The Goodman AR Commercial Electric Air Handler series offers robust solutions for A/C and heating pump split systems, available in 7½-ton and 10-ton models.
Standard Features
- Upflow or horizontal (left side) installation positions for 7½- and 10-ton cooling-only or heat pump applications.
- 10-ton model is circuited for use with two 4- or 5-ton cooling-only or heat pump systems, or one 10-ton cooling-only or heat pump system.
- All models are convertible to 460-3-60 from 208/230-3-60.
- Includes transformer and blower relay.
- TXV control: 7½-ton unit has one (1) thermal expansion check valve; 10-ton unit has two (2) thermal expansion check valves.
- Features a draw-thru centrifugal blower, belt-driven for quiet, efficient operation.
- Equipped with copper tube/aluminum fin coils.
Cabinet Features
- Constructed with a heavy-gauge, reinforced, galvanized-steel cabinet.
- Fully insulated with fiberglass blanket.
- Includes horizontal and vertical condensate pans.
- Built-in filter rack accommodates a 2” filter (included).
- Entry on top of the panel for both low and high voltage connections.
- Removable access panels facilitate faster and easier servicing.
Accessories
- 15-30 kW electric heat kits are available as field-installed options.
[5-year warranty icon] [ETL Certified icon] [AHRI Certified icon] *Complete warranty details available from your local dealer or at www.goodmanmfg.com.
NOMENCLATURE
The model number provides specific product information:
Code | Description |
---|---|
A | Brand: Single-piece Air Handler |
R | Unit Application: Multi-Position PSC Motor |
090 | Nominal Capacity Range: 7½ tons |
120 | Nominal Capacity Range: 10 Tons |
1, 2, 3,4,5, 6 | Engineering: Major/Minor Revisions (Not used for inventory management) |
SPECIFICATIONS
AR090A | AR120A | |||
---|---|---|---|---|
Cooling/Heating Capacities | ||||
Cooling (BTU/h) | 90,000 | 120,000 | ||
Heating (kW) | 15, 20, 30 | 15, 20, 30 | ||
CFM | 3,000 | 4,000 | ||
ELECTRICAL | ||||
Unit volts | 208/240/460 | 208/240/460 | ||
Hertz/ Phase | 60/3 | 60/3 | ||
Voltage Range | 187-253 / 414-506 | 187-253 / 414-506 | ||
FLA (Total) | 5.2 | 6 | ||
Minimum Circuit Ampacity | 6.5 / 3.3 | 7.5 / 3.8 | ||
BLOWER MOTOR TYPE | ||||
Type | Belt Drive | Belt Drive | ||
Horse Power | 1½ | 2 | ||
Volts | 208/230/460 | 208/230/460 | ||
Hertz/ Phase | 60/3 | 60/3 | ||
FLA/LRA | 5.2 / 35 | 6.0 / 32 | ||
BLOWER & CONTROLS | ||||
Wheel Dia. & Width (Qty.) | 11 x 10 (2) | 11 x 10 (2) | ||
Pulley Pitch Dia. | 5.9" | 6.5" | ||
Bore | 1" | 1" | ||
Motor Pulley Pitch Dia. | 1.9 to 2.9" | 2.8 to 3.8" | ||
Bore | 5/8" | 5/8" | ||
Belt Length & Width | 39 x 1½ | 41 x 1½ | ||
Nominal Airflow (Ft./Min.) | 3,000 | 4,000 | ||
Transformer (60 VAC.) | Standard | Standard | ||
Blower Relay | Standard | Standard | ||
FILTER, COIL & REFRIGERANT | ||||
Filter Size (Disposable) / Qty | 16" x 20" x 2" / 4 | 16" x 20" x 2" / 2 20" x 20" x 2" / 2 |
||
Coil Area (sq. ft.) | 9 | 10 | ||
FPI - Rows | 14 - 4 | 14 - 4 | ||
Metering Device (Qty.) | Expansion Valve (1) | Expansion Valve (2) | ||
Refrigerant | R-410A | R-410A | ||
Liquid Connection (Qty.) | 5/8" | 3/8" (2) * | ||
Suction Connection (Qty.) | 1¼" | 1¼" (2) * | ||
Condensate Drain | ¾" FPT | ¾" FPT | ||
SHIP WEIGHT (LBS) | 405 | 430 |
* For two refrigerant lines
ELECTRIC HEATER KITS
AR Series Air handlers do not have factory-installed electric heat. They are purchased as an accessory. These are the ONLY heater kits that can be used with the AR Series. The electrical characteristics of the air handler, electric heater kits, and building power supply must be compatible.
