HONEYWELL VISIONPRO TH8321U1097 (01)
Installation Guide

VisionPRO® TH8000 Series
Touch-screen Programmable Thermostat
This manual covers the following models
· TH8321U1097: For up to 3 Heat/2 Cool heat pump or up to 2 Heat/2 Cool conventional systems with dehumidification, humidification, or ventilation
(Pull thermostat from wallplate and turn over to find model number)
Must be installed by a trained, experienced technician
· Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition.
CAUTION: ELECTRICAL HAZARD Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
MERCURY NOTICE If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
This thermostat contains a Lithium battery which may contain Perchlorate material. Perchlorate Material--special handling may apply, See www.dtsc.ca.gov/hazardouswaste/perchlorate
Need Help?
For assistance with this product please visit http://customer.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502

® U.S. Registered Trademark. US Patent No. 6595430, D509151 and other patents pending.
Copyright © 2011 Honeywell International Inc. All rights reserved.
https://manual-hub.com/

69-2389-03

Installation Guide
Wallplate installation
1. Separate wallplate from thermostat. 2. Mount wallplate as shown below.
Drill 3/16" holes for drywall. Drill 7/32" holes for plaster.

Grasp top and bottom of wallplate and pull to remove from thermostat.

++ +

Wire hole

MCR29480
Mounting screws

Wall anchors

MCR29481

ENGLISH

69-2389--03

2
https://manual-hub.com/

Power options

VisionPROTM TH8000 Series

E/AUX

U1

U1

R

U1

U1

For 24VAC primary power, connect common side of transformer to "C" terminal.
Wiring

Insert supplied batteries for primary or backup power.

MCR29723

Push excess wire back into the wall opening. Plug wall opening with non-flammable insulation.

E/AUX

U1

U1

R

U1

U1

Terminal Designations

Conventional Terminal Letters:

R System power. Connect to secondary

side of system transformer.

C

Common wire from secondary side of

transformer.

W 1st stage heat relay.

W2 2nd stage heat relay.

Y

1st stage compressor contactor.

Y2 2nd stage compressor contactor.

G Fan relay.

S1/S2 Optional outdoor/remote/discharge

sensor.

U1/U1 Optional IAQ device

MCR29724

Heat Pump Terminal Letters:

R

System power. Connect to secondary

side of system transformer.

C

Common wire from secondary side of

system transformer.

Y

1st stage compressor contactor.

Y2 2nd stage compressor contactor.

E/Aux Auxiliary/Emergency heat relay.

G

Fan relay.

L

Heat pump reset (powered

continuously when System is set to

Em Heat; system monitor when set to

Heat, Cool or Off).

O/B Changeover valve for heat pumps.

S1/S2 Optional outdoor/remote/discharge

sensor.

U1/U1 Optional IAQ device

3
https://manual-hub.com/

69-2389--03

ENGLISH

Installation Guide

Wiring

Wiring guide--conventional systems

1H/1C System (1 transformer)

R

Power [1, 6]

W

Heat relay

Y

Compressor contactor

G

Fan relay

C

24VAC common [2]

S1/S2 Optional outdoor/remote/discharge

sensor

U1/U1 Optional IAQ relay

Heat Only System

R

Power [1]

W

Heat relay

C

24VAC common [2]

S1/S2 Optional outdoor/remote/discharge

sensor

U1/U1 Optional IAQ relay

Heat Only System (Series 20)

R

Series 20 valve terminal "R" [1]

W

Series 20 valve terminal "B"

Y

Series 20 valve terminal "W"

C

24VAC common [2]

S1/S2 Optional outdoor/remote/discharge

sensor

U1/U1 Optional IAQ relay

2H/2C System (1 transformer)

Y2 Cool relay 2

W2 Heat relay 2

R

Power [1, 6]

W

Heat relay 1

Y

Cool relay 1

G

Fan relay

C

24VAC common [2]

S1/S2 Optional outdoor/remote/discharge

sensor

U1/U1 Optional IAQ relay

Heat Only System With Fan

R

Power [1, 6]

W

Heat relay

G

Fan relay

C

24VAC common [2]

S1/S2 Optional outdoor/remote/discharge sensor

U1/U1 Optional IAQ relay

Cool Only System

R

Power [1]

Y

Compressor contactor

G

Fan relay

C

24VAC common [2]

S1/S2 Optional outdoor/remote/discharge

sensor

U1/U1 Optional IAQ relay

ENGLISH

See [notes] below [1] Power supply. Provide disconnect means and overload protection as required. [2] Optional 24VAC common connection. [6] Only works with single transformer systems.

