Instruction Manual for Danfoss models including: 200, 300, 301, ECA 71 MODBUS Communication Module, ECA 71, MODBUS Communication Module, Communication Module, Module
File Info : application/pdf, 26 Pages, 827.98KB
DocumentDocumentECA 71 protocol for the ECL Comfort 200/300 series Instructions DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 Instructions ECA 71 protocol for the ECL Comfort 200/300 series Table of Contents 1. Introduction 1 1.1 How to use these instructions ................................................................................................................................................................................................1 1.2 About the ECA 71 ........................................................................................................................................................................................................................1 1.3 Compatibility.................................................................................................................................................................................................................................2 2. Configuration 3 2.1 Network description...................................................................................................................................................................................................................3 2.2 Mounting and wiring of the ECA 71 .....................................................................................................................................................................................4 2.3 Add devices to the network.....................................................................................................................................................................................................6 2.3.1 Setup of addresses in the ECL Comfort 200/300/301 ....................................................................................................................................................6 3. General parameter description 8 3.1 Parameter naming.......................................................................................................................................................................................................................8 3.2 Control parameters.....................................................................................................................................................................................................................8 3.3 Schedules........................................................................................................................................................................................................................................8 3.4 Mode and status...........................................................................................................................................................................................................................8 3.5 Time and date ............................................................................................................................................................................................................................... 9 3.6 Heat meter data............................................................................................................................................................................................................................9 3.7 Special parameters......................................................................................................................................................................................................................9 4 Good behaviour in designing a district heating MODBUS network 10 4.1 Considerations before implementing communication ..............................................................................................................................................10 4.2 Basic needs for information in SCADA systems .............................................................................................................................................................10 4.3 Final number of nodes in the network..............................................................................................................................................................................11 4.4 Parallel network .........................................................................................................................................................................................................................11 4.5 Bandwidth considerations .....................................................................................................................................................................................................11 4.6 Update rate from the ECL Comfort controller.................................................................................................................................................................11 4.7 Minimize the copy of data in the network .......................................................................................................................................................................12 4.8 Network layouts .........................................................................................................................................................................................................................12 5. Protocol 13 5.1 Function codes ...........................................................................................................................................................................................................................13 5.1.1 Function codes overview........................................................................................................................................................................................................13 5.1.2 MODBUS/ECA 71 messages ...................................................................................................................................................................................................13 5.1.2.1 Read read-only parameter (0x03)........................................................................................................................................................................................13 5.1.2.2 Read parameters (0x04) ..........................................................................................................................................................................................................14 5.1.2.3 Write parameter number (0x06) ..........................................................................................................................................................................................14 5.2 Broadcasts ....................................................................................................................................................................................................................................15 5.3 Error codes....................................................................................................................................................................................................................................15 6. Dismounting 15 Appendix 16 Parameter list .............................................................................................................................................................................................................................................16 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series 1. Introduction 1.1 How to use these instructions Software and documentation for ECA 71 can be downloaded from http://heating.danfoss.com. Safety Note To avoid injury of persons and damages to the device, it is absolutely necessary to read and observe these instructions carefully. The warning sign is used to emphasize special conditions that should be taken into consideration. This symbol indicates that this particular piece of information should be read with special attention. 1.2 About the ECA 71 The ECA 71 MODBUS communication module makes it possible to establish a MODBUS network with standard network components. Via a SCADA system (OPC Client) and the Danfoss OPC server it is possible to control the controllers in the ECL Comfort in the 200/300 series remotely. ECA 71 can be used for all application cards in the ECL Comfort 200 series as well as in the 300 series. The ECA 71 with proprietary protocol for ECL Comfort is based on MODBUS®. Accessible parameters (card dependent): · Sensor values · References and desired values · Manual override · Output status · Mode indicators and status · Heat curve and parallel displacement · Flow and return temperature limitations · Schedules · Heat meter data (only in ECL Comfort 300 as of version 1.10 and only if ECA 73 is mounted) DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 1 Instructions ECA 71 protocol for the ECL Comfort 200/300 series 1.3 Compatibility Optional ECA modules: The ECA 71 is compatible with ECA 60-63, ECA 73, ECA 80, ECA 83, ECA 86 and ECA 88. Max. 2 ECA modules can be connected. ECL Comfort: ECL Comfort 200 series · As of ECL Comfort 200 version 1.09 ECA 71 is compatible, but an additional address tool is required. The address tool can be downloaded from http://heating.danfoss.com. ECL Comfort 300 series · The ECA 71 is fully compatible with ECL Comfort 300 as of version 1.10 (also known as ECL Comfort 300S) and there is no need for an additional address tool. · ECL Comfort 300 as of version 1.08 is compatible, but an additional address tool is required. · All versions of ECL Comfort 301 and 302 are compatible, but an additional address tool is required. Only ECL Comfort 300 as of version 1.10 can setup the address used in the ECA 71 module. All other ECL Comfort controllers will require an address tool to set up the address. Only ECL Comfort 300 as of version 1.10 can handle the heat meter data from the ECA 73 module. 2 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series 2. Configuration 2.1 Network description The network used for this module is conditionally compliant (implementation class = basic) with the MODBUS over serial line two-wire RS-485 interface. The module uses the RTU transmission mode. Devices are connected directly to the network, i.e. daisy chained. The network uses line polarization and line termination at both ends. These guidelines depend on the environmental conditions and the physical network characteristics: · Maximum cable length of 1200 metres without repeater · 32 devices pr. master / repeater (a repeater counts as a device) The modules uses an auto baud rate scheme that depends on the byte error ratio. If the error ratio exceeds a limit, the baud rate is changed. This means that all devices in the network must use the same communication settings, i.e multiple communication settings are not allowed. The module can operate with either 19200 (default) or 38400 baud network baud rate, 1 start bit, 8 data bits, even parity and one stop bit (11 bits). The valid address range is 1 247. For specific details, please consult the specifications · Modbus Application Protocol V1.1a. · MODBUS over Serial Line, Specification & Implementation guide V1.0 both of which can be found on http://www.modbus.org/ SCADA system: Connected via Danfoss MODBUS OPC server TCP/IP, USB or RS-232 to RS-485 (MODBUS) Fig. 2.1a: General network description ECL Comfort 300 as of version 1.10 M-Bus connection Heat meter DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 3 Instructions ECA 71 protocol for the ECL Comfort 200/300 series 2.2 Mounting and wiring of the ECA 71 1. Dismount cover plate B on the rear side of the ECL Comfort controller by using a small wire cutter. 2. Insert the module into the slides and press it gently into the connector on the ECL Comfort CPU board. 3. Mount the new cover plate B which is delivered with the module. 