SES320 Series Surge Protective Device

Warnings

  • Safety First - Hazardous Voltage & Shock Hazard
  • Only qualified licensed electricians should install or service SPDs
  • Hazardous voltages exist within SPDs
  • SPDs should never be installed or serviced when energized
  • Use appropriate safety precautions including Personal Protection Equipment
  • Failure to follow these instructions can result in death, serious injury, and/or equipment damage
  • This manual shall be read in its entirety prior to installing

Bonding and Grounding Hazard

Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National Electric Code (NEC®) and all applicable codes. During installation into an electrical system, the panel must not be energized, or the Circuit Breaker de-energized, until the SPD is completely installed, inspected, and tested. All conductors must be connected and functional, including the neutral (if required).

The voltage rating of the SPD and system must be verified before energizing the SPD. Failure to follow these guidelines can lead to abnormally high voltages at the SPD, which may cause the SPD to fail. The warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with the NEC®.

Do Not Hi-Pot Test SPDs

Any factory or on-site testing of power distribution equipment that exceeds normal operating voltage, such as high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage than their rated Maximum Continuous Operating Voltage (MCOV), must be conducted with the SPD disconnected from the power source. For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing high-potential testing. Failure to disconnect the SPD and associated components during elevated voltage testing will damage the SPD and void the warranty.

SPDs on Ungrounded Systems

Caution – Ungrounded systems are inherently unstable and can produce excessively high line-to-ground voltages during certain fault conditions. During these fault conditions, any electrical equipment, including an SPD, may be subjected to voltages that exceed their designed ratings. An SPD designed specifically for Ungrounded systems should be used.

Unpacking & Preliminary Inspection

Inspect the entire shipping container for damage or signs of mishandling. Remove the packing materials and further inspect the unit for any obvious shipping damages. If any damage was found and is a result of shipping or handling, immediately file a claim with the shipping company and forward a copy to nVent.

Storage Environment

This SPD should be stored in a clean, dry environment. Storage temperature range is -40°C (-40°F) to +60°C (+140°F). Avoid exposure to high condensation.

Pre-Installation & Installation Planning

Operating Environment

The standard unit uses a NEMA 4X enclosure. Flush-mount kits are available as an option. Before installing, ensure that your enclosure type and application are appropriate with regard to moisture, dirt, excessive dust, flammable materials or atmospheres, corrosive vapors, etc. This SPD is designed for an ambient temperature range of -25°C (-13°F) to +85°C (+185°F) with a relative humidity of 0% to 95% (noncondensing). Excessive temperature may inadvertently operate internal thermal over temperature protectors.

Line Side versus Load Side Installation

  • SES320 B Series is tested and Listed as a Type 1 SPD per UL 1449 5th Ed. This SPD can be installed on the Line Side of the service overcurrent device. Type 1 SPDs may also be installed in UL Type 2 Applications. In general, it is more practical to install as Type 2 on the load side of the main overcurrent device for maintenance reasons.
  • SES320 F Series is tested and Listed as a Type 2 SPD per UL 1449 5th Ed. This SPD can only be installed on the Load Side of the service overcurrent device.

Audible Noise

SPD background noise is negligible or non-existent, and does not restrict the location of installation.

Lead Lengths & Maximizing SPD Performance

SPDs must be located as close to the circuit as possible to minimize let-through voltage. Use the shortest & straightest possible leads. Pre-Plan installations and ensure that nearest breaker positions are used. If new construction, adjust breaker locations as appropriate. When longer leads are unavoidable, gently twist leads together (one to two twists per foot), or tie-wrap leads together.

Installation

Pre-Plan your installation

  • Meet all National and Local codes. (NEC® Article 285 addresses SPDs)
  • Mount SPD as close to panel or equipment as possible to keep leads short
  • Ensure leads are as short and straight as possible, including neutral and ground.
  • Consider a breaker position that is closest to the SPD and the panel's neutral & ground
  • Suggested breaker size is 30A.
  • Make sure system is grounded per NEC® and clear of faults before energizing SPD.

Wiring Connections

Connect to Mains:
Orange: Line(s) / Line* (High Leg Delta ONLY)
White: Neutral
Green: Ground

Connect to Alarming:
Black: NO (Normally Open)
Brown: NC (Normally Closed)
Yellow/White: Common

Installation Steps

  1. Use a voltmeter to check all voltages to ensure correct SPD.
  2. If utilizing Dry Contacts, pre-plan their installation.
  3. Remove power for panel. Confirm panel is deenergized.
  4. Identify connection/breaker location and SPD location.
  5. Make sure leads are short.
  6. Remove an appropriately sized knockout from panel.
  7. Mount SPD. Connect to equipment using an approved wiring method, including seals appropriate for the enclosure rating.
  8. Connect conductors as appropriate - short and straight as possible.
  9. Label or mark conductors as appropriate: Energized: black and orange*; Neutral: white; Ground: green
  10. Make sure system is bonded per NEC® and is clear of hazards or faults before energizing (N-G bonding not per NEC® will fail SPDs (only at Service Entrance).
  11. Energize and confirm proper operation of indicators and/or options. If Audible Alarm cycles, de-energize immediately and contact nVent for help.

