LabCon Printer Operator Manual

Temperature control system | Temperature Recorders India - PPI controller


File Info : application/pdf, 1 Pages, 432.33KB

PDF preview unavailable. Download the PDF instead.

Product-065-OM-1
LabCon (Printer)
Recording + Printer Interface

Operation Manual
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

OPERATOR PAGE PARAMETERS

Parameters

Settings (Default Value)

Select Print Option>>
Time Start Command >> Time Abort Command >> Time Interval (H:M) >>

None Print (New) Re-Print (Old) Print Info Page (Default : None)
Yes No (Default : No)
0.00 to 500.00 (HH:MM)
(Default : 0.10)

Ctrl Set Value >>

Setpoint LO limit to Setpoint HI limit
(Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)
(Default : 25.0)

Ctrl Lo Deviation >>

For RTD & DC Linear : 0.2 to 99.9 For Thermocouple : 2 to 99
(Default : 2.0)

Ctrl Hi Deviation >> Change Password >>

For RTD & DC Linear : 0.2 to 99.9 For Thermocouple : 2 to 99 (Default : 2.0)
1 to 100 (Default : 0)

SUPERVISORY > SENSOR INPUT

Parameters

Settings (Default Value)

Ctrl Zero Offset >>

-50 to 50 (Resolution 0.1°C for RTD /
DC Linear & 1°C for Thermocouple) (Default : 0.0)

SUPERVISORY > RECORDING

Parameters

Settings (Default Value)

Rec. Interval (min) >>

0 to 250 Min (Default : 5 Min)

Alarm Toggle Record >>

Enable Disable (Default : Enable)

Del Print Records >>

Yes No
(Default : No)

Del Display Record >> RTC Time >>

Yes No
(Default : No)
0 to 23 for Hour 0 to 59 for Min (Default : NA)

RTC Date >>

1 to 31 (Default : NA)

RTC Month >>

1 to 12 (Default : NA)

RTC Year >>

2000 to 2099 (Default : NA)

SUPERVISORY > CONTROL

Parameters

Settings (Default Value)

Tune >>

Yes No (Default : No)

Setpoint LO Limit >>

Min Range for the Selected Input Type to Setpoint HI Limit
(Resolution 0.1°C for RTD / DC Linear & 1°C for Thermocouple)
(Default : 0.0)

Setpoint HI Limit >>

Setpoint LO Limit to Max Range for the Selected
Input Type (Resolution 0.1°C for RTD /
DC Linear & 1°C for Thermocouple) (Default : 600.0)

Compressor Setpoint >>

0 to 100 (Resolution 0.1°C for RTD /
DC Linear & 1°C for Thermocouple) (Default : 45.0)

Compressor Hyst >>

0.1 to 99.9 (Default : 2.0)

Heat Ctrl Action >> Heat Hyst >>

ON-OFF PID
(Default : PID)
0.1 to 99.9 (Default : 0.2)

Heat Only Control

Heat + Cool Control Zone : Single

Heat + Cool Control Zone : Dual

Proportional Band >> Proportional Band >> PrCozpoPrrtioopnaBl aBnadnd>>for

0.1 to 999.9

0.1 to 999.9

Cool Pre-dominant zone

(Default : 50.0)

(Default : 50.0)

0.1 to 999.9

(Default : 50.0)

Integral Time >> 0 to 3600 sec
(Default : 100 sec)
Derivative Time >> 0 to 600 sec
(Default : 16 sec)

Integral Time >> 0 to 3600 sec
(Default : 100 sec)
Derivative Time >> 0 to 600 sec
(Default : 16 sec)

CzInItnetgergarlaTlimTiemfeor>> Cool Pre-dominant zone
0 to 3600 sec (Default : 100 sec)
Cz Derivative Time >> Derivative Time for
Cool Pre-dominant zone 0 to 600 sec
(Default : 16 sec)

Cycle Time >>
0.5 to 100.0 sec (Default : 10.0 sec)

Cycle Time >>
0.5 to 100.0 sec (Default : 10.0 sec)

PrHozpoPrrtioopnaBl aBnadnd>>for Heat Pre-dominant zone
0.1 to 999.9 (Default : 50.0)

Overshoot Inhibit >>
Enable Disable

Overshoot Inhibit >>
Enable Disable

HzInIntetgergarlaTlimTiemfeor>> Heat Pre-dominant zone

(Default : Disable)

(Default : Disable)

0 to 3600 sec

(Default : 100 sec)

Cutoff Factor >>
1.0 to 2.0 sec (Default : 1.2 sec)

Cutoff Factor >>
1.0 to 2.0 sec (Default : 1.2 sec)

Hz Derivative Time >> Derivative Time for
Heat Pre-dominant zone
0 to 600 sec (Default : 16 sec)

Cycle Time >>
0.5 to 100.0 sec (Default : 10.0 sec)

Overshoot Inhibit >>
Enable Disable (Default : Disable)

FACTORY > CONTROL SENSOR INPUT

Parameters

Settings (Default Value)

Input Type >>

Refer Table 1 (Default : RTD Pt100)

Signal LO >>

Input Type Settings Default

0 to 20mA

0.00 to Signal High

0.00

4 to 20mA

4.00 to Signal High

4.00

0 to 5V

0.000 to Signal High

0.000

0 to 10V

0.00 to Signal High

0.00

1 to 5V

1.000 to Signal High

1.000

Signal HI >>
Range LO >> Range HI >>

Input Type Settings Default

0 to 20mA

Signal Low to 20.00

20.00

4 to 20mA

Signal Low to 20.00

20.00

0 to 5V

Signal Low to 5.000

5.000

0 to 10V

Signal Low to 10.00

10.00

1 to 5V

Signal Low to 5.000

5.000

-199.9 to RANGE HI (Default : 0.0)
RANGE LO to 999.9 (Default : 100.0)

