User Guide for E Plus E Elektronik models including: EE160, EE160 Humidity and Temperature Sensor for Building Automation, EE160, Humidity and Temperature Sensor for Building Automation, Temperature Sensor for Building Automation, Sensor for Building Automation, Building Automation, Automation

Wolfgang Aichberger | E E Elektronik Ges.m.b.H.

Quick Guide EE160 372 KB

The Ideal Humidity and Temperature Sensor for Building Management

Quick Guide

Quick Guide EE160

下载中心


File Info : application/pdf, 2 Pages, 372.32KB

PDF preview unavailable. Download the PDF instead.

QG EE160
Quick Guide
EE160 - Humidity and Temperature Sensor for Building Automation
PLEASE NOTE Find this document and further product information on our website at www.epluse.com/ee160.

Electrical Connection
WARNING
Incorrect installation, wiring or power supply may cause overheating and therefore personal injuries or damage to property. It is essential that the cables are not under voltage during installation. No voltage must be applied when the product is connected or disconnected. For correct cabling of the device, always observe the presented wiring diagram for the product version used. The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling, installation, wiring, power supply and maintenance of the device.

Hardware Bus Termination
If required, the bus termination shall be realized with 120 Ohm resistor, by the jumper on the PCB. Jumper mounted  bus terminated Jumper not mounted  bus not terminated

Address Setting
Address Switch
0 1 00000000
0 1 11010000

Option
Address setting via PCS10 Product Configuration Software (= factory setting) All DIP switches at position 0  factory-set default address (245DEC, 0xF5) applicable, can be changed via software (PCS10 or Modbus protocol, permitted values: 1...247). Example: Address is set via configuration software.
Address setting via DIP switches DIP switches in any other position than 0 indicate the effective Modbus address which overrules the factory setting and any Modbus address set via PCS10 or Modbus command (permitted values: 1...247). Example: Address set to 11DEC (0000 1011BIN).

Modbus Register Map

The measurement data is saved as 32 bit float and as 16 bit signed integer values, see the Modbus Register map below.

FLOAT32

Parameter

Unit

Read register: function code 0x03 / 0x04

Temperature T

°C, °F3)

Relative humidity RH, Uw

%RH

Register number1) [DEC]
26 28

Register address2) [HEX]
19 1B

1) Register number starts from 1. 2) Register address starts from 0. 3) The choice of measurement units (metric or non-metric) is done at the time of ordering, see the ordering guide in the EE160 data sheet. It is not possible to switch
from metric to non-metric or vice versa by means of the PCS.

INT16 Parameter

Unit

Scale1) Register number2) [DEC]

Register address3) [HEX]

Read register: function code 0x03 / 0x04

Temperature T

°C, °F4)

100

301

12C

Relative humidity RH, Uw

%RH

100

302

12D

1) Example: For scale 100, reading of 2550 is equivalent to 25.5. 2) Register number starts from 1. 3) Register address starts from 0. 4) The choice of measurement units (metric or non-metric) shall be done when ordering, see the ordering guide in the datasheet.
Switching from metric to non-metric or vice versa using the PCS is not possible.

Quick Guide EE160

Modbus Setup
Baud rate Data bits Parity Stop bits Modbus address

Factory settings 9 600 8 Even 1 245

User selectable values (via PCS) 9 600, 19 200, 38 400, 57 600, 76 800, 115 200 8 None, odd, even 1, 2 1...247

The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, Even, 1.
The EE160 represents 1 unit load in a Modbus network.
Device address, baud rate, parity and stop bits can be set via:
 PCS Product Configuration Software and the appropriate configuration cable HA011018.  Modbus protocol in the register 1 (0x00) and 2 (0x01).
See Application Note Modbus AN0103 (available at www.epluse.com/ee160). The serial number as ASCII-code is located in read-only registers 1 - 8 (0x00 - 0x07, 16 bits per register). The firmware version is located in register 9 (0x08) (bit 15...8 = major release; bit 7...0 = minor release). The sensor name as ASCII-code is located in read-only registers 10 - 17 (0x09 - 0x11, 16 bits per register).

Communication settings (INT16) Parameter Write register: function code 0x06 Modbus address4) Modbus protocol settings4)

Register number1) [Dec]
1 2

Register address2) [Hex]
00 01

Device information (INT16) Parameter

Register number1) [Dec]

Register address2) [Hex]

Read register: function code 0x03 / 0x04

Serial number (as ASCII)

1

00

Firmware version

9

08

Sensor name (as ASCII)

10

09

1) Register number (decimal) starts from 1. 2) Register address (hexadecimal) starts from 0. 3) Number of registers 4) For Modbus address and protocol settings see Application Note Modbus AN0103 (available at www.epluse.com/ee160).

Size3)
1 1
Size3)
8 1 8

E+E Elektronik Ges.m.b.H. Langwiesen 7 4209 Engerwitzdorf | Austria T +43 7235 605-0 F +43 7235 605-8 info@epluse.com www.epluse.com

QG_EE160 | Version v1.5 | 09-2024 | All rights reserved | 302729