4. The connector must be inserted into the ECL Comfort as shown here. Fig. 2.2a: Mounting of the ECA 71 / 72 4 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series Fig. 2.2b: Wiring of the ECA 71 Pin connection ECA 71 Pin 1 Pin 2 (middle) Pin 3 Network connection MODBUS B / DATA + / D1 Common / SGND Network connection MODBUS A / DATA - / D0 The 2 poles + common are galvanically isolated. The pins are not interchangeable. There are no pull up / down resistors and no termination resistor. DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 5 Instructions ECA 71 protocol for the ECL Comfort 200/300 series 2.3 Add devices to the network When devices are added to the network, the master must be informed. In case of an OPC Server, this information is sent by means of the Configurator. Before adding a device to the network, it is advisable set the address. The address must be unique in the network. It is recommended to maintain a map with description of device placement and their address. 2.3.1 Setup of addresses in the ECL Comfort 200/300/301 ECL Comfort 300 as of version 1.10: · Go to line 199 (circuit I) on the grey side of the ECL Card. · Hold the arrow down button for 5 seconds, parameter line A1 will appear (A2 and A3 are only available for ECA 73). · The address menu is displayed (ECL Comfort 300 as of version 1.10 only) · Choose an available address in the network (address 1-247) Each ECL Comfort controller in the subnet must have a unique address. ECL Comfort 200 all versions: ECL Comfort 300 older versions (prior to 1.10): ECL Comfort 301 all versions: For all these ECL Comfort controllers, PC software is required for setting and reading the controller address in ECL Comfort. This software, the ECL Comfort Address Tool (ECAT), is downloadable from http://heating.danfoss.com System requirements: The software is able to run under the following operating systems: · Windows NT / XP / 2000. PC requirements: · Min. Pentium CPU · Min. 5 MB free hard disk space · Min. one free COM port for connection to the ECL Comfort controller · A cable from the COM port for connection to the ECL Comfort controller front communication slot. This cable is available on stock (code no. 087B1162). ECL Comfort Address Tool (ECAT): · Download the software and run the file: ECAT.exe · Choose the COM port into which the cable is connected · Select a free address in the network. Please note that this tool cannot detect whether the same address is used more than once in an ECL Comfort controller · Press `Write' · To verify that the address is correct, press `Read' · The button `Blink' can be used to verify the connection to the controller. If `Blink' is pressed, the controller starts blinking (press any button of the controller to stop the blinking again). 6 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series Fig. 2.3.1a: ECL Comfort Address Tool Address rules General guideline of the address rules used in the SCADA module: 1. An address can only be used once per network 2. Valid address range 1 247 3. The module uses the current or last known address a. Valid address in the ECL Comfort controller (set by the ECL Comfort Address Tool or directly in the ECL Comfort 300 as of version 1.10) b. The last used valid address c. If no valid address has been obtained, the module address is invalid ECL Comfort 200 and ECL Comfort 300 older versions (prior to 1.10): Any ECA module mounted inside the ECL Comfort controller must be removed before the address can be set. If the mounted ECA module is not removed before the address is set, the address setup will fail. ECL Comfort 300 as of version 1.10 and ECL Comfort 301/ ECL Comfort 302: No issues DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 7 Instructions ECA 71 protocol for the ECL Comfort 200/300 series 3. General parameter description 3.1 Parameter naming The parameters are divided into some functional sections, the main parts being the control parameter and schedule parameters. The complete parameter list can be found in the appendix. All parameters correspond to the MODBUS term "holding register" (or "input register" when read-only). All parameters are therefore read/write accessed as one (or more) holding/input registers independently of data type. 3.2 Control parameters The user interface parameters are located in the address range 11000 13999. The 1000th decimal indicates the ECL Comfort circuit number, i.e. 11xxx is circuit I, 12xxx is circuit II and 13xxx is circuit III. The parameters are named (numbered) in accordance with their name in the ECL Comfort. A complete list of the parameters can be found in the appendix. 3.3 Schedules The ECL Comfort divides the schedules into 7 days (17), each consisting of 48 x 30-minute periods. The week schedule in circuit III has only one day. A maximum of 3 comfort periods can be set for each day. Rules for schedule adjustment 1. The periods must be entered in chronological order, i.e. P1 ... P2 ... P3. 2. Start and stop values must be in the range 0, 30, 100, 130, 200, 230, ..., 2300, 2330, 2400. 3. Start values must be before stop values if the period is active. 4. When a stop period is written to zero, the period is automatically deleted. 5. When a start period is written different from zero, a period is automatically added. 3.4 Mode and status The mode and status parameters are located within the address range 4201 4213. The mode can be used to control the ECL Comfort mode. The status indicates the current ECL Comfort status. If one circuit is set to manual mode, it applies to all circuits (i.e. the controller is in manual mode). When the mode is changed from manual to another mode in one circuit, it also applies to all circuits in the controller. The controller automatically reverts to the previous mode if the information is available. If not (power failure / restart), the controller will revert to the default mode of all circuits which is scheduled operation. If standby mode is chosen, the status will be indicated as setback. Operating mode Manual operation Scheduled operation Constant comfort temperature Constant setback temperature Standby Code 0 1 2 3 4 Operating status Setback Pre-comfort Comfort Pre-setback Code 0 1 2 3 8 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series 3.5 Time and date The time and date parameters are located in the address range 64045 64049. When adjusting the date it is necessary to set a valid date. Example: If the date is 30/3 and must be set to 28/2, it is necessary to change the day first before changing the month. 