SIRIUS CAPACITOR MODULE User Manual
Model number: 7100-48-B-2C-M-SD-L-G
Version: 1.0; Release Date: April 2018
Introduction
The Sirius Capacitor Module (“Sirius”) is supercapacitor-based storage that uses supercapacitors as storage cells instead of chemical cells. Kilowatt Labs' proprietary balancing, control and charge retention algorithms control the operation of the supercapacitor-based modules, making Sirius a safe, efficient and effective alternative to chemical batteries wherever chemical batteries are deployed.
Legal Provisions
No part of this User Manual (“Manual”) may be reproduced, or transmitted, in any form or by any means, without the prior written permission of Kilowatt Labs, Inc. (“Kilowatt” or the “Company”). Specifications in this Manual are subject to change without notice. While every attempt has been made to make the Manual accurate and up-to-date, users are cautioned that product improvements may cause the Company to make changes to specifications without advance notice. Users are encouraged to consult the Company or its Resellers before using the Manual. Neither the Company nor its Resellers shall be liable for any indirect, incidental, or consequential damages under any circumstances caused by reliance on the material presented, including, but not limited to, omissions, typographical errors, arithmetical errors or listing errors in the content material. The content of this manual shall not be modified without the written authorization of the Company.
Trademarks
All trademarks are recognized, even if not explicitly identified as such. Kilowatt Labs® is a registered trademark of the Company.
Safety
This Manual contains instructions for unpacking, mounting, installation and operation of a Sirius module. Please read this manual carefully before operating the system and follow all warnings and safety instructions. Please follow the instructions in this Manual carefully to prevent accidents. The Sirius module must be installed by trained personnel.
Warning: Selling and installation of this product is only through the Company's Resellers who are trained on installation, operation and maintenance of the Sirius modules.
Unpacking and Handling
Unpacking
Inspect the shipping carton for damage prior to unpacking the module. Document (photograph) all damage and report this to your reseller and to the shipping agent immediately. Remove the module from the shipping carton and retain the shipping materials until the unit has been inspected and is determined to be operational. The module must be removed by lifting the module body. Do not lift the module by the terminal posts.
[!] The module must be removed from the carton by lifting the module body. Do not remove the module by the terminal posts.
The following items are included in the package:
- Sirius Capacitor Module: 7.1kWh48VDC
- Compact Disc with the monitoring software Manual and application software.
NOTE: The original shipping materials are approved for both air and ground shipment.
Handling
The Sirius Capacitor modules are designed to provide years of trouble-free operation. Proper handling is required to avoid damage to the module. In particular, the following handling precautions should be observed:
- Do not lift the module by the terminal posts.
- Do not stack modules once they have been removed from the shipping containers.
- Do not drop the module. Internal damage may occur that will not be visible from the exterior.
- Do not step on the module.
- Protect the module from impact.
Installation
Installation must strictly follow the national safety regulations in compliance with the enclosure, installation, creep age, clearance, casualty, markings, and segregation requirements of the end-use application. Installation must be performed by professional installers only. Switch off the system and check for hazardous voltages before altering any connection! Sirius modules must be handled only by qualified and trained personnel. Installation should not exert bending or twisting torque to the module enclosure.
Parallel Connection of Sirius Modules
A schematic shows four Sirius Capacitor Modules connected in parallel. The positive terminals of all modules are joined together, and the negative terminals are joined together, creating a common positive and common negative output. Any number of modules can be connected in parallel.
Product Overview
The Sirius Capacitor Module is presented as a robust, rectangular unit with a metallic casing. The front panel features a prominent power switch, an LCD display showing operational data, several communication LEDs, and clearly marked positive and negative terminal posts.
