ComfortStar VRF Troubleshooting Guide

ORBIT VRFPLUS™ APPLIED COMMERCIAL AIR CONDITIONING

VRF Error Table

Fault or protect definition

Code Fault or protect definition Code Fault or protect definition
E0 Outdoor communication failures XH9 3 times P9 protection in 30 minutes
E1 Sequence fault P0 Reserve
E2 Indoor and host communication failures P1 High pressure protection
E3 Exhaust temperature sensor fault P2 Low pressure protection
E4 Environmental temperature sensor T4 fault XP3 INV over AC current protection
E5 T6A Plate heat exchanger inlet sensor fault P4 Exhaust temperature is too high to protect
E6 T3 Condensate temperature sensor fault P5 Condensate T3 high temperature protection
E7 T6B Plate heat exchanger outlet sensor fault XP6 IPM module protection
E8 Outdoor address fault P7 The lack of the degree of superheat
E9 AC voltage protection XPA Temperature sensor T8 is too high to protect
EA Refrigerant cooling copper tube temperature sensor fault XP9 DC fan module protection
XH0 Communication failures between module board and main control board XLO DC compressor module fault
H1 Communication failures between main chip and slave chip of the main control board XL1 DC low voltage protection
H2 The decrease in the number of outdoor failures XL2 DC high voltage protection
H3 The increase in the number of outdoor failures XL4 MCE fault/synchronous/closed loop
XH4 3 times P6 protection in 60 minutes XL5 Zero speed protection
H5 3 times P2 protection in 60 minutes XL7 Phase sequence error protection
H6 3 times P4 protection in 100 minutes XL8 A moment before and after the speed change > 15 Hz
H7 The decrease in the number of indoor failures XL9 Set speed and the actual speed difference > 15 Hz
H8 Pressure sensor fault PA---- Need to enter password prompt for password
XH9 3 times P9 protection in 30 minutes XP8 Drive type mismatch
XH9 3 times P9 protection in 30 minutes XH9 3 times P9 protection in 30 minutes