69-2389--03

4
https://manual-hub.com/

VisionPROTM TH8000 Series

Wiring

Wiring guide--heat pump systems

1H/1C Heat Pump (no auxiliary heat)

R

Power [1]

O/B Changeover valve [3]

Y

Compressor relay

G

Fan relay

C

24VAC common [2]

S1/S2 Optional outdoor/remote/discharge

sensor

U1/U1 Optional IAQ relay

2H/1C Heat Pump (with auxiliary heat)

L

Equipment monitor [4, 5]

E/Aux Auxiliary/emergency heat relay

R

Power [1]

O/B Changeover valve [3]

Y

Compressor relay

G

Fan relay

C

24VAC common [2, 4]

S1/S2 Optional outdoor/remote/discharge

sensor

U1/U1 Optional IAQ relay

2H/2C Heat Pump (no auxiliary heat)

Y2 Compressor 2 relay

R

Power [1]

O/B Changeover valve [3]

Y

Compressor 1 relay

G

Fan relay

C

24VAC common [2]

S1/S2 Optional outdoor/remote/discharge

sensor

U1/U1 Optional IAQ relay

3H/2C Heat Pump (with auxiliary heat)

Y2 Compressor 2 relay

L

Equipment monitor [4, 5]

E/Aux Auxiliary/Emergency heat relay

R

Power [1]

O/B Changeover valve [3]

Y

Compressor 1 relay

G

Fan relay

C

24VAC common [2, 4]

S1/S2 Optional outdoor/remote/discharge

sensor

U1/U1 Optional IAQ relay

Wiring guide--humidification systems

Steam humidifier (or any humidifier with

its own transformer)

R

Power [1]

U1 Humidifier relay [7]

U1 Humidifier relay [7]

Bypass, flow-through humidifier (or any

humidifier that uses the system trans-

former)

R

Power [1]

U1 Field jumper R to U1 [7]

U1 Humidifier relay [7]

Wiring guide--dehumidification systems

Whole house dehumidifier

R

Power [1]

U1 Dehumidifier relay [7]

U1 Dehumidifier relay [7]

A/C with low-speed fan

R

Power [1]

U1 Field jumper R to U1 [7]

U1 Dehumidifier relay [8]

Wiring guide--ventilation systems

Whole house powered ventilator

R

Power [1]

U1 Ventilator relay [7]

U1 Ventilator relay [7]

Non-powered ventilator

R

Power [1]

U1 Field jumper R to U1 [7]

U1 Ventilator relay

See [notes] below [1] Power supply. Provide disconnect means and overload protection as required. [2] Optional 24VAC common connection. [3] O/B set to control as either O or B in installer setup. [4] If L terminal is used, 24VAC common (terminal C) must be connected. [5] Heat pump reset (powered continuously when thermostat is set to Em. Heat; system monitor when set to Heat, Cool, or Off). [7] Terminals are normally open dry contacts. [8] Equipment must include dehumidification terminal for low-speed fan.
5

69-2389--03

ENGLISH

https://manual-hub.com/

Installation Guide
Remove tab and mount thermostat
Remove tab.

Align pins on back of thermostat with slots in wallplate, then push gently until thermostat snaps into place.

MCR29484

Set date and time

Press st to set date
Press st to set month
Press st to set year

TUE
2010

Press st to set time
15
6

TUE
1:00PM

DONE

Press DONE to save changes.

Installer setup

1 Press SYSTEM

2 Press and hold for 5 seconds 3 Change settings (see p. 7-9)

TUE FAN
70 Inside
AUTO

SYSTEM
HEAT
6:00aM

SYSTEM
HEAT
6:00aM

DONE
Function

CANCEL
Setting

SCHED HOLD

0120 20

DONE

MCR29746

Press DONE to save and exit.

