Owner's Manual for Soler Palau models including: MBE-100-04B-R, MBE-100-08B-R, MBE-125-04B-R, MBE-125-08B-R, MBE-125-12B-R, MBE-160-07B-R, MBE-160-14B-R, MBE-160-21B-R, MBE-200-20T-R, MBE-200-30T-R, MBE-200-40T-R, MBE-200-50T-R, MBE-200-60T-R, MBE-250-20T-R, MBE-250-30T-R, MBE-250-40T-R, MBE-250-50T-R, MBE-250-60T-R, MBE-250-90T-R, MBE-315-, MBE-100-04B-R Electric Heaters with Regulation Incorporated, MBE-100-04B-R, Electric Heaters with Regulation Incorporated, Heaters with Regulation Incorporated, Regulation Incorporated, Incorporated

EN MBE-R

ELECTRIC HEATERS WITH REGULATION INCORPORATED MBE-R Series


File Info : application/pdf, 3 Pages, 1.33MB

PDF preview unavailable. Download the PDF instead.

EN MBE-R
ELECTRIC HEATERS WITH REGULATION INCORPORATED MBE-R Series
Designed to be installed on the fans discharge side.The minimum air speed through the heater must be 1,5 m/s. Maximum air temperature through the heater: 40ºC. The heaters are fitted with: - Tubular structure made of galvanized steel with
watertight joints at the entrance and outlet. - Electrical heater regulation, incorporated. - Stainless steel AISI-304 / AISI-321 armoured
heating element. - Double protection circuit to connect to the
heater control circuit by means of a safety overheat automatic thermostat connected in series with another safety overheat manual reset thermostat (RESET). - Wiring box IP43. For the correct operation of the electric coils it is necessary to use different accessories and installation elements (temperature probe, protection pressure switch, contactors, etc.) which are specified in the corresponding instructions, depending on the installation to be carried out.

TECHNICAL CHARACTERISTICS
Modelo
MBE-100/04B-R MBE-100/08B-R
MBE-125/04B-R MBE-125/08B-R MBE-125/12B-R
MBE-160/07B-R MBE-160/14B-R MBE-160/21B-R
MBE-200/20T-R MBE-200/30T-R MBE-200/40T-R MBE-200/50T-R MBE-200/60T-R
MBE-250/20T-R MBE-250/30T-R MBE-250/40T-R MBE-250/50T-R MBE-250/60T-R MBE-250/90T-R
MBE-315/30T-R MBE-315/60T-R MBE-315/90T-R MBE-315/120T-R
MBE-355/60T-R MBE-355/90T-R MBE-355/120T-R
MBE-400/60T-R MBE-400/90T-R MBE-400/120T-R MBE-400/150T-R
MBE-450/90T-R MBE-450/150T-R
MBE-500/60T-R MBE-500/90T-R MBE-500/120T-R

Voltage (V)
1/230 1/230
1/230 1/230 1/230
1/230 1/230 1/230
2/400 2/400 2/400 2/400 2/400
2/400 2/400 2/400 2/400 2/400 3/400
2/400 2/400 3/400 3/400
2/400 3/400 3/400
2/400 3/400 3/400 3/400
3/400 3/400
2/400 3/400 3/400

www.solerpalau.com

Power (W) 400 800
400 800 1200
700 1400 2100
2000 3000 4000 5000 6000
2000 3000 4000 5000 6000 9000
3000 6000 9000 12000
6000 9000 12000
6000 9000 12000 15000
9000 15000
6000 9000 12000

Minimum airflow (m3/h) 50 50
70 70 70
110 110 110
170 170 170 170 170
270 270 270 270 270 270
430 430 430 430
540 540 540
680 680 680 680
860 860
1.070 1.070 1.070

Ø (mm)
100 100
125 125 125
160 160 160
200 200 200 200 200
250 250 250 250 250 250
315 315 315 315
355 355 355
400 400 400 400
450 450
500 500 500

Heating range MBE-R

843

ELECTRIC HEATERS WITH REGULATION INCORPORATED MBE-R Series

DIMENSIONS (mm)

Model

D

290

A

MBE-100

100

MBE-125

125

MBE-160

160

MBE-200

200

MBE-250

250

MBE-315

315

B

MBE-355

355

MBE-400

400

MBE-450

450

MBE-500

500

50 400

PERFORMANCE CURVES MBE - Pressure drop p (Pa)
[Pa]
120

80

40

0

1

2

3

4

5

Model 100/04B 100/08B 125/04B 125/08B 125/12B 160/07B 160/14B 160/21B 200/21B 200/20T 200/30T 200/40T 200/50T 200/60T 200/90T

Curve 1 7 1 5 6 1 4 5 2 2 4 5 6 7 10

Model 250/20T 250/30T 250/40T 250/50T 250/60T 250/90T 315/30T 315/60T 315/90T 315/120T 315/150T 355/60T 355/90T 355/120T 355/150T

6

7

Curve 1 2 2 4 5 7 1 2 4 5 8 2 3 4 7

10
9 8
7
6
5 4 3 2 1

8

9 [m/s]

Model 355/180T 400/60T 400/90T 400/120T 400/150T 400/180T 450/90T 450/150T 500/60T 500/90T 500/120T 500/150T 500/180T

Curve 9 1 2 3 8 10 2 7 1 1 2 4 7

SELECTION EXAMPLE
DATA: - Airflow: 700 m3/h (Q) - Temp. of supplied air: 5ºC - Temp. of exhausted air: 27ºC
ELECTRIC HEATER POWER REQUIRED: P = Qx0,36xT = 700x0,36x22 = 5544 W
HEATER SELECTION MBE-200/50T-R or MBE-250/60T-R (Diagram 2) The final selection depends on: - Total system pressure drop - Desired sound level - Available space

844

Heating range MBE-R

www.solerpalau.com

ELECTRIC HEATERS ACCESSORIES
ELECTRIC HEATER ACCESSORIES For more information see electrical accessories.
PULSER Single phase electric heater controller.
TTC-2000 Three phase electric heater controller.
TG-R Room temperature sensor. TG-R430: Adjustable TG-R530: Not adjustable
PRESOSTATO DPS Differential pressure switch.
TT-S4/D Module to increase the controller power TTC-40F, up to 66kW.

TTC-25 and TTC-40F Three phase electric heater controller.
TT-S1 Additional PCB to increase the output power controlled.
TG-K Duct temperature sensor.
TBI-10 / TBI-30 External potentiometer.
TRAFO-15D Transformer to power the TT-S4/D to 24V.

www.solerpalau.com

Heating range ACCESSORIES

845



References

Adobe PDF Library 15.0 Adobe InDesign CC 13.1 (Macintosh)