Daikin MicroTech III – Mark IV WSHP Unit Controller Interface Installation and Operation Manual

Installation and Operation Manual

Document ID: IOM 1147

Group: Controls

Part Number: 910151284

Date: March 2013

Supersedes: New

MicroTech® III – Mark IV WSHP Unit Controller Interface

For Use with Integrating MicroTech III Unit Controllers into a Mark IV WSHP Network

© 2013 Daikin Applied

Introduction

Daikin is committed to providing solutions that support previous vintages of Water Source Heat Pump (WSHP) systems. Over time, it may become necessary to replace an existing WSHP(s) or add new WSHPs into a building with older heat pumps. This document contains the information needed to install and configure a MicroTech III (MTIII) WSHP into a Mark IV WSHP network. A MTIII-Mark IV Interface Board has been developed to produce compatible signals for the MTIII for the Pump Request, Occupancy, and Emergency Shutdown lines of the Mark IV network.

Description

The MTIII–Mark IV Interface Board is a printed circuit board with two terminal blocks, labeled T1 and T2. T1 has four terminal pin connectors that interface to the Mark IV network. T2 has five terminal pin connectors that interface directly to the MTIII unit controller. See Figure 1 for locations of the terminal blocks and Table 1 for a description of terminal pin functions.

Figure 1: MTIII–Mark IV Interface Board Features
Figure 1 shows the Daikin MicroTech III – Mark IV Interface Board, highlighting the locations of Terminal Block T1 (labeled ECUP) and Terminal Block T2 (labeled CPUER).

Terminal Pin Descriptions

Terminal Block (T1)Pin DescriptionTerminal Block (T2)Pin Description
EEmergency ShutdownR24Vac from MTIII WSHP
UUn-occupancyEEmergency Shutdown
CCommonUUn-occupancy
PPump requestPPump request
CCommon

Table 1. MTIII–Mark IV Interface Board Terminal Pin Descriptions

Application

The MTIII-Mark IV Interface Board is used to incorporate a MTIII WSHP unit controller into an existing Mark IV WSHP network. This board is required in the following application scenarios:

  1. When adding a new heat pump (with corresponding MTIII unit controller) into an existing network of Mark IV heat pumps.
  2. When replacing a Mark IV heat pump (the entire unit, not just the controller) with a MTIII heat pump unit.

The MTIII-Mark IV Interface Board provides the following:

  • Provides a means of electrical isolation for the "E" and/or "U" control signals between a Mark IV and MTIII WSHP daisy-chained network.
  • Converts the pump request signal from the MTIII WSHP unit controller to be compatible with the respective pump request signal from the existing Mark IV WSHP unit controller.

Component Data

MTIII WSHP Unit Controller

The MTIII WSHP Unit Controller is a microprocessor-based controller designed to operate Enfinity™, SmartSource™, and Vertical Stack models of Water Source Heat Pump units. It is capable of network communication to a Building Automation System (BAS) via optional BACnet® or LonWorks® interface boards.

Mark IV WSHP Unit Controller

The Mark IV WSHP Unit Controller is a microprocessor-based controller designed to operate a Water Source Heat Pump unit as well as provide outputs for unit status and fault detection. It can be used as a 1) a stand-alone controller, 2) daisy-chained in series to a Loop Water Controller for system control of the water loop or 3) used in conjunction with the Multiple Unit Control Panel (MUCP), which is an accessory that enables up to three WSHP units to be controlled from a single thermostat.

Loop Water Controller

The Loop Water Controller (LWC) is a microprocessor-based controller providing control of the heat rejection/heat addition stages and the water circulating pumps for control of a water source heat pump system through solid-state output relays. The LWC is designed to be used with the Mark IV unit controllers for standalone operation of the water loop. The LWC does not support serial communications to a BAS. The Mark IV network has a pump request signal that can be used to request flow from the LWC. If the Mark IV network has incorporated the use of the Pump Request signal, it is implied that it includes a Pump Restart Relay board or similar mechanism to start the pump for the water loop.

Installation

The following section describes how to install MTIII-Mark IV Interface Board in a Mark IV WSHP network.