Panel Description
The front panel of the Sirius Capacitor Module is detailed with numbered components:
| 1 | Positive Terminal |
| 2 | Negative Terminal |
| 3 | LCD Display |
| 4 | COMM LEDs |
| 5 | COMM Connector |
| 6 | Power Switch |
LCD Description
Once the power is switched ON from the Power Switch, the module gets power and the LCD shows the following message:
Voltage Current
V=51.55 I=-18.45
T=24.02 E=0.45
Temperature Energy Delivered
LCD Messages
This section describes the messages that appear on the LCD.
Overcurrent (OCD)
When the module has an overcurrent fault (OCD), the LCD shows the following warning message:
!WARNING
!OCD I >296A
This means the current has increased beyond the cut off current of 296A. The LCD shows that the module current has increased above 296A.
Overvoltage (OV)
When the module has an overvoltage fault (OV), the LCD shows the following warning message:
!WARNING
!OV V=56.1
This means the module voltage has increased beyond the cut off limit of 54.5V. The LCD shows the voltage at that time as well, for example, the module voltage has increased to 56.1V.
Undervoltage (UV)
When the module has an undervoltage fault (UV), the LCD shows the following warning message:
! WARNING
!UV U=43.9
This means the module voltage has decreased below the cut off value of 44V. The LCD shows the voltage at that time as well, for example, the module voltage has decreased to 43.9V.
Overtemperature (OT)
When the module has an overtemperature fault (OT), the LCD shows the following warning message:
!WARNING
!OT T=75.1
This means that the temperature of the module has increased beyond the cut off value of 75°C. The LCD shows the temperature at that time as well, for example, the module temperature has increased to 75.1°C.
COMM LEDs
COMM LEDs are the LEDs which show the status of communication of the control module with the application software. There are 4 LEDs for the four control modules in the Sirius Capacitor Module.
Each LED has the following status:
- OFF: The control module is not powered and hence not communicating with the application software.
- ON (Green): The control module is powered ON but no communication with the application software.
- Blinking Red: The control module is communicating with the application software.
COMM Connector
This is an RJ45 connector to monitor the module using the application software.
Power Switch
When the power is switched ON using the ON/OFF switch on the front panel, the module electronics are powered up. The module is now functional and can be operated.
Safety Features
This Sirius Capacitor Module has the following safety features:
Anti-theft
The module is password protected and can only be operated by authorized personnel with a valid password at the time of connecting the module. The password is loaded to the module via a PC. If the module is disconnected from the DC power source, the anti-theft feature requires the password to be loaded to restart the module. In the event of disconnection from the DC power source, to restart the module, connect a PC to the module and enter the password.
If the module disconnects due to a safety event (described below), it automatically reconnects once the safety event is over.
Shut-down due to Safety Events:
- Over-voltage cut off: This feature will be activated when the module voltage goes beyond the high voltage threshold of 54.5V.
- Under-voltage cut off: This feature will be activated when the module voltage goes below the low voltage threshold of 44V.
- Over-current cut off: This feature will be activated when the module current exceeds the maximum load capacity of 296A.
- Over temperature cut off: This feature will be activated when the module temperature exceeds the maximum temperature limit of 75°C.
Reconnect Feature
These features work as follows:
| Disconnect Event | Disconnect Value | Reconnect Feature |
|---|---|---|
| Over voltage | 54.5V | Module senses system voltage and reconnects automatically when system voltage is ≤53.0V |
| Under voltage | 44.0V | Module senses system voltage and reconnects automatically when system voltage is ≥46.0V |
| Over Current | 296A | Module senses system voltage and reconnects if V-system <> +-1V from Vbat@ rest |
| Disconnected from DC power source | Poles removed | Enter password through PC to reconnect |
Operation Procedures
The module should only be operated within the specified voltage and temperature ratings. Observe polarity indicated on module. [!] Do not reverse polarity.
Follow the steps below while operating the module:
- Connect the cables to the module terminals and ensure that the bolt enters 40mm into the terminals. The LCD will give an error message if the terminals and bolts are not connected as specified here.
- Configure the PC IP in the network and internet settings of the monitoring device.
- Connect the RJ45 cables to the COMM connector slot to start communication and monitoring.