Press DONE to save & exit
0120 20
DONE

69-2389--03

DONE
Press s t to change

6
https://manual-hub.com/

MCR29745

ENGLISH

Installer setup

Setup functions

0120

Year (first two digits)

0130

Year (second two digits)

0140

Month

0150

Date

0160

Schedule format

0165

Restore energy saving

0170

System type

0173 0180 0190 0200 0210 0220 0230 0240
0250

Heat Pump Type
Fan control (heating) Changeover valve (O/B terminal) Auxiliary heat
External fossil fuel kit 1st stage compressor cycle rate 2nd stage compressor cycle rate 1st stage heat cycle rate (CPH= cycles per hour)
2nd stage heat cycle rate (CPH)

0260

3rd stage heat cycle rate (CPH)

VisionPROTM TH8000 Series

Settings & Options (factory default in bold)
20 (2000-2099) 21 (2101-2178)
10 (2010) [Other options: 00-99]
6 [Other options: 1-12]
15 [Other options: 1-31]
4 7-day programming 0 Non-programmable
0 No 1 Yes
1 1 heat/1 cool conventional 2 1 heat/1 cool heat pump (no aux. heat) 3 Heat only (2-wire systems) 4 Heat only with fan 5 Hot water Series 20 system (power to open & close zone
valves/normally open zone valves) 6 Cool only 7 2 heat/1 cool heat pump (with aux. heat) 8 2 heat/2 cool multistage conventional 9 2 heat/1 cool multistage conventional 10 1 heat/2 cool multistage conventional 11 2 heat/2 cool heat pump (no aux. heat) 12 3 heat/2 cool heat pump (with aux. heat)
0 Air to Air heat pump 1 Geothermal heat pump
0 Gas/Oil heat (equipment controls heating fan) 1 Electric furnace (thermostat controls heating fan)
0 O/B terminal controls valve in cooling 1 O/B terminal controls valve in heating
0 Electric backup heat 1 Fossil fuel backup heat
1 External fossil fuel kit controls backup heat 0 Thermostat controls backup heat (outdoor sensor required)
3 Recommended for most compressors [Other options: 1, 2, 4, 5 or 6 CPH]
3 Recommended for most compressors [Other options: 1, 2, 4, 5 or 6 CPH]
5 Gas or oil furnaces of less than 90% efficiency 1 Steam or gravity systems 3 Hot water systems & furnaces of 90%+ efficiency 9 Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH] 5 Gas or oil furnaces of less than 90% efficiency 1 Steam or gravity systems 3 Hot water systems & furnaces of 90%+ efficiency 9 Electric furnaces
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]
9 Electric auxiliary heat or electric furnaces 1 Steam or gravity systems 3 Hot water systems & furnaces of 90%+ efficiency 5 Gas or oil furnaces of less than 90% efficiency
[Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH]

Continued on next page

7

69-2389--03

https://manual-hub.com/

ENGLISH

Installation Guide

Installer setup

Setup functions

0280

Backlight

0300 0310 0320 0330 0340

Manual/Auto changeover Auto changeover deadband Temperature display Daylight savings
Remote sensor

0345 0346 0347 0350 0360 0371
0372

Dual Fuel Heat Pump Control **
Dual fuel heat pump upstage to furnace timer ** Droop temperature
Heat pump compressor lockout Heat pump auxiliary lockout Indoor Air Quality device on U1/U1
Humidification Control

0374

Hum fan action

0379

Dehumidification Control

0380

Dehumidify with air conditioner

0383 0384 0386

Over cooling limit
Dehumidification fan control Whole house dehumidification lockout

69-2389--03

Settings & Options (factory default in bold)

0 Backlight on for approx. 8 seconds after keypress 1 Backlight always on low intensity, full bright after keypress
(requires 24VAC connection)

0 Manual changeover (Heat/Cool/Off) 1 Automatic changeover (Heat/Cool/Auto/Off)

3 Heat/cool temperature 3°F apart (1.5°C) [Other options: 2-9 (2°F to 9°F/1°C to 5°C)]

** See page 11

0 Fahrenheit 1 Celsius

2 Auto-change to daylight saving time 0 Daylight saving time is turned off

0 No remote sensor 1 Outdoor sensor (display only) 2 Outdoor sensor for control (select lockouts and frost protec-
tion) ** See page 11 3 Indoor sensor 4 Discharge air sensor (Required for Desert humidity control)
** See page 11