Installing the MTIII – Mark IV Interface Board

⚠️ DANGER: Hazardous voltage. Can cause severe injury or death. Disconnect electric power before servicing equipment. More than one disconnect may be required to de-energize the unit.

Each MTIII WSHP board needs a MTIII-Mark IV Interface Board for its operation in an existing Mark IV network. Follow the steps below to properly install this interface board:

  1. Disconnect power from the unit.
  2. Unscrew terminal T1 and T2 terminal blocks of MTIII-Mark IV Interface Board.
  3. Connect the C and R Pins of terminal block TB2 on MTIII WSHP board to pin C and R of T2 on MTIII-Mark IV Interface Board respectively.
  4. Connect pin E and U of terminal block TB3 on MTIII WSHP board with E and U of terminal block T2 on MTIII-Mark IV Interface Board respectively.
  5. Connect pin P and C on Terminal block T1 of MTIII-Mark IV Interface Board to pin 1 and 3 of header H8 on MTIII board respectively.
  6. Connect pin E and U on Terminal block T1 of MTIII-Mark IV Interface Board to pin E and U of Mark IV respectively.
  7. See Figure 2 below for interfacing a MTII WSHP to a Mark IV network using MTIII-Mark IV interface board.

Figure 2: MTIII-Mark IV Interface Board Wiring Diagram
Figure 2 illustrates the wiring diagram for interfacing a MTIII WSHP to a Mark IV network using the MTIII-Mark IV Interface Board. It shows connections between Mark IV units, the interface board, and MTIII units, detailing pin assignments for P, C, E, U, R.

Replacing a MTIII – Mark IV Interface Board

⚠️ DANGER: Hazardous voltage. Can cause severe injury or death. Disconnect electric power before servicing equipment. More than one disconnect may be required to de-energize the unit.

To replace a MTIII – Mark IV Interface Board, follow the steps below:

  1. Remove power from the unit controller.
  2. Unscrew and disconnect all the wiring from terminal connector T1 and T2.
  3. Remove the old board and replace with the new one.
  4. Replace with the new unit and screw the wires back (see fig).
  5. Apply power to the unit controller.

Operation

Pump Request from MTIII WSHP board

  • When a MTIII WSHP board has a call for Pump Request or compressor operation (Cooling or Heating), the control closes the PRVI Relay.
  • MTIII WSHP board applies a 24VAC on H8 pin 1 on the control board.
  • The H8 pin 1 of the MTIII WSHP board is connected to T2 pin P of the MTIII-Mark IV Interface Board. For Pump Request only wiring, see installation wiring diagram Fig 3.
  • The MTIII WSHP board applies 24VAC to pin P of MTIII-Mark IV Interface Board.
  • The MTII-Mark IV Interface converts the 24VAC from MTIII to a voltage level compatible to a Mark IV pump output.

Pump Request from Mark IV WSHP board

  • The pump output of the Mark IV board is connected to T1 terminal P of the MTIII-Mark IV Interface Board and terminal 2 of the Pump Restart Relay board. The Pump Restart Relay board is connected to the loop water controller terminals 58 and 64.
  • When a call for pump is received from the MTIII-Mark IV WSHP board, it will restart the loop circulation pump.

Figure 3: MTIII–Mark IV Interface Board Pump Request Wiring
Figure 3 depicts the wiring for Pump Request signals between MTIII WSHP units, the Mark IV network, and the MTIII-Mark IV Interface Board. It shows connections for pump request signals (P) and common (C) between the boards and the Pump Restart Relay.

Emergency Shutdown and Occupancy from Mark IV WSHP board

When MTIII WSHP units are installed in a Mark IV network, the Occupancy (U) and Emergency Shutdown (E) inputs used by the Mark IV boards are connected to the MTIII-Mark IV Interface Board T1 side of terminal U and E respectively. For emergency shutdown and occupancy in a network that involves both MTIII and Mark IV boards, the sensor connection that triggers the emergency shutdown or occupancy shall be made on Mark IV (T1) side NOT on MTIII (T2) side of the MTIII-Mark IV Interface Board. For a Mark IV board, the Occupancy and Emergency Shutdown inputs are 24VAC or 24VDC. On MTIII-Mark IV Interface Board T2 side of terminal U and E are connected to TB3 terminal U and E of MTIII respectively.