3.6 Heat meter data When an ECA 73 with heat meters (only when connected by M-Bus) is installed, it is possible to read the following values*. · Actual flow · Accumulated volume · Actual power · Accumulated energy · Flow temperature · Return temperature For detailed information please consult the ECA 73 instructions and the appendix. * Not all heat meters supports these values 3.7 Special parameters The special parameters include information about types and versions. The parameters can be found in the parameter list in the appendix. Only the ones with a special encoding/decoding are described here. Device version Parameter 2003 holds the device version. The number is based on the ECL Comfort application version N.nn, encoded 256*N + nn. ECL Comfort application Parameter 2108 holds the ECL Comfort application. The 2 last digits indicate the application number, and the first digit(s) the application letter. Value 0 1 2 3 4 5 6 7 8 9 10 11 12 Letter A b C d E F G H L n o P U Example: 237, letter 2 = C and the number is 37 so the application is a C37. DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 9 Instructions ECA 71 protocol for the ECL Comfort 200/300 series 4 Good behaviour in designing a district heating MODBUS network In this chapter some basic design recommendations are listed. These recommendations are based on communication in heating systems. This chapter is built as an example of a network design. The example can vary from a specific application. The typical requirement in heating systems is to get access to a number of similar components and to be able to make a few adjustments. The illustrated performance levels might decrease in real systems. In general it can be said that the network master controls the performance of the network. 4.1 Considerations before implementing communication It is very important to be realistic when network and performance are specified. Some considerations have to be made in order to secure that important information is not blocked because of a frequent update of trivial information. Keep in mind that heating systems typically have long time constants, and hence can be polled less frequent. 4.2 Basic needs for information in SCADA systems The ECL Comfort controller can support a network with some pieces of information concerning a heating system. It might be a good idea to consider how to split up the traffic that these different information types generate. · Alarm handling: Values that are used to generate alarm conditions in the SCADA system. · Error handling: In all networks errors will occur, error means time out, check of sum error, retransmission and extra traffic generated. The errors might be caused by EMC or other conditions, and it is important to reserve some bandwidth for error handling. · Data logging: Logging of temperature etc. in a database is a function which typically is non-critical in a heating system. This function must normally run all the time "in the background". It is not recommended to include parameters such as set-points and other parameters that require user interaction to change. · Online communication: This is a direct communication with a single controller. When a controller is chosen (e.g. service picture in a SCADA system) the traffic to this single controller is increased. Parameter values can be polled frequently in order to give the user fast response. When the online communication is no longer needed (e.g. leaving the service picture in a SCADA system), the traffic must be set back to the normal level. · Other devices: Do not forget to reserve bandwidth for devices from other manufacturers and future devices. Heat meters, pressure sensors, and other devices have to share the network capacity. The level for different kinds of communication types must be considered (an example is given in figure 4.2a). 0UIFSOPEFT "MBSNIBOEMJOH &SSPSIBOEMJOH Fig. 4.2a: Split up of information type 10 0OMJOF %BUBMPH VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series 4.3 Final number of nodes in the network At start-up the network has to be designed with due consideration to the final number of nodes and the network traffic in the network. A network with a few controllers connected might run without any bandwidth problems at all. When the network is increased, however, bandwidth problems might occur in the network. To solve such problems, the amount of traffic has to be decreased in all controllers, or extra bandwidth can be implemented. 4.4 Parallel network If a large number of controllers are used in a limited area with a limited length of the communication cable, parallel network might be a way to generate more bandwidth. If the master is located in the middle of the network, the network can easily be split-up into two and the bandwidth can be doubled. 4.5 Bandwidth considerations The ECA 71 is based on a command/query and response, meaning that the SCADA system sends a command/query and the ECA 71 responses to this. Do not attempt to send new commands before the ECA 71 has send the latest response or the timeout expires. In a MODBUS network it is not possible to send commands/queries to different devices at the same time (except broadcast). One command/query response must be completed before the next can be started. It is necessary to think about the roundtrip time when designing the network. Larger networks will inherently have larger roundtrip times. If multiple devices must have the same information, it is possible to use the broadcast address 0. Broadcast can only be used when no response is necessary, i.e. by a write command. 