1 Droop Control 0 No droop control 2 Droop control with aux heat lockout

1 1 hour 0 Off
[Other options: 0.5, 1.5, 2-6, 8, 10, 12, 14, 16 hours]

2 2°F (1°C) [Other options: 2-5 (2°F to 5°F/1°C to 2.5°C)]

0 No heat pump compressor lockout [Other options: 5­60°F (-15°C to 15.5°C)] ** See page 11

0 No heat pump auxiliary lockout [Other options: 5­65°F (-15°C to 18.5°C)] ** See page 11

0 None 1 Humidification 2 Dehumidification
3 Ventilation

0 Off 1 Humidify with no frost protection 3 Humidify with frost protection 8 Desert humidity control in heat, off, or cool; DATS required

0 Humidify only while fan is on 1 Humidifier forces fan on
2 Humidify only when heat it on 3 Humidifier operates independent of fan

0 None
1 Air conditioning with low speed fan 3 Whole house dehumidification
0 No dehumidification control 1 Thermostat controls dehumidification with air conditioner
high speed fan ** See page 11

3 3°F (1.5°C)
[Other options: 1-2 (1°F to 2°F/.5°C to 1°C)]
0 Fan turns on with dehumidifier 1 Dehumidifier operates independent of fan

0 Off 1 On

** See pages 11­12 Continued on next page

8

ENGLISH

https://manual-hub.com/

Installer setup

Setup functions

0390

Dehumidification Away

Mode

0391

Dehumidification Away

Mode Fan Setting

0392
0393 0394 0400

Dehum. Away Mode Low Limit Temperature Setting
Dehum. away mode temp. setting
Dehum. Away Mode Dehum. Setting
Ventilation control

0401 0402 0403 0404

Number of bedrooms Size of home
Ventilation level
Max. ventilation limit

0405 0430

Ventilation fan action Ventilation lockout

0431 0432 0500

Ventilation high temperature lockout
Ventilation low temperature lockout Furnace filter change reminder

0502 0510
0520

Furnace filter alert options Humidifier pad change reminder
UV lamp change reminder

VisionPROTM TH8000 Series

Settings & Options (factory default in bold)
0 No 1 Yes
0 Fan auto 1 Fan on 2 Fan circulate
76 Low limit temperature 76°F (24°C) [Other options: 70°F to 80°F (21°C to 27°C)]

85 Low limit away temperature 85°F (29°C) [Other options: 70°F to 99°F (21°C to 37°C)]

65 Away humidity level 65% [Other options: 40% to 70%]

0 No ventilation 1 Vent on during all periods 2 Vent off during sleep period 3 Vent on during all periods with lockouts 4 Vent off during sleep period with lockouts

2 Two bedrooms [Other options: 1 to 6]

10 1,000 square feet} [Other options: 11 to 50 (1,100 to 5,000 square feet)]

160 CFM (cubic feet per minute) [Other options: (30 to 195 CFM)]

50 50% ventilation limit [Other options: 30% to 60% or 100%]
P Meets ASHRAE 62.2 standard F Does not meet ASHRAE 62.2 standard

1 Ventilation on forces fan on 2 Ventilation does not force fan on

0 Off 1 Lockout for high temperatures ** See page 11 2 Lockout for low temperatures ** See page 11 3 Lockout for high and low temperatures ** See page 11

100 100°F (38°C): Settings 5°F apart (3°C) [Other options: (90°F to 110°F/32°C to 43.5°C)]

-10 -10°F (-23.5°C): Settings 5°F apart (3°C) [Other options: (-20°F to 0°F/-29°C to -18°C)]

0 Off 1 10-day run time 2 30-day run time 3 60-day run time 4 90-day run time 5 120-day run time 6 180-day run time 7 270-day run time

8 365-day run time 9 30 calendar days 10 60 calendar days 11 90 calendar days 12 120 calendar days 13 180 calendar days 14 365 calendar days

