AQ251486498741en-010607
Operating Guide
NovoCon® S - High Accuracy Actuator



IP54





NovoCon® S / 73690900


IP54

IP54

 DN 15 - 32
NO presetting!

DN 15, 20 10 [100 %]



DN 25, 32 100 %





Manuel Calibration: Press button  until two LED's are turned on, and then release again. DIP switch:  Manual override: Adjust wheel 











Common ground shall be used for all devices on the same network.

NovoCon® digital cable

Red Black Green

Power Common ground for power and bus signal wire ´+´ non-inverting signal wire

White/green ´-´ inverting signal wire

Actuator NovoCon® Actuator NovoCon®

ChangeOver6

ChangeOver6 Energy

Purple O-ring

Blue O-ring

NovoCon® Energy cable - PT1000 surface sensors

NovoCon® I/O cable

NovoCon® Energy cable - PT1000 immersed sensors

Cable NovoCon® Temperature I/O

Digital port
Port for CO6 actuator or Energy cable, I/O cable, analog cable or voltage booster.
Digital port

NovoCon® analog cable Red

Power 24V

Black GND

Grey Analog input or Flow sensor

Blue Analog input ground

Actuator NovoCon® ChangeOver6 Flexible

Red

Power 24V

Black GND

White CO6 Control signal

Grey CO6 Feedback signal

Red Black Blue Grey White Yellow Orange
Red Black Blue Grey White

Power 24V Power ground Ground T1, T2, V/mA input & V output signal V/mA input signal or Flow sensor V output signal T1, resistance input or Flow sensor T2, resistance input or Flow sensor
Power 24V (in/out) Power ground (in/out) Ground T1, T2, V/mA input & V output signal V/mA input signal or Flow sensor V output signal T1 T2

© Danfoss | 2024.05

AQ251486498741en-010607 | 1

NovoCon® S - High Accuracy Actuator



NovoCon®S
003Z8504
Actuator for AB-QM DN10-32
Control signal: BACnet MS/TP, Modbus RTU, 0-10V, 0-20mA

Power: 24VAC/DC, 50/60 HZ

Force: 90N. Stroke: 7 mm. Speed: 3-24s/mm

Consumption: 3.3VA running. Standby 0.9W

III

IP54/40, -10T55

E100 VX01X 281624 0030471

6430 Nordborg, Denmark MADE IN SLOVENIA

E100 VX01X 281624 0030471


Serial number and QR code can be removed from the NovoCon® S label and added to installation drawing.

E100 VX01X 281624 0030471

Device Object Instance Number


DIP Switch 1 2 3 4 5 6 7 8 9 10 ON OFF

DIP Switches 1 to 7 are used to assign the MAC address manually. Default MAC address assignment method is Auto MAC addressing for BACnet MS/TP and DIP Switches for Modbus RTU. For termination of last unit on the field bus, turn DIP Switch 8 ON. Dip switch 9 is not used. Dip switch 10 is used to select between BACnet MS/TP (OFF=Default) and Modbus RTU (ON). When the protocol is changed on DIP Switch 10, a power cycle is required.



Optional step (connecting flow sensor)

Cable NovoCon® I/O 24 V GND GND AI AO T1 T2

Sharky FS 473 flow sensor
Wire Description Brown Ground (-) White Volume pulse output (+)

 Initial configuration

NovoCon® S

Application mode:

MSV:9 / 32810



Digital control (default), Analog control, CO6 mode,
Inverted CO6 mode, CO6 without alarms, Inverted CO6 without alarms,



Select Valve Type MSV:3 / 32802
(default AB-QM 4.0 ISO DN 15)

Select application
  MSV:10 / 32811 Heating (default) Cooling

Design Flow Rate AV:30 / 32796 Heating AV:31 / 32798 Cooling

Activate calibration
 MSV:0 / 33284 state 2 or use manual calibration

Analog CO6 mode,

Analog inverted CO6 mode

 Safety Note To avoid injury and damage to persons and devices, it is absolutely necessary these instructions are carefully read and observed prior to assembly and commissioning. Necessary assembly, start-up, and maintenance work must be performed only by qualified, trained and authorised personnel. Switch off the power line before wiring the actuator.
Safety Note
Connect via safety isolating transformer. Galvanic separations shall be provided for segments crossing buildings.

Safety Note
If the NovoCon® S network is supplied with two or more AC power boosters, caution must be observed when disconnecting one of the transformers from the high voltage power line. As the NovoCons are connected in a daisy chain, there may be high voltage on the primary side of the disconnected power supply. Disconnect always both the primary and secondary side of the transformer.
Firmware update
We recommend to validate the firmware version before installation. The latest firmware can be downloaded at www.novocon.com by selecting the tab: Support files.

The following information is provided with the product documentation or marked on the product: A) Purpose of control: Operating Control. B) Construction of control: Independently Mounted. C) Type 1 Action. D) Pollution Degree: 3. E) Impulse Voltage: 500 V. F) Type of movement: Linear. G) Mechanical and thermal ratings (ref. to Ratings section for more details). H) Main power supply for actuator and "Input control signal" shall be provided by the same SELV/Class 2 circuit.
: UA:    « » 04080,  80, / 168, 

2 | © Danfoss | DCS-SGDPT/SI | 2024.05

73690900 / AQ251486498741en-010607