4.6 Update rate from the ECL Comfort controller Values in the module are buffered values. The value update times depend on the application. The following is a rough guideline: Parameter type Control parameters Schedule Mode Output Time & date M-Bus (actual values) M-Bus (accumulated values) Update time (approx.) All parameters, once every 10 seconds One day, once a minute Once every 15 seconds Once every 5 seconds Once every 30 seconds Once every 60 seconds (1 minute) Once every 300 seconds (5 minutes) These update times indicate how often it is reasonable to read values from the different categories. DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 11 Instructions ECA 71 protocol for the ECL Comfort 200/300 series 4.7 Minimize the copy of data in the network Minimize the number of copied data. Adjust the poll time in the system to the actual need and the data update rate. It makes little sense to poll time and date every second when they only are updated once or twice every minute from the ECL Comfort controller. 4.8 Network layouts The network must always be configured as a daisy chained network, see the three examples from a very simple network to more complex networks below. Fig. 4.8a illustrates how termination and line polarization must be added. For specific details, consult the MODBUS specifications. ,0 4 . . .BTUFS 1$ ,0 -JOF1PMBSJ[BUJPO 4 5FSNJOBUPS 3 3FQFBUFS 4 . ,0 4 4 . 4 ,0 4 4 3 ,0 ,0 4 4 3 4 ,0 Fig. 4.8a: Daisy chain types The network should not be configured as shown below: 4 4 . . Fig. 4.8b: Not allowed 12 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series 5. Protocol The ECA 71 module is a MODBUS compliant device. The module supports a number of public function codes. The MODBUS application data unit (ADU) is limited to 50 bytes. Supported public function codes 03 (0x03) Read Holding Registers 04 (0x04) Read Input Registers 06 (0x06) Write Single Register 5.1 Function codes 5.1.1 Function codes overview Function Read PNU Read PNU Write PNU Function code 0x03 0x04 0x06 Comments Single PNU/register only Single PNU/holding register only Single PNU/holding register only 5.1.2 MODBUS/ECA 71 messages 5.1.2.1 Read read-only parameter (0x03) This function is used to read the value of an ECL Comfort read-only parameter number. Values are always returned as integer values and must be scaled according to the parameter definition. Requesting a quantity of more than 17 parameters in sequence gives an error response. Requesting non-existing parameter number(s) will give an error response. Request Function code Start PNU Quantity N of PNU 1 byte 2 bytes 2 bytes 0x03 0x0064 0xffff 0x0001 0x0011 Response Function code Byte count PNU data value 1 byte 1 byte 2 bytes 0x03 2 34 0x0000 0xffff Error Function code Error code 1 bytes 2 bytes 0x83 1, 2, 3 or 4 The request/response is MODBUS compliant when reading a sequence of parameters (Read input register). DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 13 Instructions ECA 71 protocol for the ECL Comfort 200/300 series 5.1.2.2 Read parameters (0x04) This function is used to read the value of an ECL Comfort parameter number. Values are always returned as integer values and must be scaled according to the parameter definition. Requesting a quantity of more than 17 parameters gives an error response. Requesting non-existing parameter number(s) will give an error response. Request Function code Start PNU Quantity N of PNU 1 byte 2 bytes 2 bytes 0x04 0x0064 0xffff 0x0001 0x0011 Response Function code Byte count PNU data value 1 byte 1 byte 2 bytes 0x04 2 - 34 0x0000 0xffff Error Function code Error code 1 byte 2 bytes 0x84 1, 2, 3 or 4 The request/response is MODBUS compliant reading a sequence of parameters (Read input register). 5.1.2.3 Write parameter number (0x06) This function is used to write a new setting value to an ECL Comfort parameter number. Values must be written as integer values and must be scaled according to the parameter definition. Attempts to write a value outside the valid range will give an error response. The minimum and maximum values must be obtained from the instructions for ECL Comport controller. Request Function code Write PNU New PNU value 1 byte 2 bytes 2 bytes 0x06 0x0064 0xffff 0x0000 0xffff Response Function code Write PNU New PNU value 1 byte 2 bytes 2 bytes 0x06 0x0064 0xffff 0x0000 0xffff Error Function code Error code 1 byte 2 bytes 0x86 1, 2, 3 or 4 The request/response is MODBUS compliant when writing a parameter (Write single register). 14 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series 5.2 Broadcasts The modules support MODBUS broadcast messages (unit address = 0). Command/function where a broadcast is usable · write ECL parameter (0x06) 5.3 Error codes For specific details, please consult the specifications · Modbus Application Protocol V1.1a. · MODBUS over Serial Line, Specification & Implementation guide V1.0 both of which can be found on http://www.modbus.org/ 6. Dismounting Disposal instruction: This product should be dismantled and its components sorted, if possible, in various groups before recycling or disposal. Always follow the local disposal regulations. DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 15 Instructions ECA 71 protocol for the ECL Comfort 200/300 series Appendix Parameter list ECL Comfort control parameters ECL line Upload text 11 11 Cancel red 12 12 Boost 13 13 Ref ramp 14 14 Opt const 16 16 Frost lim 17 17 Tref f back 18 18 Ball tmp 21 21 Total stop 30 30 RTL const 31 31 RTL upper X 32 32 RTL upper Y 33 33 RTL lower X 34 34 RTL lower Y 35 35 RTI max 36 36 RTI min 37 37 Adaptive RTL 44 44 Max DHW load 45 45 Max heat time 53 53 PI ref DHW 57 57 Comp infl min 58 58 Comp 59 59 Adaptive comp 60 60 Comp limit 61 61 Comp infl max 62 62 Comp infl min 63 63 Adaptive comp 64 64 Comp limit 65 65 Comp infl max 66 66 Comp infl min 67 67 Adaptive comp ECL Comfort parameter line Setback temperature dependent on outdoor temperature Boost Reference ramping Optimizing time constant Frost protection by DHW circulation pump Influence on desired flow temperature Temperature reference feedback Balance temperature Total stop Relay 1 (R1) function related to room temperature Return temperature limitation Limitation temperature, sensor S4 Return temperature limitation - upper limit (X-axis) Return temperature limitation - upper limit (Y-axis) Return