than can seep into water supplies posing serious health hazards for the population/society. Hence, recycling of batteries will prevent pollution and also saves resource.

20

6. Specifications

6-1. UPS without ISO transformer

NOMINAL POWER* (KVA)
PID Active power** INPUT
Low line transfer

Voltage range

Low line comeback

High line transfer

High line comeback

Frequency range

Phase

Power factor

OUTPUT

Output voltage

AC voltage regulation

Frequency range (Synchronized)

Frequency range (Battery mode)

Overload

Current crest ratio

Harmonic distortion

Transfer AC mode to battery mode

Time

Inverter to Bypass

Waveform (Battery mode)

EXTERNAL BATTERY

Battery type

Battery numbers

Maximum battery AH

Current of external BAT pack

Charging current 10 A model (FM)

Charging voltage

PHYSICAL

Dimension W x D x H (in mm)

Net weight (kgs)

ENVIRONMENT

Operation humidity

Noise level

MANAGEMENT

Smart RS-232 or USB

Optional SNMP

1 KVA FM
NU 72 01 701 1000 VA/800 W

2 KVA 72 V FM 2 KVA 96 V FM

NU 72 01 703

NU 72 01 705

2000 VA/1600 W

3 KVA 72 V FM 3 KVA 96 V FM

NU 72 01 707

NU 72 01 709

3000 VA/2400 W

160/140/120/110 Vac ± 5% (based on load percentage 100% - 80%/80% - 70%/70 - 60%/60% - 0)
175/155/135/125 Vac ± 5 % (based on load percentage 100% - 80%/80% - 70%/70 - 60%/60% - 0)
300 Vac ± 5% 290 Vac ± 5% 40 Hz ~ 70 Hz Single phase with ground  0.99 @ nominal input voltage
200/208/220/230/240 Vac ± 1%
46 - 54 Hz or 56 - 64 Hz 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz 105%~110%: UPS shuts down after 10 min at battery mode or transfer to Bypass when the utility is normal 110%~130%: UPS shuts down after 1 min at battery mode or 2 min transfer to Bypass when the utility is normal 130%~150%: UPS shuts down after 3 secs at battery mode or 30 secs transfer to Bypass when the utility is normal
3:1  3% THD (Linear load);  5% THD (Non-linear load)
Zero 4 ms (Typical) Pure sinewave

3 120 30 Adc max
41.0 Vdc ± 1%

Depending on the capacity of external batteries

6

8

6

120

100

120

30 Adc max

30 Adc max

45 Adc max

1 / 2 / 5 / 10 A (adjustable)

82.1 Vdc ±1%

109.5 Vdc ±1%

82.1 Vdc ±1%

8 100 32 Adc max
109.5 Vdc ±1%

145 x 290 x 225 4.9

145 x 397 x 238

7.9

8.3

20-90% RH @ 0- 40°C (non-condensing) Less than 50 dBA @ 1 Meter (AVG)

Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC Power management from SNMP manager and web browser

*FM - Floor Mount; FMI - Floor Mount with isloation transformer. **Derate capacity to 80% of capacity in frequency converter mode or when the output voltage is adjusted to 208. Vac/200 Vac. Product specifications are subject to change without further notice.

21

6. Specifications

6-2. UPS with ISO transformer

NOMINAL POWER* (KVA)
PID Active power** INPUT
Low line transfer

Voltage range

Low line comeback

High line transfer

High line comeback

Frequency range

Phase

Power factor

OUTPUT

Output voltage

AC voltage regulation

Frequency range (Synchronized)

Frequency range (Battery mode)

Overload

Current crest ratio

Harmonic distortion

Transfer AC mode to battery mode

Time

Inverter to Bypass

Waveform (Battery mode)

EXTERNAL BATTERY

Battery type

Battery numbers

Maximum battery AH

Current of external BAT pack

Charging current 10 A model (FM)

Charging voltage

PHYSICAL

Dimension W x D x H (in mm)

Net weight (kgs)

ENVIRONMENT

Operation humidity

Noise level

MANAGEMENT

Smart RS-232 or USB

Optional SNMP

1 KVA FMI
NU 72 01 702 1000 VA/800 W

2 KVA 72 V FMI 2 KVA 96 V FMI

NU 72 01 704

NU 72 01 706

2000 VA/1600 W

3 KVA 72 V FMI 3 KVA 96 V FMI

NU 72 01 708

NU 72 01 710

3000 VA/2400 W

160/140/120/110 Vac ± 5% (based on load percentage 100% - 80%/80% - 70%/70 - 60%/60% - 0)
175/155/135/125 Vac ± 5% (based on load percentage 100% - 80%/80% - 70%/70 - 60%/60% - 0)
300 Vac ± 5% 290 Vac ± 5% 40 Hz ~ 70 Hz Single phase with ground  0.99 @ nominal input voltage
200/208/220/230/240 Vac ± 2%
46 - 54 Hz or 56 - 64 Hz 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz 105%~110%: UPS shuts down after 10 min at battery mode or transfer to Bypass when the utility is normal 110%~130%: UPS shuts down after 1 min at battery mode or 2 min transfer to Bypass when the utility is normal 130%~150%: UPS shuts down after 3 secs at battery mode or 30 secs transfer to Bypass when the utility is normal
3:1  3% THD (Linear load);  5% THD (Non-linear load)
Zero 4 ms (Typical) Pure sinewave