The MTIII-Mark IV Interface Board converts the 24VAC or 24VDC input signals from the Mark IV boards to common signal compatible to a MTIII WSHP board ground signal.

See Figure 4 below for Emergency shutdown and Occupancy wiring.

Figure 4: MTIII–Mark IV Interface Board Emergency Shutdown and Occupancy Wiring
Figure 4 presents the wiring for Emergency Shutdown (E) and Occupancy (U) signals between MTIII WSHP units, the Mark IV network, and the MTIII-Mark IV Interface Board. It details how these signals are routed and converted.

Service Information

Troubleshooting Guide

For further technical assistance, contact the Daikin Controls Network Integration Support group at daikincontrols@DaikinApplied.com (email) or phone 866-462-7829.

Parts List

DescriptionPart Number
MicroTech III – Mark IV Interface Board250693001

This document contains the most current product information as of this printing. For the most current product information, please go to www.DaikinApplied.com.

All Daikin equipment is sold pursuant to Daikin's Standard Terms and Conditions of Sale and Limited Warranty. Consult your local Daikin Representative for warranty details. Refer to Form 933-43285Y.

PDF preview unavailable. Download the PDF instead.

IOM 1147-March2013 Dawn Zeleke Adobe PDF Library 10.0

Related Documents

Preview Daikin MicroTech III SmartSource Unit Controller Installation and Maintenance Manual
Comprehensive installation and maintenance manual for the Daikin MicroTech III SmartSource Unit Controller, covering models GC, GS, GT, and VH. Details features, operation, and troubleshooting for water source heat pumps.
Preview Daikin Digitally Adjustable Display Sensor Installation and Maintenance Manual
Comprehensive guide for the installation and maintenance of the Daikin Digitally Adjustable Display Sensor (IM 1237-3). Covers mounting, wiring, operation, and troubleshooting for Water Source Heat Pumps.
Preview Daikin MicroTech III Network Integration Guide for BACnet and LONWORKS
Comprehensive guide detailing network integration protocols (BACnet and LONWORKS) for Daikin's MicroTech III Unit Controllers, covering commercial packaged rooftop, applied rooftop, and self-contained systems. Includes data points, parameters, and configuration details for models DPS, MPS, RAH, RDE, RDS, RDT, RFS, RPE, RPS, SWP, and SWT.
Preview Daikin SmartSource Compact Vertical Water Source Heat Pump Installation and Maintenance Manual
This manual provides comprehensive installation and maintenance guidance for Daikin's SmartSource® Compact Vertical Water Source Heat Pump (WSHP) units, Model GCV series (Sizes 007-070). It covers system applications, electrical and piping, controls, maintenance, and troubleshooting.
Preview Daikin SmartSource GCV Series: Installation and Maintenance Manual IM 1251-4
Comprehensive installation and maintenance manual for Daikin SmartSource Compact Vertical Water Source Heat Pump (GCV Series) models 007-070. Covers system applications, electrical/piping, controls, troubleshooting, and technical specifications.
Preview Daikin MicroTech Unit Controller Remote User Interface Installation and Operation Manual (IM 1005-7)
Comprehensive installation and operation guide for the Daikin MicroTech Unit Controller Remote User Interface (Model IM 1005-7). Covers features, installation, wiring, operation, troubleshooting, and firmware updates for Daikin HVAC systems.
Preview Daikin Applied MicroTech II to MicroTech III Controller Conversion: Installation and Maintenance Guide (IM 1330-2)
Comprehensive guide for Daikin Applied Self-Contained Unit Controllers, detailing the conversion process from MicroTech II to MicroTech III. Covers installation, wiring, and configuration for HVAC systems.
Preview Daikin MicroTech II OM 748-4 Operation and Maintenance Manual
Operation and Maintenance Manual for Daikin's MicroTech II control system used with Unit Ventilators, including Air Source Heat Pumps with Electric Heat (Software Model UV00) and Classroom Unit Ventilator Model AEQ. Covers system components, configurations, and service procedures.