- Now turn on the power switch which lights up the LCD.
- Open the monitoring software application in the monitoring device from the CD provided.
- The module has the anti-theft feature. So an authorized password should be entered to start operating the module.
NOTE: Please refer to the monitoring software manual in the CD provided with the module for the details.
- Now the module stays functional even when the RJ45 connector is removed (monitoring OFF).
NOTE: Authorization is required again when the module is either powered OFF or the cables are removed.
- The module can be shutdown either by the ON/OFF switch or by removing the output cables from the module terminals.
NOTE: Switch OFF the module when not in use as the module is self-powered or else, it can result in the self-discharge of the super-capacitors.
Trouble shooting: Faults and Solutions
This section explains how to correct faults:
Over-voltage (OV)
The OV cut-off is at 54.5V. Set the charger's limit below 54.5V to prevent an OV event. If the voltage exceeds 54.5V, the module shuts down and locks. The module unlocks when the module's surface charge is cleared, and the voltage drops below 54V. The event can be repeated if the charger is still ON and operating in the same condition.
Troubleshooting: Check the charger's upper cut off limit and ensure it is set below 54.5V.
Under-voltage (UV)
The UV cut-off is 44V. If the voltage goes below 44V, the module shuts down and locks. The module unlocks when the voltage goes above 44V. The event can be repeated if the load is still ON and operating in the same condition.
Troubleshooting: Check for the operating load lower cut off limit and ensure it is above the lower threshold limit of 44V.
Over-Current (OC)
OC occurs when the current goes above 296A or when the module is short-circuited. In this event the module shuts down and locks.
Troubleshooting: Switch off the module and check the voltage across the module terminals to find whether it is a short circuit. In case of short circuit, check the operating circuitry and clear the short circuit. The module can be unlocked in 30 seconds after the current goes below 296A.
Over-Temperature (OT)
OT occurs when the module temperature goes above 75°C. In this event, the module shuts down and locks.
Troubleshooting: Shut down the module and check the room temperature and ensure the cooling units are operating properly. Leave the module to cool till the module temperature comes below 75°C. Now, turn ON the module.
Multiple Errors
The above-mentioned errors can occur simultaneously and will be shown on the LCD. To clear these, follow the steps explained in the above sections.
Maintenance
The Sirius Capacitor Module does not require periodic maintenance.
Safety Instructions
Strictly observe the safety instructions listed below to ensure safe handling, injury prevention and trouble-free operation of the module.
- Never touch the positive (+) or negative (-) terminals as the module can be charged and cause fatal electrical shocks. Always verify that the module is fully discharged before handling the module.
- Ensure precautions to prevent short-circuit under all circumstances.
- Do not operate the module above the specified voltage.
- Do not operate the module above the specified temperature rating.
- Do not touch the terminals with conductors while the module is charged. Serious burns, shock, or material fusing may occur.
- Wear protective equipment when handling the modules including gloves, eyewear and hardhat.
- Protect surrounding electrical components from incidental contact.
- Do not use the module in an open environment, in rain or in a place exposed to water and other liquids.
- In case the module is physically damaged due to any event, do not install and energize the module under any circumstances and contact your Reseller.
- When connecting to external devices ensure that galvanic isolation does not exceed 1500V.
- Under no circumstances must the charge / discharge current exceed 296A.
- Under no circumstances must the charging voltage exceed 54VDC for more than 60 seconds.
- During charge cycle ensure never to exceed constant voltage of 54VDC and constant current of 296A.
- All modules must be at 100% SOC before connecting in series or parallel.
- The maximum number of modules that can be connected in series is 8 with a Module Combiner. Under no circumstances should you connect more than 3 modules in series.
- If you want to connect more than 8 modules in series, please contact your Reseller.
- Modules cannot be connected in a series – parallel combination under any circumstances.
Storage
The Sirius modules can be stored at any SOC (State of Charge) without affecting the projected cell cycle life of 1,000,000 cycles.