3 120 30 Adc max
41.0 Vdc ± 1%

Depending on the capacity of external batteries

6

8

6

120

100

120

30 Adc max

30 Adc max

45 Adc max

1 / 2 / 5 / 10 A (adjustable)

82.1 Vdc ±1%

109.5 Vdc ±1%

82.1 Vdc ±1%

8 100 32 Adc max
109.5 Vdc ±1%

145 x 290 x 458 26

145 x 397 x 458

35

36

20-90% RH @ 0- 40°C (non-condensing) Less than 50 dBA @ 1 Meter (AVG)

Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC Power management from SNMP manager and web browser

*FM - Floor Mount; FMI - Floor Mount with isloation transformer. **Derate capacity to 80% of capacity in frequency converter mode or when the output voltage is adjusted to. 208 Vac/200 Vac. or operating temperature is > 40 deg C and > 50 deg C Product specifications are subject to change without further notice.

22

23

Head Office
10th Floor, Prestige Center Court, Office Block, Vijaya Forum Mall, 183, N.S.K Salai, Vadapalani, Chennai - 600 026. Phone: +91 44 4656 5555
Regional Offices
New Delhi B-225, Okhla Industrial Area, 4th Floor, Phase-1, New Delhi - 110 020. Phone: +91 11 2699 0028
Kolkata Bhakta Tower, Plot No. KB22, 2nd & 3rd Floor, Salt Lake City, Sector - III, Kolkata - 700 098. Phone : +91 33 4021 3535 / 3536
Mumbai C/203, Corporate Avenue, Atul Projects, Near Mirador Hotel, Chakala, Andheri Ghatkopar Link Road, Andheri (East), Mumbai - 400 099. Phone : +91 22 3385 6201
Chennai 10th Floor, Prestige Center Court, Office Block, Vijaya Forum Mall, 183, N.S.K Salai, Vadapalani, Chennai - 600 026. Phone : +91 44 3024 7236 / 200
Branch Offices
Chandigarh SCO 4, First Floor, Sector 16, Panchkula, Chandigarh - 134 109. Phone : +91 93160 06215
Dehradun Unit-1 and 2, Chakrata Road, Vijay Park Dehradun ­ 248001. Uttrakhand Phone : +91 135 661 6111
Jaipur Plot No. J-6, Scheme-12B, Sharma Colony, Bais Godown, Jaipur - 302 019. Phone : +91 141 221 9082

Lucknow 209/B, 2nd Floor, Cyber Heights, Vibhuti Khand, Gomti Nagar, Lucknow - 226 018. Phone : +91 93352 01364
Bhubaneswar N-2/72 Ground Floor, IRC Village, Nayapally, Bhubaneswar - 751 015. Phone: +91 674 255 0760
Guwahati House No 02, Rajgarh Girls High School Road (Behind Rajgarh Girls High School), Guwahati - 781 007. Phone : +91 96000 87171
Patna 405, Fraser Road, Hemplaza, 4th Floor, Patna - 800 001. Phone : +91 612 220 0657
Ranchi 202 & 203, 2nd Floor, Sunrise Forum, Bardwan Compound, Lalpur, 2nd Floor, Ranchi - 834 001. Phone : + 91 98300 62078
Ahmedabad A-101/102, Mondeal Heights, Beside Hotel Novotel, Near Iscon Circle, S G Highway, Ahmedabad - 380 015. Phone : +91 79 6134 0555
Bhopal Plot No. 2, 221, 2nd Floor, Akansha Complex, Zone-1, M.P.Nagar, Bhopal­ 462 011. Phone : +91 755 276 4202
Nagpur Plot.No.174, H.No.4181/C/174, 1st Floor, Loksewa Housing Society, Near Dr. Umathe & Mokhare College, Bhamti Road, Lokseva Nagar, Nagpur - 440 022. Phone : +91 712 228 6991 / 228 9668

Pune Pinacle 664 park avenue, 8th floor, Plot no 102+103, CTS No. 66/4, Final, 4, Law College Rd, Erandwane, Pune, Maharashtra - 411 004. Phone : +91 +20 6729 5624
Bengaluru No-58, First Floor, Firoze White Manor, Bowring Hospital Road, Shivajinagar, Bangalore -560 001. Phone : +91 80 6822 0000
Coimbatore No. B-15, Thirumalai Towers, No. 723, 1st Floor, Avinashi Road, Coimbatore - 641 018. Phone : +91 422 420 4018
Hyderabad Prestige Phoenix Building, 1st Floor, Survey no. 199, No. 6-3-1219/J/101 & 102, Uma Nagar, Opposite to Begumpet Metro Station Begumpet 500016 Phone: +91 40 4567 1717/2341 4398/2341 4367
Kochi Door No. 50/1107A9, JB Manjooran Estate, 3rd Floor, Bypass Junction, Edappally, Kochi ­ 682 024. Phone : +91 484 6604 710
Madurai 12/2, DSP Nagar, Dinamalar Avenue, Madurai - 625 016. Phone : +91 452 260 4555

Contact us.: Email : customer.care@numericups.com Phone : 0484-3103266 / 4723266 www.numericups.com



References

Adobe InDesign 14.0 (Windows) Adobe PDF Library 15.0