temperature limitation - lower limit (X-axis) Return temperature limitation - lower limit (Y-axis) Limitation temperature influence, max. Limitation temperature influence, min. Time constant for temperature limitation Time constant for return temperature limitation Max. DHW charging time DHW charging deactivation time Compensation of heat loss in circulation circuit Desired flow temperature, DHW charging Temperature influence by S4, sliding frost protection Surface temperature influence during cooling Compensation Adaptive function of compensation Compensation temperature, 1. point Surface temperature limitation during heating Max. slab temperature limitation Compensation temperature influence, 1. point, max. limitation Influence at max. slab temperature Compensation temperature influence, 1. point, min. limitation Surface temperature influence during heating Time constant, compensation temperature Adaptive function of max. slab temperature limitation Adaptation of the surface temperature limitation Compensation temperature, 2. point Min. slab temperature limitation Flow temperature, max. limitation during heating (thermostatic function) Compensation temperature influence, 2. point, max. limitation Influence at min. slab temperature Compensation temperature influence, 2. point, min. limitation Adaptive function of min. slab temperature limitation Adaptive function of S2 flow temperature during DHW charging PNU (Parameter NUmber) Cir. I Cir. II Cir. III 11011 12011 NA 11012 12012 NA 11013 12013 NA 11014 12014 NA 11016 NA NA 11017 NA NA 11018 NA NA 11021 12021 NA 11030 12030 NA 11031 12031 NA 11032 12032 NA 11033 12033 NA 11034 12034 NA 11035 12035 NA 11036 12036 NA 11037 12037 NA 11044 12044 NA 11045 12045 NA 11053 12053 NA 11057 12057 NA 11058 12058 NA 11059 12059 NA 11060 12060 NA 11061 12061 NA 11062 12062 NA 11063 12063 NA 11064 12064 NA 11065 12065 NA 11066 12066 NA 11067 12067 NA Access Scale 10-x default 0 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W -1 R/W -1 R/W R/W R/W R/W R/W -1 R/W R/W R/W -1 R/W -1 R/W R/W R/W -1 R/W -1 R/W 16 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series ECL Comfort control parameters ECL line Upload text 78 78 Setpoint 80 80 Time set-up 99 99 Man valve pos 100 100 Acc Out tmp 101 101 Acc room tmp 102 102 RH 103 103 CSPT 104 104 Valve pos 110 110 Act value 111 111 Setpoint 112 112 Flow int 113 113 Flow filter 114 114 Flow type 115 115 Flow unit 116 116 FL upper y 117 117 FL lower y 118 118 FL upper x 119 119 FL lower x 133 133 Prop Xp low 134 134 Prop Xp up 135 135 Int const Tn 136 136 Neutral zone 142 142 Alarm type 146 146 Alarm setpt4 156 156 Cooling out 157 157 Cooling room 158 158 R infl heat 159 159 R infl cool 160 160 Max outdoor 161 161 Min outdoor 162 162 Setpoint 163 163 R diff cool 164 164 Disp COCSPT C 175 Heat curve 175 175 Heat curve 176 176 Paral disp 2 177 Flow tmp min 177 177 Flow tmp min 178 178 Flow tmp max ECL Comfort parameter line Desired temperature for anti-bacteria function Activation of humidistat Anti-bacteria function period Humidistat, post activation Set valve position manual (0-250) Accumulated outdoor temperature Accumulated room temperature Actual humidity Dew point temperature Valve position 0-100% Actual flow / energy Flow / enegy limitation Integrator time constant Filter time constant M-Bus / amount of unit Flow / energy unit Flow / energy limitation - upper limit (Y-axis) Flow / energy limitation - lower limit (Y-axis) Flow / energy limitation - upper limit (X-axis) Flow / energy limitation - lower limit (X-axis) Proportional band, Xp - lower circuit III Proportional band, Xp - upper circuit III Integration time constant, Tn circuit III Neutral zone - Nz circuit III Function of input S2 TR restart period TST pressure stabilization time Activation / deactivation of cooling, accumulated outdoor temperature Activation / deactivation of cooling, accumulated room temperature Acceptable temperature deviation below desired flow temperature (T1ALARM) Room temperature influence, heating Acceptable temperature deviation above the desired flow temperature (T2ALARM) Room temperature influence, cooling Time interval tALARM before activation of alarm function Max. outdoor temperature (cut-in / cut-out value) Min. outdoor temperature (cut-in / cut-out value) Generel set-point Cooling, activation difference, actual room temperature Displacement of the calculated dew point temperature Slope Slope Parallel displacement Flow temperature, min. limits Boiler flow temperature limits, min. Flow temperature , min. limits Flow temperature , max. limits PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 11078 12078 NA R/W 11080 12080 NA R/W 11099 12099 NA R/W 11100 12100 NA R 11101 12101 NA R 11102 12102 NA R 11103 12103 NA R 11104 12104 NA R 11110 12110 NA R 11111 12111 NA R/W 11112 12112 NA R/W 11113 12113 NA R/W 11114 12114 NA R/W 11115 12115 NA R/W 11116 12116 NA R/W 11117 12117 NA R/W 11118 12118 NA R/W 11119 12119 NA R/W 11133 12133 NA R/W 11134 12134 NA R/W 11135 12135 NA R/W 11136 12136 NA R/W 11142 12142 13142 R/W 11146 12146 NA R/W 11156 12156 NA R/W 11157 12157 NA R/W 11158 12158 NA R/W 11159 12159 NA R/W 11160 12160 NA R/W 11161 12161 NA R/W 11162 12162 NA R/W 11163 12163 NA R/W 11164 12164 NA R/W 11175 12175 NA R/W -1 11175 12175 NA R/W -1 11176 12176 NA R/W 11177 12177 NA R/W 11177 12177 NA R/W 11178 12178 NA R/W DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 17 Instructions ECA 71 protocol for the ECL Comfort 200/300 series ECL Comfort control parameters ECL line Upload text 1 179 Heat cut out 179 179 Heat cut out A 180 Day setpt 180 180 Day setpt 181 181 Night setpt B 182 Room inf max 3 182 Room inf max 182 182 Room inf max 183 183 Room inf min 4 184 Prob Xp 184 184 Prob Xp 5 185 Int const Tn 185 185 Int const Tn 6 186 Run time 186 186 Run time 7 187 Neutral zone 187 187 Neutral zone 188 188 BEM 190 190 DHW day 191 191 DHW night 192 192 DHW diff 193 193 Charging tmp 194 194 Diff1 cutout 195 195 Diff2 cutin 198 198 Summertime ECL Comfort parameter line Limit for heating cut-out Limit for heating cut-out Desired room temperature - comfort Desired room temperature - comfort Desired room temperature - setback Room temperature influence - max Room temperature influence Room temperature influence - max Room temperature influence - min Room temperature influence Proportional band, Xp Proportional band - Xp Integration time constant, Tn Integration constant - Tn Running time of the motorized control valve Running time of the motorized control valve Neutral zone, Nz Neutral zone - Nz BEM-function Boiler temperature difference Desired DHW temperature - comfort Desired DHW temperature - setback DHW temperature difference Charging temperature difference Cut-out temperature difference - (lower sensor)* Temperature difference at DHW charging, cut-out temperature difference - lower tank temperature sensor Cut-in temperature difference - (upper sensor)* Temperature at DHW charging, cut-in temperature difference - upper tank temperature sensor Daylight saving time changeover PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 11179 12179 NA R/W 11179 12179 NA R/W 11180 12180 NA R/W 11180 12180 NA R/W 11181 12181 NA R/W 11182 12182 NA R/W -1 11182 12182 NA R/W -1 11182 12182 NA R/W -1 11183 12183 NA R/W -1 11184 12184 NA R/W 11184 12184 NA R/W 11185 12185 NA R/W 11185 12185 NA R/W 11186 12186 NA R/W 11186 12186 NA R/W 11187 12187 NA R/W 11187 12187 NA R/W 11188 NA NA R/W 11190 12190 13190 R/W 11191 12191 13191 R/W 11192 12192 NA R/W 11193 12193 NA R/W 11194 12194 NA R/W 11195 12195 NA R/W 11198 NA NA R/W Time counters ECL line Upload text Minutes step 1 Minutes step 2 Hours step 1 Hours step 2 Cutin step1 Cutin step2 Cutin 1000 step1 Cutin 1000 step2 ECL Comfort parameter Minutes step 1 Minutes step 2 Hours step 1 Hours step 2 Cut in step 1 Cut in step 2 Cut in * 1000 step 1 Cut in * 1000 step 2 PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 11213 12213 NA R 11214 12214 NA R 11215 12215 NA R 11216 12216 NA R 11242 12242 NA R 11243 12243 NA R 11245 12245 NA R 11246 12246 NA R 18 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series Sensors and references ECL line Upload text S1 sensor S2 sensor S3 sensor S4 sensor S5 sensor S6 sensor ECL Comfort parameter S1 sensor S2 sensor S3 sensor S4 sensor S5 sensor S6 sensor Room temp Room temperature Minutes step 1 Minutes step 2 Hours step 1 Hours step 2 Minutes step 1 Minutes step 2 Hours step 1 Hours step 2 1000 h step 1 1000 h step 2 Hours * 1000 step 1 Hours * 1000 step 2 NA S7 sensor S8 sensor S9 sensor S10 sensor Relative humidity S7 options sensor S8 options sensor S9 options sensor S10 options sensor S1 reference S2 reference S3 reference S4 reference S5 reference S6 reference S1 sensor 1 reference S2 sensor 2 reference S3 sensor 3 reference S4 sensor 4 reference S5 sensor 5 reference S6 sensor 6 reference Cutin step1 Cutin step2 Cutin 1000 step1 Cutin 1000 step2 Cut in step 1 Cut in step 2 Cut in * 1000 step 1 Cut in * 1000 step 2 S7 reference S8 reference S9 reference S10 reference S7 sensor reference S8 sensor reference S9 sensor reference S10 sensor reference PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 11201 NA NA R/W -1 11202 12202 13202 R -1 11203 12203 13203 R -1 11204 12204 13204 R -1 11205 12205 13205 R -1 11206 12206 13206 R -1 11211 12211 NA R -1 11213 12213 NA R -1 11214 12214 NA R 11215 12215 NA R 11216 12216 NA R 11218 12218 NA R 11219 12219 NA R 11220 12220 NA R 11221 12221 13221 R -1 11222 12222 13222 R -1 11223 12223 13223 R -1 11224 12224 13224 R -1 11228 12228 13228 R -1 11229 12229 13229 R -1 11230 12230 13230 R -1 11231 12231 13231 R -1 11232 12232 13232 R -1 11233 12233 13233 R -1 11242 12242 NA R 11243 12243 NA R 11245 12245 NA R 11246 12246 NA R 11248 12248 13248 R -1 11249 12249 13249 R -1 11250 12250 13250 R -1 11251 12251 13251 R -1 DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 19 Instructions ECA 71 protocol for the ECL Comfort 200/300 series Output status ECL line Upload text Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Triac 1 Triac 2 Triac 3 Triac 4 Alarm word ECL Comfort parameter Relay 1 status Relay 2 status Relay 3 status Relay 4 status Relay 5 status Triac 1 status Triac 2 status Triac 3 status Triac 4 status Alarm word PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 4001 NA NA R/W 4002 NA NA R/W 4003 NA NA R/W 4004 NA NA R 4005 NA NA R 4101 NA NA R/W 4102 NA NA R/W 4103 NA NA R/W 4104 NA NA R/W 4110 NA NA R Controller mode ECL line Upload text Cir 1 mode Cir 2 mode Cir 3 mode Cir 1 status Cir 2 status Cir 3 status ECL Comfort parameter Circuit 1 mode Circuit 2 mode Circuit 3 mode Circuit 1 status Circuit 2 status Circuit 3 status PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 4201 NA NA R/W 4202 NA NA R/W 4203 NA NA R/W 4211 NA NA R 4212 NA NA R 4213 NA NA R 20 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series Schedules ECL line Upload text Active Schedule Monday P1 ON Monday P1 OFF Monday P2 ON Monday P2 OFF Monday P3 ON Monday P3 OFF Tuesday P1 ON Tuesday P1 OFF Tuesday P2 ON Tuesday P2 OFF Tuesday P3 ON Tuesday P3 OFF Wednesday P1 ON Wednesday P1 OFF Wednesday P2 ON Wednesday P2 OFF Wednesday P3 ON Wednesday P3 OFF Thursday P1 ON Thursday P1 OFF Thursday P2 ON Thursday P2 OFF Thursday P3 ON Thursday P3 OFF Friday P1 ON Friday P1 OFF Friday P2 ON Friday P2 OFF Friday P3 ON Friday P3 OFF Saturday P1 ON Saturday P1 OFF Saturday P2 ON Saturday P2 OFF Saturday P3 ON Saturday P3 OFF Sunday P1 ON Sunday P1 OFF Sunday P2 ON Sunday P2 OFF Sunday P3 ON Sunday P3 OFF ECL Comfort parameter line Active Schedule (X-value Schedule) Schedule Monday circuit X period 1 start Schedule Monday circuit X period 1 stop Schedule Monday circuit X period 2 start Schedule Monday circuit X period 2 stop Schedule Monday circuit X period 3 start Schedule Monday circuit X period 3 stop Schedule Tuesday circuit X period 1 start Schedule Tuesday circuit X period 1 stop Schedule Tuesday circuit X period 2 start Schedule Tuesday circuit X period 2 stop Schedule Tuesday circuit X period 3 start Schedule Tuesday circuit X period 3 stop Schedule Wednesday circuit X period 1 start Schedule Wednesday circuit X period 1 stop Schedule Wednesday circuit X period 2 start Schedule Wednesday circuit X period 