VRF Operating Parameters Table

LED display in check procedures

No. Display Reference values No. Display Reference values
1 Current frequency (indoor unit quantity when unit in standby mode) 0, 1, 2, 3 35 Secondary side current of inverter compressor B Actual value (A)
2 This outdoor unit address 0-F, The corresponding number of outdoor units is shown in the table on the nameplate of the outdoor unit 36 AC voltage Actual value = Display value * 4(V)
3 This outdoor unit capacity address Available for master unit only 37 DC bus line voltage of compressor A Actual value = Display value * 4(V)
4 Number of online outdoor units When paralleling, available for master unit only 38 DC bus line voltage of compressor B Actual value = Display value * 4(V)
5 Total capacity of outdoor units Master display only 39 Priority mode 0: Auto priority 1: Heating priority 2: Cooling priority 3: Heating only 4: Cooling only 5: VIP priority and auto priority
6 Number of outdoor units in operation Master-slave display 40 Silence mode 0: Standard mode; 1: Silence mode 1; 2: Silence mode 2; 3: Silence mode 3; 4: Night silence mode
7 Total HP of outdoor units in operation The maximum total number of indoor units used to communicate with outdoor units 41 Static pressure mode 0: Standard mode; 1: Low pressure; 2: Medium pressure; 3: High pressure; 4: Super high pressure
8 Maximum online indoor units quantities Current total number of indoor units communicating with outdoor units 42 VIP indoor unit address 0: Normal 1: Excessive refrigerant 2: Serious excessive refrigerant 11: Lack of refrigerant 12: Lack of much refrigerant 13: Lack of too much refrigerant
9 Current online indoor units quantities Current total number of indoor units in operation 43 Refrigerant status Factory default 8, setting range: 5-15
10 Quantities of indoor units in operation 0: Off or fan only 2: Cooling only 3: Heating only 4:Forced cooling 5: Forced heating 44 T2B condition A Factory default 44, setting range: 40-50
11 Running mode 0: Off or fan only 2: Cooling only 3: Heating only 4:Forced cooling 5: Forced heating 45 T2 condition B Factory default 100%, setting range: 100%-40%
12 Total capacity demand of indoor units Available for master unit only 46 Energy saving value Factory default 10 minutes, setting range: 5-20 minutes
13 Amended capacity demand for the master unit Available for master unit only 47 Maximum defrost time Factory default 15°C, setting range: 10-18°C
14 Output capacity of outdoor unit Actual output HP 48 Defrosting T3 temperature exit condition Factory default 60 minutes, can be set as 60,120,180,240,480
15 Low pressure value Actual value= Display value * 0.01 (Mpa) 49 Allowed offline time of indoor unit Factory default 2, setting range: 0-6
16 High pressure value Actual value= Display value * 0.1 (Mpa) 50 Number of allowed offline indoor units Reserve
17 Fan speed range 0~36 51 Reserve 0-No correction
18 Average temperature of evaporators T2/T2B Actual value (°C) 52 T2B correction plus or minus 4-Unit number correction (No T2B average correction) 5-Number of units+T2B average correction+3 6-Number of units+T2B
19 Temperature of condenser outlet T3 Actual value (°C) 53 Reserve Reserve
20 Ambient temperature T4 Actual value (°C) 54 Reserve Reserve
21 Temperature sensor T5 Reserve 55 Compressor A drive code 0246
22 Inlet temperature (T6A) of plate heat exchanger Actual value (°C) 56 Compressor B drive code 0246
23 Outlet temperature (T6B) of plate heat exchanger Actual value (°C) 57 Frequency limitation of inverter compressor A 0: Unlimited frequency 1: T4 frequency limiting Pressure frequency limiting 3: Voltage frequency limiting Exhaust frequency limiting 5: Current frequency limiting 6: P6 frequency limiting 7: Module temperature limiting
24 Discharge temperature of inverter compressor A Actual value (°C) 58 Frequency limitation of inverter compressor B Unlimited frequency 1: T4 frequency limiting Pressure frequency limiting 3: Voltage frequency limiting Exhaust frequency limiting 5: Current frequency limiting 6: P6 frequency limiting 7: Module temperature limiting
25 Discharge temperature of inverter compressor B Actual value (°C) 59 Reserve Reserve
26 Temperature sensor T8 Actual value (°C), Internal temperature of IPM 60 Last time error fault or protection code No protection or fault display 00
27 Temperature of IPM A Actual value (°C), Internal temperature of IPM
28 Temperature of IPM B Actual value (°C)
29 Superheat degree of compressor Actual value (°C)
30 Refrigerant cooling copper tube temperature 8-24HP:Actual value = Display value * 8 26-32HP: Actual value = Display value * 8*6 Actual value = Display value * 8
31 Opening degree of EXV A 0-OFF; 1-Minimum opening; 2-Automatic adjustment
32 Opening degree of EXV C 0-OFF; 1-Minimum opening; 2-Automatic adjustment
33 Auxiliary valve adjustment interval 0-OFF; 1-Minimum opening; 2-Automatic adjustment
34 Current of inverter compressor A Actual value (A)
35 Current of inverter compressor B Actual value (A)
36 Secondary side current of inverter compressor A Actual value (A)

VRF trouble shooting

E0: Outdoor unit communication error

Reason: The communication between the slave unit and the master unit is lost, and the slave show error.

Solution:

  • Check whether the connection wire between the main board of the master and slave unit to the communication terminal is normal and whether the connection is firm.
  • Check whether the communication line H1H2E of the master and slave unit is connected correctly, connect the corresponding letters hand in hand, prohibit star connection, use a multimeter to measure whether the communication line is open current/short current.
  • If there is no problem with the above steps, replace the communication board or main control board.

VRF trouble shooting

E1: Phase sequence malfunction

Reason: Three-phase power supply phase sequence error or lack of phase (This fault is only reflected when phase B is missing, phase A is missing, the main control board is out of power, phase C is missing, and the fan module is out of power).

Solution:

  • Use a multimeter to measure the phase voltage, whether it is between 220-240V, to ensure that there is no lack of phase.
  • Check whether the power supply of the filter board is normal, the line voltage is 380V, if it is not normal, replace the filter board.
  • The above steps are normal, replace the main control board.