Projected Calendar Life (the projected life of the module (in years) from the date it is first operated) is 45 years for the supercapacitor cells.
Shelf Life (the life of the module (in years) from the date it is manufactured to the time it is first operated) is 10 years.
Disposal
Do not dispose of the module in trash. Dispose of according to local regulations.
Technical Specifications
| Nominal Voltage | 48VDC |
|---|---|
| Voltage Range | 44VDC - 54VDC |
| Capacity | 7100Wh |
| Maximum Charge Rate (0% -100% SOC) | 296A |
| Maximum Discharge Rate (100% - 0% SOC) | 296A |
| Maximum Charging Voltage | 54VDC |
| Internal Resistance | ≤3mΩ |
| Supercap cell DC to DC Roundtrip efficiency (@296A) | 99.1% |
| Supercap cell Operating Temperature | -30°C to 85°C |
| Galvanic Isolation | 1500V |
| Projected Cycle Life1,2 | 1,000,000 |
| Projected Calendar Life2,3 | 45 years |
| Shelf Life4 | 10 years |
| Warehousing | Can be stored at any SOC without affecting cycle life |
| Communication Port | TCP/IP RJ45 Ethernet |
| Monitoring Data | Temperature, Voltage, Current, Energy, Supercap Balancing |
| Remote Control Input | Battery Self-Check |
| Safety | Shutdown on Over-Charge, Over-Discharge, Over-Current, Over-Temperature, Reverse Polarity, Cell Imbalance |
| Terminal Type | F12 |
| Module Casing Material | Aluminium |
| Dimensions (w x d x h) | 600mm x 490mm x 330mm |
| Weight | Approx.127kg |
| Self-discharge5 | 5% after 25 days |
| CE Certification6 | EN55032:2015, EN55024:2010, EN61000-4-2:2009, EN61000-4-3:2006+A1:2008+A2:2010 |
Precautions
- In case the module is physically damaged due to any event, do not install and energize the module under any circumstances and contact an authorized technician.
- Ensure precautions to prevent short-circuit under all circumstances.
- When connecting to external devices ensure that galvanic isolation does not exceed 1500V.
- Under no circumstances must the charge / discharge current exceed 296A.
- Under no circumstances must the charging voltage exceed 54VDC for more than 60 seconds.
- During charge cycle ensure never to exceed constant voltage of 54VDC and constant current of 296A.
- To connect modules in series, ensure all modules are at 100% SOC before connecting. Do not connect otherwise.
- Maximum number of modules that can be connected in series7: 8 with Module Combiner.
Series - Parallel Connection
Please consult with Kilowatt Labs or its Reseller when connecting the modules in series. Under no circumstances should more than 3 modules be connected in series without the Module Combiner.
Maximum number of modules that can be connected in parallel: No limit.
Modules cannot be connected in a series – parallel combination under any circumstances.
SiriusVIEW – Monitoring Software
Individual Cell
Monitoring of voltage.
Module
Monitoring of current, max. & min. voltage, temperature, DOD, SOC, rate of charge, rate of discharge, time to discharge, balance energy, total energy delivered over lifetime, graphs.
System
Monitoring of all modules connected together.
Notes
1 Projected Cycle life of supercap cells.
2 Additional terms and conditions, including a limited warranty, will apply at the time of purchase.
3 Projected Calendar life of supercap cells from the date of first operation.
4 Shelf life is the life of the module (in years) from the date it is manufactured to the time it is first operated.
5 Self-discharge: (1) 30% after 30 days; (2) 80% after 60 days; Self-discharge only when not charging or discharging; No memory effect; Module can be recharged to 100% at any time.
6 CE certification is completed for supercap cells.
7 Consult Kilowatt labs Reseller for information on connecting modules in series.
Product dimensions are for reference only unless otherwise identified and may change without notice. For critical applications, please contact Kilowatt Labs, Inc., or its Reseller.