2 stop Schedule Wednesday circuit X period 3 start Schedule Wednesday circuit X period 3 stop Schedule Thursday circuit X period 1 start Schedule Thursday circuit X period 1 stop Schedule Thursday circuit X period 2 start Schedule Thursday circuit X period 2 stop Schedule Thursday circuit X period 3 start Schedule Thursday circuit X period 3 stop Schedule Friday circuit X period 1 start Schedule Friday circuit X period 1 stop Schedule Friday circuit X period 2 start Schedule Friday circuit X period 2 stop Schedule Friday circuit X period 3 start Schedule Friday circuit X period 3 stop Schedule Saturday circuit X period 1 start Schedule Saturday circuit X period 1 stop Schedule Saturday circuit X period 2 start Schedule Saturday circuit X period 2 stop Schedule Saturday circuit X period 3 start Schedule Saturday circuit X period 3 stop Schedule Sunday circuit X period 1 start Schedule Sunday circuit X period 1 stop Schedule Sunday circuit X period 2 start Schedule Sunday circuit X period 2 stop Schedule Sunday circuit X period 3 start Schedule Sunday circuit X period 3 stop PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 1100 NA NA R/W 1110 NA NA R/W 1111 NA NA R/W 1112 NA NA R/W 1113 NA NA R/W 1114 NA NA R/W 1115 NA NA R/W 1120 NA NA R/W 1121 NA NA R/W 1122 NA NA R/W 1123 NA NA R/W 1124 NA NA R/W 1125 NA NA R/W 1130 NA NA R/W 1131 NA NA R/W 1132 NA NA R/W 1133 NA NA R/W 1134 NA NA R/W 1135 NA NA R/W 1140 NA NA R/W 1141 NA NA R/W 1142 NA NA R/W 1143 NA NA R/W 1144 NA NA R/W 1145 NA NA R/W 1150 NA NA R/W 1151 NA NA R/W 1152 NA NA R/W 1153 NA NA R/W 1154 NA NA R/W 1155 NA NA R/W 1160 NA NA R/W 1161 NA NA R/W 1162 NA NA R/W 1163 NA NA R/W 1164 NA NA R/W 1165 NA NA R/W 1170 NA NA R/W 1171 NA NA R/W 1172 NA NA R/W 1173 NA NA R/W 1174 NA NA R/W 1175 NA NA R/W DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 21 Instructions ECA 71 protocol for the ECL Comfort 200/300 series M-Bus data from heat meter ECL line Upload text Flow 1 Flow unit 1 Volumen 1 Volumen unit 1 Power 1 Power unit 1 Energy 1 Energy unit 1 Flow temp 1 Return temp 1 ECL Comfort parameter line M-Bus slave 1 actual flow value M-Bus slave 1 actual flow unit M-Bus slave 1 accumulated volumen value M-Bus slave 1 accumulated volumen unit M-Bus slave 1 actual power value M-Bus slave 1 actual power unit M-Bus slave 1 accumulated energy value M-Bus slave 1 accumulated energy unit M-Bus slave 1 flow temperature M-Bus slave 1 return temperature Flow 2 Flow unit 2 Volumen 2 Volumen unit 2 Power 2 Power unit 2 Energy 2 Energy unit 2 Flow temp 2 Return temp 2 M-Bus slave 2 actual flow value M-Bus slave 2 actual flow unit M-Bus slave 2 accumulated volumen value M-Bus slave 2 accumulated volumen unit M-Bus slave 2 actual power value M-Bus slave 2 actual power unit M-Bus slave 2 accumulated energy value M-Bus slave 2 accumulated energy unit M-Bus slave 2 flow temperature M-Bus slave 2 return temperature PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 4501 NA NA R -1 4502 NA NA R 4503 NA NA R 4504 NA NA R/W 4505 NA NA R -1 4506 NA NA R 4507 NA NA R 4508 NA NA R/W 4509 NA NA R -1 4510 NA NA R -1 4521 NA NA R -1 4522 NA NA R 4523 NA NA R 4524 NA NA R/W 4525 NA NA R -1 4526 NA NA R 4527 NA NA R 4528 NA NA R/W 4529 NA NA R -1 4530 NA NA R -1 Data from ECA 83 and ECA 88 ECL line Upload text Analog 1 Analog 2 NA NA NA NA ECL Comfort parameter line Analog input 1 (ECA 83) Analog input 2 (ECA 83) Accumulated pulse circuit 1 (high word) Accumulated pulse circuit 1 (low word) Accumulated pulse circuit 2 (high word) Accumulated pulse circuit 2 (low word) PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 4601 NA NA R -1 4602 NA NA R -1 4611 NA NA R/W 4612 NA NA R/W 4613 NA NA R/W 4614 NA NA R/W 22 VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK Instructions ECA 71 protocol for the ECL Comfort 200/300 series M-Bus high resolution data from heat meter ECL line Upload text NA NA NA NA NA NA NA NA NA NA NA NA ECL Comfort parameter line M-Bus slave 1 high res. Accumulated volumen unit M-Bus slave 1 high res. Accumulated volumen (high word) M-Bus slave 1 high res. Accumulated volumen (low word) M-Bus slave 1 high res. Accumulated energy unit M-Bus slave 1 high res. Accumulated energy (high word) M-Bus slave 1 high res. Accumulated energy (low word) M-Bus slave 1 high res. Accumulated volumen unit M-Bus slave 2 high res. Accumulated volumen (high word) M-Bus slave 2 high res. Accumulated volumen (low word) M-Bus slave 1 high res. Accumulated energy unit M-Bus slave 2 high res. Accumulated energy (high word) M-Bus slave 2 high res. Accumulated energy (low word) PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 4620 NA NA R/W 4621 NA NA R 4622 NA NA R 4623 NA NA R/W 4624 NA NA R 4625 NA NA R 4626 NA NA R/W 4627 NA NA R 4628 NA NA R 4629 NA NA R/W 4630 NA NA R 4631 NA NA R Time, date and system ECL line Upload text Hour Minutes DayMonth Month Year ECL Comfort parameter line Hour Min Date Month Year ECL SW ver Manual control ECL net adr ECL Code No ECA SW ver NA NA NA NA NA ECL Comfort software version Manual control ECL Comfort network address ECL Comfort Code number Modbus / LON software version ECA module SW version ECA module HW version/revision ECL Comfort SW version ECL Comfort HW Type ECL Comfort Hardware version/revision PNU Access Scale 10-x (Parameter NUmber) Cir. I Cir. II Cir. III default 0 64045 R/W 64046 R/W 64047 R/W 64048 R/W 64049 R/W 2003 2004 2008 2011 2012 2103 2104 2105 2106 2107 R -1 R/W R R R -1 R R R R R Explanations: ECL line The parameter line according to the ECL Comfort user interface / instructions Upload text Text to be uploaded from the ECA 71 which is used in the ServiceTool ECL Comfort parameter line Description of the parameter Cir. Circuit in the ECL Comfort controller Access Read / write permission Scale Decimal numbers cannot be send so the sent value is divided by 10-1. Example: The slope has the scale -1. Value read = 18. 18 x 10 -1 = 1.8 DH-SMT/DK VI.KP.O2.02 © Danfoss 02/2008 23 Instructions ECA 71 protocol for the ECL Comfort 200/300 series *087R9775* *VIKPO202* Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. VI.KP.O2.02 © Danfoss 02/2008 DH-SMT/DK