VRF trouble shooting

E2: Communication failure between indoor unit and outdoor unit

Reason: Communication failure between indoor unit and outdoor unit

Solution:

  • Check whether the communication wire between the communication board and the main control board is normal, confirm that the wiring is firm and the wiring harness is not damaged, then proceed to the next step.
  • Check whether the communication wire PQE uses 2-core shielded wire and connect it correctly. Star connection is forbidden. It must be P to P, Q to Q, E to E.
  • Check whether there is an open circuit/short circuit in the communication wire. Use a multimeter to measure the resistance between PQ to see if there is a short circuit; if there is no short circuit, short circuit PQ, and measure whether there is open circuit from the PQ terminal of outdoor unit.
  • Confirm that there is no problem with the communication wire, then check whether all the indoor unit are powered on, whether the indoor unit have addresses, make sure that the indoor unit are powered on and have addresses, if there is no address, please refer to the internal machine FE troubleshooting.
  • If there is no problem with the above steps, it may be communication interference. Connect a 100Ω resistance between the PQ of the last indoor unit of system. If it still cannot be solved, check the interference source and eliminate it. If it still does not solve the problem, replace the communication board/main board.

VRF trouble shooting

E3/E4/E5/E6/E7/EA: Sensor failures (Exhaust gas temperature sensor TP/ambient temperature sensor T4/plate exchange inlet T6A sensor/condenser temperature T3 sensor/plate exchange outlet T6B sensor failure/refrigerant heat dissipation copper pipe sensor T8)

Reason: Sensor reading error or sensor is damaged

Solution:

  • Confirm whether the sensor is firmly connected to the main board, reconnect it firmly, or if it is faulty, proceed to the next step.
  • Unplug the sensor, measure the resistance of the sensor, whether it is open/short, if yes, replace the sensor group, otherwise replace the main board.
  • E3 exhaust sensor failure may be inaccurate resistance (After running for 10 minutes, Pc≥3.0MPa, TP<15℃).

VRF trouble shooting

E8: Outdoor unit address error

Reason: Outdoor unit address dialing error

Solution:

  • Check the dialing codes of the master and slave unit, perform the dialing according to the SW6 dialing introduction, and power on again.

SW6 Outdoor address setting:

  • Position 0: Master
  • Position 1: Slave 1
  • Position 2: Slave 2
  • Position 3: Slave 3

VRF trouble shooting

E9: AC voltage protection

Reason: AC supply voltage problem

Solution:

  • Use a multimeter to measure the voltage of the power supply phase to confirm the supply voltage (below 165V or higher than 265V).
  • If the power supply voltage is no problem, replace the main board.

VRF trouble shooting

XH0: Communication failure between main control chip and DSP module board

Reason: Communication failure between main control board chip and module

Solution:

  • Use a multimeter to measure the RST voltage to confirm whether the voltage is 380V, if not, check the power supply and the power supply voltage of the filter board, otherwise proceed to the next step.
  • Check whether the connection wire of the module board and the main control board is open current/short current, confirm that it is normal and connect firmly.
  • Determine the reference voltage between the middle port and the GND or 5V on both sides. If there are fluctuations on both ends of the multimeter's DC gear, or there is no fluctuation at both ends, then the motherboard is faulty; if one end has fluctuations and the other end has no fluctuations, the module board is faulty.

Diagram Description: Includes connections for IPM A, IPM COMM. A, IPM COMM. B, sensor connections (Condensing temp., Environment temp., High press sensor), and various connectors (CN47, CN42, CN45, CN16).

VRF trouble shooting

H1: Communication error between master chip and slave chip

Reason: The internal chip communication problem of the main control board

Solution:

  • Replace the outdoor unit main board.

VRF trouble shooting

H2: Outdoor units decrease

Reason: Slave unit communication lost on parallel system

Solution:

  • Check if any slave unit is powered off, and confirm that all outdoor unit are powered on.
  • Check whether the slave dialing code is wrong, refer to the introduction of SW6 dialing code, correct the dialing code and power on again.
  • Check whether the connection wire from the main board to the communication terminal is normal and whether it is firmly connected.
  • Check whether the slave communication line H1H2E is connected correctly, hand in hand connection, star connection is prohibited, use a multimeter to measure whether the communication line is open current/short current.
  • If there is no problem with the above steps, replace the communication board or main control board.

SW6 Outdoor address setting: (See E8 description for details)

Diagram Description: Includes wiring details for various connectors (CN39, CN2, CN6, CN19, CN3, CN6-1, CN23, CN3-1, CN6-2, CN3-2, CN23-1, CN23-2) and labels like FAN POWER, +12V, MODBUS.

