Fisher™ FIELDVUE™ DVC6200p DTM with PACTware 4.1

Document Number: D104172X012

Publication Date: November 2017

Introduction

This document provides instructions for establishing a connection to a PROFIBUS PA device, the Fisher™ FIELDVUE™ DVC6200p, within the PACTware 4.1 environment. It covers the installation of the supported DTM (Device Type Manager) using PROFIusb USB.

Notes

The information presented here can also be applied when establishing connections using FieldCare™ and FieldMate configuration tools.

For detailed information on DVC6200p installation, connection, and initial configuration, refer to the DVC6200 Series Quick Start Guide (Document Number: D103556X012).

For comprehensive details on the DVC6200p digital valve controller, including product specifications, reference materials, custom setup information, maintenance procedures, and replacement part details, consult the DVC6200p Instruction Manual (Document Number: D103563X012).

DTM Supported

DVC6200p_Profibus_DTM

Assumptions and Supported Environment

The following software and hardware should be installed prior to launching the DVC6200p DTM in PACTware 4.1:

S. NoSystemVersionReference Link
1PD to PA Coupler (Pepperl and Fuchs)Compact PROFIBUS Power Hub and Segment Coupler KT-MB-GTB-2PS H/W V1.03 Driver Ver. 5.45.11http://www.pepperl-fuchs.us/usa/en/classid_1482.htm?view=productdetails&prodid=36114
2PROFIusb USBFROFIdtmDrivers included with CD/DVD when purchased
3PROFIBUS CommDTMPROFIbus DTM
4Pactware 4.1Ver 4.1PACTware 4.1 from pepperl-fuchs

Installation Procedure

  1. Download the DVC6200p_Profibus_DTM and extract the folder. Navigate to setup.exe in the extracted folder.
  2. Right-click on setup.exe and select "Run as administrator" from the context menu. Visual: Screenshot showing the setup.exe file with its context menu open, displaying "Run as administrator".
  3. The DVC6200p device DTM installation wizard will start. Visual: Screenshot of the InstallShield Wizard indicating "Preparing to Install..." with a progress bar.
  4. Click "Next" in the welcome screen. Visual: Screenshot of the InstallShield Wizard's welcome screen prompting to click "Next".
  5. Accept the terms in the license agreement by selecting the appropriate option and click "Next". Visual: Screenshot of the InstallShield Wizard's license agreement dialog requiring acceptance.
  6. Select the "Complete" setup type and click "Next" to continue the installation. Visual: Screenshot of the InstallShield Wizard's setup type selection screen.
  7. Click "Install" to begin the installation of the DVC6200p Device DTM. Visual: Screenshot of the InstallShield Wizard indicating it is "Ready to Install the Program".
  8. Click "Finish" to complete the installation. Visual: Screenshot of the InstallShield Wizard's completion dialog confirming successful installation.
  9. The DVC6200p Device DTM is now successfully installed on your machine.

Launching the DVC6200p DTM in PACTware 4.1

  1. Navigate to "All Programs" and select "PACTware 4.1". Visual: Screenshot of the PACTware software interface with the project explorer showing "HOST PC".
  2. Right-click on "HOST PC" and select "Add device" from the context menu. Visual: Screenshot of the PACTware interface with the "HOST PC" right-clicked, showing the "Add device" option in the context menu.
  3. In the "Add Device" dialog, select "PROFIdtm DPV1" and click "OK". Visual: Screenshot of the PACTware "Add Device" dialog listing available drivers, with "PROFIdtm DPV1" selected.
  4. The PROFIdtm is now added as a project item.
  5. Right-click on the newly added PROFIdtm and select "Connect" from the context menu. Visual: Screenshot of the PACTware interface with "PROFIdtm" right-clicked, showing the "Connect" option in the context menu.
  6. Select "Parameter" from the dropdown menu. Enter the Baud Rate: 93.75 k Bit/s for the P&F Coupler or 45.45 k Bit/s for the Siemens Coupler. Visual: Screenshot of the PACTware parameter configuration window showing Baud Rate settings.
  7. The PROFIBUS communication DTM is now connected, indicated by a green connection status icon. Visual: Screenshot of the PACTware interface showing a green connection status icon next to the PROFIdtm entry.
  8. Right-click on the PROFIdtm again and select "Topology Scan". Visual: Screenshot of the PACTware interface with "PROFIdtm" right-clicked, showing the "Topology Scan" option.
  9. Click the blue arrow button in the "Topology Scan" window to start the scan. Visual: Screenshot of the PACTware "Topology Scan" window with the start scan button (blue arrow) highlighted.
  10. The scan is in progress. Please wait. Visual: Screenshot of the PACTware "Topology Scan" window showing the scan in progress.
  11. After the scan completes, the DVC6200p_DTM will be added to the Scan Tree. Click "Close" to exit the Topology Scan window. Visual: Screenshot of the PACTware "Topology Scan" window after completion, showing the DVC6200p_DTM in the Scan Tree.
  12. Right-click on the DVC6200P_DTM in the Scan Tree and click "Connect". Visual: Screenshot of the PACTware interface with "DVC6200P_DTM" right-clicked, showing the "Connect" option.
  13. The DVC6200p DTM is now connected, indicated by a green connection status icon. Visual: Screenshot of the PACTware interface showing a green connection status icon next to the DVC6200P_DTM entry.
  14. Right-click on the device and select "Parameter" > "Online Parameterization" > "Parameterize". Visual: Screenshot of the PACTware interface with the device right-clicked, showing the "Parameter" menu expanded to "Online Parameterization" and "Parameterize".
  15. The device DVC6200P_DTM Parameterization interface is now launched in PACTware 4.1. Visual: Screenshot of the PACTware parameterization window for the DVC6200p DTM, displaying various parameters and controls.