0 Timer counts Heat & Cool run time 1 Timer counts Cool run time only

0 Off 1 90 calendar days 2 180 calendar days 3 365 calendar days

0 Off 1 1 year 2 2 years

Continued on next page

9

69-2389--03

ENGLISH

https://manual-hub.com/

Installation Guide

Installer setup

Setup functions

0530 0540

Adaptive Intelligent RecoveryTM Program periods

0580 0600 0610 0640

Compressor protection Heat temperature range stop Cool temperature range stop Clock format

0650

Extended fan timer (heat)

0660

Extended fan timer (cool)

0670

Keypad lock

0680
0690
0700 0701 0710

Heat temperature control
Cool temperature control
Temperature display offset Humidity display offset
RESET

Settings & Options (factory default in bold)
1 On ** See page 11 0 Off
4 4 program periods (Wake, Leave, Return, Sleep) 2 2 program periods (Wake, Sleep)
5 5 minute compressor off time ** See page 11 [Other options: 0, 1, 2, 3 or 4-minute off time]
90 Max. heat temperature setting is 90°F (32°C) [Other options: 40-89°F (4°C to 32°C)]
50 Min. cool temperature setting is 50°F (10°C) [Other options: 51-99°F (11°C to 37°C)]
12 12-hour time (i.e., "3:30 pm") 24 24-hour time (i.e., "15:30")
0 Off [Other options: Fan runs for 30, 60, 90, or 120 seconds after call for heat ends]
0 Off [Other options: Fan runs for 30, 60, 90, or 120 seconds after call for cool ends]
0 Keypad unlocked (fully functional) 1 Partially locked (access to temperature settings only) 2 Fully locked
2 Standard temperature control (recommended) 1 Choose if room is warmer than set temperature 3 Choose if room does not reach set temperature
2 Standard temperature control (recommended) 1 Choose if room is cooler than set temperature 3 Choose if room does not reach set temperature
0 Thermostat displays actual room temperature [Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)
0 0% [Other options: -12% to 12%]
0 No reset 1 Reset installer options & program schedule to factory de-
fault (only date and time settings are retained)

ENGLISH

Installer system test
During installer setup, press t repeatedly until "Test" appears.
0120 20

Test number

System status
1

DONE

TEST

0

69-2389--03

Press DONE to terminate testing. 10
https://manual-hub.com/

DONE
Press st to select test

MCR29488
Press st to change status

VisionPROTM TH8000 Series

Installer system test

System test 1 Cooling system
2 Fan system 3 Heating system
4 Emergency heating system
5 Humidifier 6 Dehumidifier 7 Ventilator

System status

0 Compressor and fan turn off 1 Compressor and fan turn on 2 Second stage compressor turns on 0 Fan turns off 1 Fan turns on

0 Heat and fan turn off 1 Heat turns on (fan on if Function 0170 is set for heat pump,
or if Function 0180 is set to "1") ** See page 6 2 Second stage heat turns on 3 Third stage heat turns on

0 Heat and fan turn off 1 Heat and fan turn on 0 Off 1 Humidifier on 0 Off 1 Dehumidifier on 0 Off 1 Ventilator on

CAUTION: EQUIPMENT
DAMAGE HAZARD. Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.