AHKD Model | Nominal kW | ELECTRICAL DATA | STAGES | WEIGHT (LBS.) | MAX. OVERCURRENT PROTECTION |
---|---|---|---|---|---|
AHKD15-3 | 15 | 208-230/3/60 | 1 | 56 | 60 |
AHKD15-4 | 15 | 460/3/60 | 1 | 55 | 30 |
AHKD20-3 | 20 | 208-230/3/60 | 2 | 59 | 70 |
AHKD20-4 | 20 | 460/3/60 | 2 | 57 | 35 |
AHKD30-3 | 30 | 208-230/3/60 | 2 | 60 | 100 |
AHKD30-4 | 30 | 460/3/60 | 2 | 58 | 50 |
Temperature Rise (°F)
AR090A
MODEL | HEAT KIT KW | CFM | SUPPLY VOLTAGE | ||
---|---|---|---|---|---|
208 | 240 | 480 | |||
15 | 2,800 | 14 | 19 | 19 | |
2,900 | 14 | 18 | 18 | ||
3,000 | 13 | 18 | 18 | ||
3,100 | 13 | 17 | 17 | ||
3,200 | 12 | 17 | 17 | ||
AR090A | 20 | 2,800 | 19 | 25 | 25 |
2,900 | 18 | 24 | 24 | ||
3,000 | 18 | 24 | 24 | ||
3,100 | 17 | 23 | 23 | ||
3,200 | 17 | 22 | 22 | ||
30 | 2,800 | 28 | 38 | 38 | |
2,900 | 27 | 37 | 37 | ||
3,000 | 27 | 35 | 35 | ||
3,100 | 26 | 34 | 34 | ||
3,200 | 25 | 33 | 33 |
AR120A
MODEL | HEAT KIT KW | CFM | SUPPLY VOLTAGE | ||
---|---|---|---|---|---|
208 | 240 | 480 | |||
10 | 3,800 | 14 | 14 | 14 | |
3,900 | 14 | 14 | 14 | ||
15 | 4,000 | 13 | 13 | 13 | |
4,100 | 13 | 13 | 13 | ||
4,200 | 9 | 13 | 13 | ||
AR120A | 20 | 3,800 | 14 | 19 | 19 |
3,900 | 14 | 18 | 18 | ||
4,000 | 13 | 18 | 18 | ||
4,100 | 13 | 17 | 17 | ||
4,200 | 13 | 17 | 17 | ||
30 | 3,800 | 21 | 28 | 28 | |
3,900 | 20 | 27 | 27 | ||
4,000 | 20 | 27 | 27 | ||
4,100 | 19 | 26 | 26 | ||
4,200 | 19 | 25 | 25 |
* Tables above are calculated with both stages of electric heat engaged (2-stage heat systems). Divide the temperature rise from the table by 2 for 1st stage operation for systems using staged electric heat.