Cutoff Factor >>
1.0 to 2.0 sec (Default : 1.2 sec)

FACTORY > ALARM PARAMETERS

Parameters

Settings (Default Value)

SUPERVISORY > PRINTER SETTING

Parameters

Settings (Default Value)

Line Per Page >>

25 to 100 (Default : 65)

Hysteresis >> Inhibit >>

0.1 to 99.9 (Default : 0.2)
Yes No (Default : Yes)

Top Margine >> Bottom Margine >> Header & Footer >>
Enable >>

1 to 5 (Default : 2)
1 to 5 (Default : 2)
No On First Page Every Page (Default : No)
Yes No (Default : No)

SUPERVISORY > PRINT EVENT

Parameters

Settings (Default Value)

Alarm Toggle >>
RTC Modify >> Interval Modify >> Power Up >> Door Open >> Mains Fail >> Setpoint Modify >>

Yes No
(Default : Yes)

SUPERVISORY > PASSWORD

Parameters

Settings (Default Value)

Change Password >>

1000 to 1999 (Default : 123)

FACTORY > HEAT COOL SELECT

Parameters

Settings (Default Value)

Control Strategy >>

Heat Only Cool Only Heat + Cool
(Default : Heat + Cool)

Control Strategy : Cool Only

Time Delay (sec) >>

0 to 1000 Sec (Default : 200 Sec)

Compressor Strategy >>

Control Strategy : Heat + Cool
CONT. OFF CONT. ON SP BASED PV BASED (Default : CONT. ON)

CONT. ON
Time Delay (sec) >>
0 to 1000 Sec (Default : 200 Sec)

SP BASED
Boundary Set Value >>
0 to 100 (Resolution 0.1°C for RTD / DC Linear & 1°C
for Thermocouple) (Default : 45.0)
Control Zones >> Single Dual
(Default : Single)
Time Delay (sec) >> 0 to 1000 Sec (Default : 200 Sec)

PV BASED
Time Delay (sec) >> 0 to 1000 Sec (Default : 200 Sec)

SUPERVISORY > EXIT

Parameters

Settings (Default Value)

Exit Setup Mode >>

Yes No
(Default : No)

FACTORY > SOAK TIMER PARAMETERS

Parameters

Settings (Default Value)

Enable >>

No Yes
(Default : No)

Start Band >>

0 to 999.9 (Default : 0.5)

Holdback Strategy >>

None Up
Down Both
(Default : None)

Hold Band >>

0.1 to 999.9 (Default : 0.5)

Heat Off >>

No Yes
(Default : No)

Cool Off >>

No Yes
(Default : No)

Power Recovery >>

Abort Restart Continuous (Default : Restart)

FACTORY > DOOR OPEN

Parameters

Settings (Default Value)

Enable >>

Yes No (Default : No)

Switch Logic >> Door Alrm Dly (sec) >>

Close : Door Open Open : Door Open (Default : Close : Door Open)
0 to 1000 Sec (Default : 60 Sec)

FACTORY > MAINS FAILURE

Parameters

Settings (Default Value)

Enable >>

Yes No
(Default : No)

Switch Logic >>

Close : Mains Fail
Open : Mains Fail (Default : Close : Mains Fail)

FACTORY > PASSWORD

Parameters

Settings (Default Value)

Change Password >>

2000 to 2999 (Default : 321)

FACTORY > FACTORY DEFAULT

Parameters

Settings (Default Value)

Set To Default >>

Yes No
(Default : No)

FACTORY > EXIT

Parameters

Settings (Default Value)

Exit Setup Mode >>

Yes No
(Default : No)

101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar - 401 210. Sales : 8208199048 / 8208141446 Support : 07498799226 / 08767395333 E: sales@ppiindia.net, support@ppiindia.net

What it means Type J Thermocouple Type K Thermocouple Type T Thermocouple Type R Thermocouple Type S Thermocouple Type B Thermocouple Type N Thermocouple
Reserve
3-wire, RTD Pt100 0 to 20mA DC current 4 to 20mA DC current 0 to 5.0V DC voltage 0 to 10.0V DC voltage 1 to 5.0V DC voltage

TABLE 1 Range (Min. to Max.)

Resolution

0 to +960°C

-200 to +1376°C

-200 to +385°C 0 to +1770°C 0 to +1765°C

Fixed 1°C

0 to +1825°C

0 to +1300°C

Reserved for customer specific Thermocouple type not listed above. The type shall be specified in accordance with the ordered (optional on request) Thermocouple type.

-199.9 to 600.0°C

Fixed 0.1°C

-199.9 to 999.9 units

Fixed 0.1 unit

ELECTRICAL CONNECTIONS

SOAK START ACK
BATTERY

01 234
COMMON DOOR

RS485

Control Outputs

COMM HTR CMP ALM
+DEV- +PC- + - + - + -

9 10 11 12 13 14 15 16 17 18

LabCon (w/o map) Configuration PC Printer Recording

5678 Pt100
+++mVA---
TC
Supply
18~32VDC +-
19 20 21

PV ERROR INDICATIONS

Message OPEN OVR UNR

Error Type Sensor Open Over-range Under-range

Cause Sensor (RTD Pt100) Broken / Open
Temperature above Max. Specified Range
Temperature below Min. Specified Range

FRONT PANEL KEYS

Symbol

Key

Scroll
Alarm Acknowledge

DOWN

UP

Function
Press to scroll through various Process Information Screens in Normal Operation Mode.
Press to acknowledge and mute (if active) alarm output.
Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.
Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.

SET-UP ENTER

Press to enter or exit set-up mode.
Press to store the set parameter value and to scroll to the next parameter.

Jan 2022