VRF trouble shooting

H3: Outdoor units increase

Reason: Master unit read slave unit quantity increase

Solution:

  • Check whether the number of master unit and slave unit is correct, and whether other system slave unit communication is incorrectly connected to this system.
  • Confirm that the actual number of outdoor unit in the system is correct, then power on again.

VRF trouble shooting

XH4: There are 3 times P6 protection in 60 minutes

Solution: Refer to P6

H5: There are 3 times P2 protection in 60 minutes

Solution: Refer to P2

H6: There are 3 times P4 protection in 100 minutes

Solution: Refer to P4

H7: Indoor unit quantities decreasing malfunction over 3 minutes

Reason: Part of the indoor unit communication is lost

Solution:

  • Refer to the indoor unit error code FE&E1.

VRF trouble shooting

H8: Pressure sensor error

Reason: The main control board detects exhaust pressure <0.3MPa

Solution:

  • Check whether the pressure sensor is firmly connected, and confirm that the connection is secure.
  • There is no problem with the above steps, replace the pressure sensor/main control board.

Diagram Description: Shows connections for sensors (Condensing temp., Environment temp., High press sensor) and connectors (CN42, CN45, CN16) related to T3, T4, HP S, IPM COMM. B.

VRF trouble shooting

XH9: There are 3 times P9 protection in 30 minutes

Solution: Refer to P9

P0: Reserved

VRF trouble shooting

P1: High pressure protection

Reason: The open circuit state is detected at the high pressure switch detection port

Solution:

  • Check whether the wiring of the high pressure switch is firm and confirm that the wiring is normal.
  • Check whether the condenser has poor heat dissipation and ensure that there is no problem with heat dissipation.
  • Check parameter item 23/24 exhaust temperature to see if it is less than 120°C; if yes, short-circuit the exhaust thermostat, if the fault disappears, replace the exhaust thermostat; if the exhaust is ≥120°C, refer to P4 fault; otherwise Go to the next step.
  • Connect the pressure gauge, run the unit, check the high and low pressure. If the pressure is normal, remove the pressure switch to measure the resistance. If it is infinite, replace the pressure switch; if the pressure switch resistance is 0, replace the main board.
  • Connecting the pressure gauge to test, if the pressure of the pressure gauge is too high, it is the system Reason, and it is necessary to troubleshoot problems such as system blockage, vacuum, and excessive refrigerant.

Diagram Description: Shows connections for pressure switches (PH, FT, PL) and connectors (CN44, CN47, CN49).

VRF trouble shooting

P2: Low pressure protection

Reason: The open circuit state is detected at the low pressure switch detection port

Solution:

  • Check whether the wiring of the low pressure switch is firm and confirm that the wiring is normal.
  • Check whether the evaporator has poor heat dissipation and ensure that there is no problem with heat dissipation.
  • Connect the pressure gauge, run the unit, check the high and low pressure. If the pressure is normal, remove the pressure switch to measure the resistance. If it is infinite, replace the pressure switch; if the pressure switch resistance is 0, replace the main board.
  • Connecting the pressure gauge to test, if the pressure of the pressure gauge is too low, it is the system Reason, and it is necessary to troubleshoot problems such as system blockage, leakage, and lack refrigerant.

Diagram Description: Shows connections for pressure switches (PH, FT, PL, LP) and connectors (CN44, CN47, CN49).

VRF trouble shooting

XP3: Inverter compressor over current protection

Reason: The main board detects that the operating current is too large

Solution:

  • Check whether the wiring of the motor and compressor is tight and confirm that the wiring is normal.
  • Check whether the current transformer is firmly connected.
  • Use the clamp meter to check the primary side AC current and the secondary side compressor DC current, and check items 32/33/34/35, compare the difference between the check value and the clamp meter. If the difference is large, it means there is a problem with the current transformer or the main control board. Try to use a normal transformer; if not resolved, replace the main control board.
  • If the difference between the clamp meter and the check value is not large, the compressor problem or the system problem.

Diagram Description: Shows connections for IPM module (TPM, A1, B1, C1, T3, CN50, COMM. A).