Changing the Device Address

  1. Confirm the PROFIBUS communication DTM is connected, as indicated by the green connection status icon. Visual: Screenshot of the PACTware interface showing a green connection status icon.
  2. Right-click PROFIdtm and select "Additional functions" > "Show Live List...". Visual: Screenshot of the PACTware interface with "PROFIdtm" right-clicked, showing the "Additional functions" submenu expanded to "Show Live List...".
  3. Right-click the selected device in the Live List and select "Set Device Station Address". Type the desired address in the "New Address:" field and click "Set". Visual: Screenshot of the PACTware "Set Device Station Address" dialog box, showing fields for address input.

PDF preview unavailable. Download the PDF instead.

im-supplement-fisher-fieldvue-dvc6200p-dtm-pactware-4-1-en-122740 Acrobat Distiller 15.0 (Windows)

Related Documents

Preview Fisher FIELDVUE DVC6200p Digital Valve Controller: Introduction and Specifications
This manual provides an introduction to the Fisher FIELDVUE DVC6200p Digital Valve Controller, covering its specifications, features, and applications. Learn about its PROFIBUS PA communication, function blocks, and mounting options.
Preview Fisher FIELDVUE DVC6200p Digital Valve Controller Instruction Manual
This instruction manual provides comprehensive details for the Fisher FIELDVUE DVC6200p Digital Valve Controller, covering installation, configuration, maintenance, troubleshooting, and specifications for this PROFIBUS PA communicating instrument.
Preview Fisher FIELDVUE DVC6200p Digital Valve Controller - Safety and Operation Guide
This document provides essential safety information and operational guidelines for the Fisher FIELDVUE DVC6200p Digital Valve Controller. It emphasizes the need for trained personnel and careful adherence to documentation to prevent injury or damage. The guide is available in multiple languages.
Preview Fisher FIELDVUE DVC6200 Series Hazardous Area Approval Nameplates
This document provides a comprehensive overview of the hazardous area approval nameplates for the Fisher FIELDVUE DVC6200 Series of digital valve controllers, including HART, FOUNDATION fieldbus, and PROFIBUS models, as well as the DVC6215 Remote Travel Sensor. It details certifications and specifications for various hazardous area classifications such as CSA, FM, ATEX, IECEx, INMETRO, KGS, NEPSI, and Customs Union.
Preview Fisher FIELDVUE DVC6200 Digital Valve Controllers - Product Information
Information on the Fisher FIELDVUE DVC6200 Digital Valve Controllers, including safety precautions, installation, operation, and maintenance guidelines. The document is available in multiple languages.
Preview Руководство по эксплуатации цифрового контроллера клапанов Fisher FIELDVUE DVC6200
Полное руководство по эксплуатации цифрового контроллера клапанов Fisher FIELDVUE DVC6200, охватывающее установку, настройку, эксплуатацию, техническое обслуживание и поиск неисправностей.
Preview Fisher FIELDVUE DVC6200 디지털 밸브 컨트롤러 사용 설명서
Fisher FIELDVUE DVC6200 디지털 밸브 컨트롤러의 설치, 배선, 구성, 작동, 유지보수 및 문제 해결에 대한 포괄적인 사용자 가이드입니다. HART 통신 및 ValveLink 소프트웨어 통합에 대한 정보를 제공합니다.
Preview Fisher FIELDVUE DLC3010 Digital Level Controller Quick Start Guide
Quick start guide for the Fisher FIELDVUE DLC3010 Digital Level Controller, covering installation, operation, maintenance, and safety instructions for industrial applications. Includes technical specifications and hazardous area certifications.