System Wiring Diagrams

The wiring diagram illustrates connections for various system types. For single-phase systems, connect the Line wire (typically orange) to the SPD, the Neutral wire (typically white) to the SPD, and the Ground wire (typically green) to the SPD. For split-phase systems, connect Phase A (typically orange) and Phase B (typically black) to the SPD, along with Neutral (white) and Ground (green). For three-phase Wye systems, connect Phase A, Phase B, and Phase C (all typically black) to the SPD, along with Neutral (white) and Ground (green). For three-phase High Leg Delta systems, connect Phase A (black), the High Leg (orange), and Phase C (black) to the SPD, along with Neutral (white) and Ground (green). For three-phase Delta & HRG systems, connect Phase A, Phase B, and Phase C (all typically black) to the SPD, along with Neutral (white) and Ground (green). Alarm connections include Normally Open (NO) via a black wire, Normally Closed (NC) via a brown wire, and Common via a yellow/white wire.

Operation

LED Operation

Each SPD contains 2 green LEDs per line shown in the appropriate voltage configuration. When the LEDs are green, complete protection is present. Upon MOV failure, the LED corresponding to the failed mode will extinguish.

Audible Alarm

Similar to the LEDs, the Audible Alarm will sound upon suppression element failure. The Audible Alarm may be silenced by removing power to the SPD.

Dry Contact

Three 18", 22 AWG wires are included through the nipple as the Form C Dry Contacts. The Contacts change state during inoperative conditions, including loss of power. Any status change can be monitored elsewhere via the Relay Contacts.

  • Please note: Dry Contacts are designed for low voltage or control signals only
  • Maximum switching current is 2A
  • Maximum switching voltage is 240Vac
  • Higher energy applications require additional relay implementation outside the SPD
  • Yellow/White is Common, Black is Normally Open and Brown is Normally Closed. If the Dry Contacts are not utilized, insulate lead ends, coil and secure.

Maintenance

SPDs require minimal maintenance. We recommend periodic inspection of diagnostic indicators to ensure proper operation. We also recommend keeping the SPD clean as appropriate.

Troubleshooting & Service

Please contact nVent for any service related issues.

Diagnostics Table for the SES320 Series

L1 LEDL2 LEDL3 LEDAlarm LEDAudibleAction
GreenGreenGreenOffOffThe SPD is Operational
OffOffOffOffOffNo Power to the Unit; Check Circuit Breaker
1 or 2 LEDs OffFlashing RedOnCheck Line Voltages; Replace Unit
GreenGreenGreenFlashing RedOn(*) Check N & G Connections, Voltage N-G (GRM Fault)

(*): SES320F ONLY

Models: SES320 Series Surge Protective Device, SES320 Series, Surge Protective Device, Protective Device, Device

File Info : application/pdf, 5 Pages, 687.44KB

IP9018

References

SOLIDWORKS PDF Publisher

Related Documents

Preview nVent TDX100M & TDX200M Series Surge Protection Device Installation Instructions
Comprehensive installation guide for nVent TDX100M and TDX200M Series Surge Protection Devices (SPDs). Covers essential safety warnings, step-by-step installation procedures, activation, alarm conditions, and fuse replacement for optimal electrical protection.
Preview nVent Battery Energy Storage Solutions: Resilient, Safe, and Efficient Electrical Systems
Explore nVent's comprehensive Battery Energy Storage Solutions (BESS), offering robust enclosures, advanced cooling, reliable electrical distribution, and grounding for mission-critical applications. Enhance safety, efficiency, and reduce total cost of ownership.
Preview nVent CADWELD Flint Ignitor T320 - Product Overview and Specifications
Detailed information on the nVent CADWELD Flint Ignitor, model T320. This product is used to ignite starting material for nVent ERICO Cadweld and nVent LENTON Cadweld rebar connections. Includes features, warnings, and regional contact information.
Preview nVent ERIFLEX 569150 Distribution Block Jumper Link - 160A
Datasheet for the nVent ERIFLEX 569150 jumper link, a 160A distribution block accessory designed for termination points. Features tin-plated terminals for copper or aluminium conductors and IP2X touch protection.
Preview nVent ERIFLEX FleXbus Advanced Installation Guide
Comprehensive installation guide for the nVent ERIFLEX FleXbus Advanced busbar system, covering setup, connections, and optional accessories. Learn how to safely and efficiently install your FleXbus system.
Preview nVent Electrical Connections RoHS Declaration of Compliance
This document declares the compliance of nVent Electrical Connections products with RoHS Directive 2011/65/EU and its amendment 2015/863/EU. It lists product families and specific part numbers that are compliant or non-compliant, along with any applicable exemptions.
Preview nVent LENTON Cadweld Filler Material RBF180 - Product Information
Information on nVent LENTON Cadweld filler material, a proprietary blend of iron and aluminum, for rebar splicing. Includes product details, safety notices, and contact information.
Preview nVent ESD Clip for Strut for AdvancedMC - Product Information
Detailed information on the nVent ESD Clip for Strut, catalog number 20849-021, designed for AdvancedMC guide rails. Includes product attributes and installation warnings.