AIR DELIVERY
AR090A Air Delivery*
STATIC PRESSURE | MOTOR SHEAVE TURNS OPEN | ||||
---|---|---|---|---|---|
0 | 1 | 2 | 3 | 4 | |
0.1" | 4,264 | 3,930 | 3,633 | 3,273 | |
0.2" | 3,996 | 3,705 | 3,235 | 2,998 | |
0.3" | 3,731 | 3,379 | 3,002 | 2,517 | |
0.4" | 3,445 | 3,066 | 2,613 | ||
0.5" | 3,113 | 2,662 |
* With dry coil and 2" air filter
AR120A DELIVERY*
STATIC PRESSURE | MOTOR SHEAVE TURNS OPEN | |||||
---|---|---|---|---|---|---|
0 | 1 | 2 | 3 | 4 | 5 | |
0.1" | 5,193 | 5,037 | 4,790 | 4,529 | 4,097 | 4,097 |
0.2" | 5,012 | 4,873 | 4,603 | 4,315 | 3,842 | 3,842 |
0.3" | 4,852 | 4,675 | 4,393 | 4,091 | 3,589 | 3,589 |
0.4" | 4,687 | 4,484 | 4,172 | 3,853 | 3,295 | 3,073 |
0.5" | 4,501 | 4,268 | 3,939 | 3,561 | 2,922 | 2,610 |
0.6" | 4,293 | 4,041 | 3,673 | 3,223 | 2,642 | |
0.7" | 4,073 | 3,782 | 3,347 | 2,892 | ||
0.8" | 3,807 | 3,485 | 2,962 | |||
0.9" | 3,540 | 3,117 |
* With dry coil and 2" air filter
Note: Any adjustment made to the blower should not cause the motor to draw more than the motor's rated RLA. Applications that exceed the above could require a larger motor.
FILTERS
MODEL | FILTER SIZE |
---|---|
AR090A | 16" x 20" x 2" |
AR120A | 16" x 20" x 2" 20" x 20" x 2" |
DIMENSIONS
Diagram showing top and side views of the air handler with key dimensions labeled. Key connection points include Power Inlet Opening, Elec. Heat, 1-1/8" Sweat (AR090), 1-1/8" Sweat (AR120), Blower & Control Access, 5/8" Liquid Line (AR090), 3/8" Liquid Line (AR120), Coil Access, and Drain. Overall dimensions are approximately 24" height and 48-1/8" length.
Note: AR090A (1) 5/8" Liquid Line, AR120A (2) 3/8" Liquid Line.
DUCT CONNECTION SIZING WITHOUT ELECTRIC HEATERS
MINIMUM SUPPLY AND RETURN DUCT DIMENSIONS
Dimensional Data for Electric Heater Kits
- 15, 20, & 30 kW Heater Kits
- Supply opening is 13½" x 40½"
SUPPLY DUCT | RETURN DUCT | |||
---|---|---|---|---|
A | B | C | D | |
13½" | 40" | 24" | 48" |
Diagram illustrating supply and return duct connections with labels A, B, C, D and dimensions.
WIRING DIAGRAM
Diagram shows the electrical connections for supply voltage (L1, L2, L3), contactor, transformer, blower relay (sequencer), and evaporator motor. It details factory wiring for 240V and instructions for changing voltage (240V to 208V, 240V to 460V) and rewiring the motor for high voltage (480V) or low voltage (240V) based on model (AR090 or AR120).
Notes:
- 1) All replacement wires must be same gauge and type.
- 2) To change voltage from 240V to 208V, move wire from 240V tap to 208V tap at transformer primary.
- 3) To convert voltage from 240V to 460V: a) Move wire from 240V tap to 480V tap at transformer primary. b) Identify model (i.e. AR090 or AR120) and rewire motor from low voltage (240V) to high voltage (480V) according to instructions below.
COLOR CODE
B | BLACK | GORW | ORANGE |
BL | BLUE | R | RED |
BR | BROWN | W | WHITE |
G | GREEN |
WIRING CODE
FACTORY WIRING | HIGH VOLTAGE | ||
LOW VOLTAGE | |||
FIELD WIRING | HIGH VOLTAGE | ||
LOW VOLTAGE |
Diagrams for A.O. Smith Motors (AR120, AR090) showing high voltage (480V) and low voltage (240V) connections.
[⚠️] High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.
Wiring is subject to change. Always refer to the wiring diagram or the unit for the most up-to-date wiring.
NOTES
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. © 2010 Goodman Manufacturing Company, L.P. Houston, Texas Printed in the USA.