VRF trouble shooting

P4: Discharge temperature sensor protection

Reason: Exhaust temperature sensor reads that the temperature is too high

Solution:

  • Connect a pressure gauge to measure whether the low pressure pressure is too low (normally 0.7-0.9MPa). If the pressure is too low, add refrigerant. At the same time, check whether the SV5 spray cooling valve on the main control board has output 220V before the failure. If there is no output, replace the main board. If the output valve does not act, replace the SV5 coil.
  • Measure the resistance of the temperature sensor. If it is inaccurate, replace the sensor.
  • If the temperature sensor reading is accurate, check the exhaust temperature of item 11 and compare it. If the temperature of the main control board is unreasonable, replace the main control board.
  • If the above steps are normal, check whether the refrigerant system is normal, such as blockage of the air return pipe, poor evaporation, wear of the compressor, etc.

VRF trouble shooting

P5: Heat exchanger high temperature protection

Reason: The condenser temperature sensor reads that the temperature is too high

Solution:

  • Check whether the heat dissipation of the condenser is normal, to ensure that there is no dirty block, poor return air, etc.
  • Measure the resistance of the temperature sensor. If it is inaccurate, replace the sensor.
  • If the temperature sensor reading is accurate, check the middle and outlet temperature of the condenser for items 8 & 9 and compare it. If the temperature of the main control board is unreasonable, replace the main control board.
  • The above steps are all normal, check whether the system is normal, such as the indoor unit load is too large, the vacuum problem.

VRF trouble shooting

XP6: IPM module protection

Reason: Compressor drive module abnormal

Solution:

  • Check whether the power supply is normal, the power supply phase voltage is 220-240V, and confirm that the power supply is normal.
  • Check whether the heat dissipation of the condenser is normal, to ensure that there is no dirty blockage, poor return air, etc.
  • Measure the resistance between compressor UWV (normally within 20Ω) and UVW resistance to ground (normally infinite, MΩ level). If the compressor resistance is abnormal, replace the compressor, otherwise proceed to the next step.
  • Check whether the module heat dissipation silicone grease is applied evenly and normally. If abnormal, apply silicone grease again, otherwise proceed to the next step.
  • The above steps are normal, then run the unit and observe whether the compressor is abnormal, such as abnormal noise, excessive current, etc., otherwise replace the compressor.
  • Observe whether the system has poor heat dissipation or module overheating and overcurrent caused by mixing with difficult-to-compress gas, otherwise replace the main control board.

VRF trouble shooting

P7: Insufficient exhaust gas overheat protection

Reason: Too much refrigerant in the system, liquid back in the compressor, problems with the refrigerant system

Solution:

  • Check whether the exhaust temperature sensor is inaccurate, replace it if it is inaccurate, otherwise it is a refrigerant system problem.
  • Connect the pressure gauge to check the high and low pressures, and check items 15/23/24 to see if there is too much refrigerant. If there is too much refrigerant, release the refrigerant.
  • Check whether the indoor unit is poorly evaporated and other problems.

VRF trouble shooting

XP8: The outdoor unit capacity dial code does not match the compressor drive model protection

Reason: Dial code problem, fan module detection is abnormal

Solution:

  • Check whether the SW11 capability dialing code of the main control board is correct, correct it if it is incorrect.
  • Check whether the dialing code of the IPM module board is correct, correct it if it is incorrect.
  • After correcting the dialing code, power on again. If the problem is not resolved, replace the main control board.

DIP switch on IPM:

  • 8-18HP: DIP switch 1-4
  • 20-22HP: DIP switch 1-4
  • 24-32HP (IPM. A&B): DIP switch 1-4

SW11 setting for outdoor unit capacity:

Set Capacity Set Capacity
0 8HP A 28HP
1 10HP B 30HP
2 12HP C 32HP
3 14HP D Reserved
4 16HP E Reserved
5 18HP F Reserved
6 20HP
7 22HP
8 24HP
9 26HP

VRF trouble shooting

XP9: DC fan module protection

Reason: Fan drive module abnormal

Solution:

  • Check whether the power supply is normal, the power supply phase voltage is 220-240V, and confirm that the power supply is normal.
  • Check whether the input voltage of the rectifier bridge is 220V, if not, replace the filter board.
  • Check whether the output of the rectifier bridge is 310V, otherwise replace the rectifier bridge, if yes, proceed to the next step.
  • Check if the DC+/DC- of the fan module board is 310V, otherwise replace the filter board, if yes, proceed to the next step.
  • Check whether the FAN POWER interface of the main control board is DC12V, otherwise replace the main control board, if yes, proceed to the next step.
  • Check whether the communication line between the main control board and the fan module is firmly connected, whether it is open/short, otherwise replace the communication line and proceed to the next step normally.
  • Use a multimeter to measure the resistance between the UVW of the motor, whether it is open/short, within 20Ω; measure the resistance of UVW to ground, and it is normal infinity (MΩ level), otherwise the motor is damaged, replace the motor.
  • Measure the voltage between VCC and COM, it is normally DC5V, otherwise replace the main control board.
  • Measure PWM-COM, DC0V is off, normal DC2.5V voltage fluctuates, otherwise replace the main control board.
  • If the voltages of VCC-COM and PWM-COM are normal, replace the module board. If it still cannot be solved, replace the motor.

Diagram Description: Shows FAN Board connections (CN3, CN1, FAN POWER, DC FAN, DC FAN Feedback, VCC, PWM, FG, ON/OFF, COM). The communication port with the main board provides: Power ground COM; Fan start signal Ctrl; 0V start, 5V close; Fan speed feedback FG.

VRF trouble shooting

XPA: Module temperature sensor over-temperature protection

Reason: IPM module board temperature is too high

Solution:

  • Check whether the heat dissipation of the condenser is normal, to ensure that there is no dirty block, short circuit of the return air, etc.
  • Check whether the module heat dissipation silicone grease is applied evenly and normally. If it is abnormal, apply silicone grease again, otherwise proceed to the next step.
  • Check whether the system has poor heat dissipation or module overheating and overcurrent caused by mixing with difficult-to-compress gas, otherwise replace the IPM module board.

THANK YOU!

WE PROVIDE COMFORT AT A GREAT VALUE

Models: ORBIT, ORBIT Variable Refrigerant Flow System, ORBIT, Variable Refrigerant Flow System, Refrigerant Flow System, Flow System, System

File Info : application/pdf, 29 Pages, 4.29MB

PDF preview unavailable. Download the PDF instead.

VRF-trouble-shooting 20230817

Related Documents

Preview ComfortStar CSA-S Series Split Air Conditioner Service Manual
Comprehensive service manual for ComfortStar CSA-S series split air conditioners, covering product specifications, refrigeration diagrams, wiring diagrams, and troubleshooting.
Preview ComfortStar MINI VRF System Service Manual | CC-MAH Series
Comprehensive service manual for ComfortStar MINI VRF systems, covering model series CC-MAH002-2S1 and CC-MAH005-2SB. Includes technical specifications, selection procedures, operational data, and maintenance guidelines for advanced VRF HVAC solutions.
Preview ComfortStar CCT-S Super-Slim Four-Way Cassette Air Conditioner Owner's Manual
Owner's manual for ComfortStar CCT-S Super-Slim Four-Way Cassette air conditioner, detailing safety precautions, unit parts and functions, operation, maintenance, troubleshooting, error codes, and European disposal guidelines.
Preview AHRI Certified Product Ratings: ComfortStar CMZ Series HVAC
Official AHRI Certificate of Product Ratings for ComfortStar CMZ Series HVAC equipment, detailing cooling and heating performance metrics like SEER2, EER2, and HSPF2, with information on potential IRA tax credit eligibility.
Preview ComfortStar BAR6 & BAH6 Series Residential Air Conditioning & Heating Product Catalog
Comprehensive catalog detailing ComfortStar's BAR6 and BAH6 series residential air conditioning and heating products, including specifications, features, and match-up tables for various models. Features R454B refrigerant and up to 14.3 SEER2 efficiency.
Preview VRF Two-way Cassette Indoor Unit Instruction Manual
Comprehensive instruction manual for the VRF Two-way Cassette Indoor Unit, covering installation, operation, safety, and troubleshooting. Essential guide for installers and users.
Preview COMFORTSTAR BAR5-18-15 CHX30CD AHRI Certified Product Ratings
Official AHRI Certificate of Product Ratings for the COMFORTSTAR BAR5-18-15 outdoor unit and CHX30CD indoor unit, detailing cooling capacity, SEER2, and EER2 ratings according to AHRI 210/240 – 2023 standards.
Preview ComfortStar Air Conditioner Owner's Manual - AHU-SG2 & CPR Series
Comprehensive owner's manual for ComfortStar AHU-SG2 and CPR series air conditioners. Covers safety precautions, unit parts, operating conditions, maintenance, and troubleshooting.