Philips Maxos Fusion LL500X / LL600X
Product Overview
The Philips Maxos Fusion LL500X and LL600X series offers versatile LED lighting solutions designed for various indoor applications. These luminaires combine energy efficiency with robust performance and flexible installation options.
General Specifications
Certifications & Ratings:
- CE Marking
- Indoor Use
- Frequency: 50Hz / 220V, 60Hz / 240V
- LED Types: LL600X, LL500X
- IP Rating: IP54, IP20
- IK Rating: IK02
- Operating Temperature: Max. 35°C, Min. -20°C
Model Variants and Specifications
Model | Length (mm) | LED31S PSD/SR P(W) | LED50S PSD/SR P(W) | LED61S PSD/SR P(W) | LED62S PSD/SR P(W) | LED100S PSD/SR P(W) | LED123S PSD/SR P(W) | LED160S PSD/SR P(W) | Weight (kg) |
---|---|---|---|---|---|---|---|---|---|
LL512X | 1138 | 21 | 36 | 45 | 41 | 71 | 89 | 127 | 1.30 |
LL523X | 2276 | - | - | - | - | - | - | - | 2.40 |
LL612X | 1257 | 21 | 36 | 45 | 41 | 71 | 89 | 127 | 4.25 |
LL623X | 2395 | - | - | - | - | - | - | - | 6.00 |
Emergency Lighting PSED / SRED Versions
Specifications for Emergency Lighting (PSED / SRED) versions:
Driver Type | LED31S | LED50S | LED50S XT | LED61S | LED61S XT | LED62S | LED100S | LED100S XT | LED123S | LED123S XT | LED160S | LED160S XT |
---|---|---|---|---|---|---|---|---|---|---|---|---|
35W | 35W | Xit 100W | 60W | Xit 100W | 60W | Xit 100W | Xit 100W | Xit 100W | Xit 100W | Xit 150W | ||
AC Lumen output [lm] | 3100 | 5000 | 6100 | 6200 | 10000 | 12300 | 16000 | |||||
AC Power [W] | 21 | 36 | 36 | 45 | 45 | 41 | 71 | 89 | 127 | 19 | ||
DC Lumen Output [lm] | 465 | 750 | 750 | 915 | 915 | 930 | 1500 | 1845 | 2400 | |||
DC Power [W] | 3 | 5 | 5 | 7 | 7 | 6 | 11 | 13 | 19 | |||
DC Voltage Range [V] | 168 - 275 | |||||||||||
PSED / SRED FUSE | 1 x 0.8A |
Model Variants: LL512X, LL523X, LL512X PCO, LL523X PCO, LL612X, LL623X.
Diagram: Illustrates beam direction in A20 optics.
Installation and Wiring
Phase Selection: The luminaire supports phase selection for L1/L2/L3 connections. ⚠️ (Warning): Only for A20 if needed.
Wiring Diagram: Detailed diagrams show front and back side connections, including PE, N, L1, L2, L3, and other pins (4-11). Specific wiring configurations are provided for different driver types (PSD7/SR7, PSD13 ELP/SR13 ELP, PSD13 ELD/SR13 ELD, PSED7/SRED7, PSED13/SRED13) and trunk compatibility (LL...T 7..., LL...T 9..., LL...T 13...).
Notes:
- Wires to be connected by installer (available PINs: N, L1-L3, 6-11).
- Wires to be connected by installer (available PINs: 6-11).
- Available lines in trunk (N, L1-L3, 4, 5, 6, 7).
Inrush Current Data
The following table details inrush current (Imax) and time to reach reference current (Tref) for various driver types, along with recommended MCB ratings (B 10A to C 25A) for different panel configurations.
Driver Type | LED31S 35W PSD SR | LED50S 35W PSD SR | LED50S XT Xit 100W PSD/SR | LED61S 60W PSD SR | LED61S XT Xit 100W PSD/SR | LED62S 60W PSD SR | LED100S Xit 100W PSD/SR | LED100S XT Xit 100W PSD/SR | LED123S Xit 100W PSD/SR | LED123S XT Xit 100W PSD/SR | LED160S Xit 150W PSD/SR | LED160S XT Xit 150W PSD/SR | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | Imax (A) | Tref (µs) | |
Imax (A) | 21 | 280 | 21 | 280 | 4.5 | 1000 | 21 | 280 | 4.5 | 1000 | 21 | 280 | 4.5 | 1000 | 4.5 | 1000 | 4.5 | 1000 | 5.1 | 760 | ||||
MCB | B 10A | 15 | 13 | 15 | 13 | 11 | 15 | 13 | 11 | 15 | 13 | 11 | 11 | 7 | ||||||||||
B 13A | 19 | 17 | 19 | 17 | 14 | 19 | 17 | 14 | 19 | 17 | 14 | 14 | 9 | |||||||||||
B 16A | 24 | 21 | 24 | 21 | 18 | 24 | 21 | 18 | 24 | 21 | 18 | 18 | 12 | |||||||||||
I nom. | B 20A | 30 | 26 | 30 | 26 | 22 | 30 | 26 | 22 | 30 | 26 | 22 | 22 | 15 | ||||||||||
B 25A | 37 | 32 | 37 | 32 | 28 | 37 | 32 | 28 | 37 | 32 | 28 | 28 | 18 | |||||||||||
C 10A | 24 | 21 | 24 | 21 | 18 | 24 | 21 | 18 | 24 | 21 | 18 | 18 | 12 | |||||||||||
C 13A | 32 | 28 | 32 | 28 | 24 | 32 | 28 | 24 | 32 | 28 | 24 | 24 | 16 | |||||||||||
Tref (µs) | C 16A | 40 | 35 | 40 | 35 | 30 | 40 | 35 | 30 | 40 | 35 | 30 | 30 | 20 | ||||||||||
C 20A | 49 | 43 | 49 | 43 | 37 | 49 | 43 | 37 | 49 | 43 | 37 | 37 | 24 | |||||||||||
C 25A | 62 | 54 | 62 | 54 | 46 | 62 | 54 | 46 | 62 | 54 | 46 | 46 | 31 |
Installation Steps
The document illustrates installation procedures for the Maxos Fusion luminaires:
- EL Version Installation: Shows steps for installing the luminaire with an integrated emergency lighting (EL) module. This involves connecting wires to specific terminals.
- Without Connector Side Installation: Depicts the process for luminaires installed without a dedicated connector side, also detailing wiring connections.
- Flexibility: A diagram highlights the flexibility of the luminaire system.
System IP Ratings and Configuration
Different system configurations and their associated IP ratings for optical areas are presented:
- LL500T + LL500X: IP20 (System), IP53 (Optical Area Only)
- LL500T + LL500XPCO: IP20 (System), IP54 (Optical Area Only)
- LL600T + LL600X: IP54 (System), IP65 (Optical Area Only)
IP54 Blind Cover Position: A diagram shows the correct positioning of a blind cover for IP54 rating, accompanied by a ⚠️ warning symbol.