Special functions

Auto Changeover (Setup Function 0300): When set to Auto, the thermostat automatically selects heating or cooling depending on the indoor temperature. Heat and cool settings must be at least 2 degrees apart. If function 0380 is set to On, the heat and cool settings must be at least 5 degrees apart.
Remote Sensor (Setup Function 0340): If an optional outdoor sensor is installed, the thermostat can display the outside temperature. If an optional remote indoor sensor is installed, the thermostat will display the temperature at the sensor location (the internal sensor in the thermostat is not used). A Discharge Air Temperature Sensor (DATS) is required to enable desert humidification.
Adaptive Intelligent Recovery (Setup Function 0530): Allows the thermostat to "learn" how long the furnace and air conditioner take to reach programmed temperature settings, so the temperature is reached at the scheduled time.
Compressor Protection (Setup Function 0580): Forces the compressor to wait a few minutes before restarting, to prevent damage. During this time, the message "Wait" is displayed. Dehumidification control (Setup Function 0380): TH8321 models monitor the indoor humidity level and automatically activate the cooling system to reduce humidity by lowering the temperature by up to 3 degrees below the current cool setting. When Setup Function 0371 is set to dehumidification, the U1/U1 relay can be set to control dehumidification.
Heat Pump Control -- Electric Backup (Setup Functions 0350-0360): If an outdoor temperature sensor is installed, select a compressor lockout temperature (Function 0350). Below this temperature, only electric heat operates. Also select an auxiliary lockout temperature (Function 0360). Above this temperature, only the compressor operates. Between these temperatures, both heat sources operate.
Heat Pump Control -- Fossil Fuel Backup (Setup Function 0345): Option 0 (No Droop Control): If outdoor temperature is above balance point (Function 0350), only the compressor operates. Below this temperature, only backup heat operates. Option 1 (Droop Control): As above, but backup heat is activated if room temperature drops to the selected droop temperature setting (compressor is deactivated). Option 2: (Droop Control with Aux Heat lockout): Compressor works only above auxiliary lockout temperature, backup heat works only below balance point, 2° droop between temperatures.
If temperature is not reached in a reasonable time, set the upstage timer (Function 0346). After the designated time, the compressor will be deactivated and the system will switch to backup heat.
Ventilation Control (Setup Functions 0400-0432): If the system includes a self-powered ventilation unit (Function 0400), the home can be ventilated on demand. Ventilation can also be locked out based on high and low outdoor temperature (Function 0431 & 0432)--outdoor temperature sensor required.
Dehumidification Away Mode (Setup Functions 0390-0394): This feature is useful for homes in southern climates. It allows humidity control when the the home is unoccupied for long periods during the hot/humid season. You can control temperature (Function 0393) and dehumidification (Function 0394) while away. You can control humidity with a dehumidifier or a cooling system (Function 0379). If a cooling system is used, humidity is controlled by cooling indoor air to the Low Limit Temperature (Function 0392). When the desired humidity is reached, the system will maintain the temperature you select in Function 0393.
Indoor Air Quality Device (Setup Function 0371): This feature allows the thermostat to control one of the following IAQ devices: whole house humidifier, dehumidifier, or ventilator.
11

69-2389--03

ENGLISH

https://manual-hub.com/

Installation Guide
Accessories & replacement parts
Please contact your distributor to order replacement parts.
Outdoor temperature sensor...............................................Part Number C7089U1006 Remote indoor temperature sensor ...................................Part Number C7189U1005 Discharge air temperature sensor .....................................Part Number C7735A1000 Energy recovery ventilator ..................................................Part number ER200B2006 Heat recovery ventilator ......................................................Part number HR200B1005 Fresh air damper ..................................................................Part number EARD6 Bypass flow through humidifier .........................................Part number HE265A1007 TrueSTEAM humidifier..........................................................Part number HM512W1005 Cover plate*...........................................................................Part Number 32003796-001 *(Use to cover marks left by old thermostats.)

Specifications
Temperature Ranges · Heat: 40° to 90°F (4.5° to 32°C) · Cool: 50° to 99°F (10° to 37°C)
Operating Ambient Temperature · 0° to 120°F (-18° to 48.9°C)
Shipping Temperature · -30° to 150°F (-34° to 66°C)
Operating Relative Humidity · 5% to 90% (non-condensing)
Physical Dimensions · 4-9/16" H x 6" W x 1-3/8" D · 116 mm H x 152 mm W x 35 mm D

Electrical Ratings

Terminal

Voltage (50/60Hz)

W Heating

20-30 Vac

(Powerpile)

750 mV DC

W2 Heating

20-30 Vac

Y Cooling

20-30 Vac

Y2 Cooling

20-30 Vac

E/Aux Auxiliary/ Emergency heat

20-30 Vac

O/B Changeover

20-30 Vac

L Heat pump reset

20-30 Vac

U1/U1 IAQ relay 20-30 Vac

20-30 Vac

Running Current 0.02-1.0 A 100 mA DC 0.02-0.6 A 0.02-1.0 A 0.02-0.6 A
0.02-1.0 A 0.02-0.6 A 0.02-0.6 A