HVAC Control & Balancing Dampers

Models VCD, ICD, FBH, FBV, MBD and RBD

• Selection • Construction • Performance

Design and Construction Features

Commercial Control Dampers are used in buildings to regulate the flow of air in an HVAC system. They can be used in intake, exhaust, or mixed air applications. There are two categories of control dampers: Volume Control (pages 2-15) and Balancing (pages 16-19).

Diagram of a control damper with labels: Bearing, Blade seal, Linkage, Blade, Jamb seal, Frame, Axle.

Frame - Tog-L-Loc® Advantage

Greenheck control dampers utilize a 5 in. x 1 in. (127 mm x 25 mm) hat channel frame. Each frame is built with four separate pieces of material and joined by the Tog-L-Loc® process. The Tog-L-Loc process provides a more rigid frame that resists "racking" better than welded construction.

Close-up of a reinforced corner showing the Tog-L-Loc® connection.

Frame Options

There are five frame options available:

Illustrations of the five frame options: Channel Frame, Single Flange, Single Reversed Flange, Double Flange, and Quick Connect.

Maximize Performance - Low Profile Frame

On dampers that are 17 in. (432 mm) high or less, Greenheck uses a low profile top and bottom frame section to maximize free area, which allows for lower pressure drop and increases damper performance.

Diagram comparing Greenheck's free area to a competitor's, highlighting Greenheck's advantage.

Blades

Illustration of a 3V Blade.
Illustration of a Steel Airfoil Blade.
Illustration of an Aluminum Airfoil Blade.
Illustration of an ICD Blade.

Variable Symmetric Blade Design (VSB) - a Greenheck Exclusive!

Extensive testing has shown that utilizing various blade sizes will reduce the required actuator torque, which leads to reduction in the size and quantity of actuators needed to operate a damper. This ultimately results in lower initial costs for the building owner, as well as a reduction in ongoing electrical power consumption.

Diagram illustrating balanced vs. unbalanced blades and their effect on actuator torque.

Parallel Versus Opposed Blade Operation

Greenheck control dampers are offered with either parallel or opposed blades. Each style has distinguishing characteristics in regard to the type of operation required.

Diagrams comparing parallel and opposed blade operation.

Seals

Seals are used for low leakage applications.

Diagram showing a jamb seal.

Linkage

Greenheck control dampers have blade linkages concealed in the frame to prevent additional pressure drop and unwanted noise. The linkage is engineered to accurately control each and every blade without need for adjustment.

Diagram showing the concealed linkage within the damper frame.

Bearings

The ICD-45 uses a dual bearing with inner sleeve and flanged outer bearing that features no metal-to-metal or metal-to-plastic contact.

Illustrations of synthetic and 304SS bearings.

Options and Accessories

Open Closed Indicator-OCI

The OCI provides positive open and closed signals when used in conjunction with remote indicator lights. Switches are physically linked to a damper blade and therefore give a true representation of the damper's position.

Factory Sleeve Option

Greenheck control dampers are available with factory-furnished sleeves in lengths up to 48 in. (1219 mm). When dampers are installed in factory sleeves, the “A” dimension specifies the location of the damper within the sleeve.

Diagram illustrating the factory sleeve option with dimensions.

Round Transition

Greenheck control dampers can be supplied with a round transition option in applications where dampers require installation into round openings. The sleeve is transitioned at each end to the appropriate round size.

Security Bars

When security becomes an issue, Greenheck offers optional factory-installed security bars. Security bars are factory welded into a 10 ga. (3.5 mm) sleeve.

Paint Finishes

A wide variety of paint finishes are available. See color charts on www.greenheck.com for standard color offering.

QR Codes

Greenheck has added QR (Quick Response) codes to the labels on commercial control and air measuring dampers. Scanning the QR code will link you to the Installation Instructions on www.greenheck.com.

Image of a Greenheck damper label with a QR code.

Actuators

Actuators may be installed at the factory or shipped loose with the necessary linkage and brackets required for mounting. Each unit is tested for operation before shipping when factory-installed actuators are ordered.

Manual Hand Quadrant

Pull Chain

Electric Actuator Checklist

Illustrations of Manual Quadrant, Pull Chain, Electric External Mount, and Electric Internal Mount actuators.

Pressure Drop

Pressure Drop Comparison

Greenheck compared the AMCA licensed pressure drop data of a VCD-33 12 in. wide x 12 in. high (305 mm x 305 mm) versus a competitor's equivalent 12 in. wide x 12 in. high (305 mm x 305 mm) damper. Both dampers were tested in a fully ducted system. The chart at the right shows the results at a velocity of 2,000 ft./min. The results are dramatic!

Chart showing AMCA Licensed Pressure Drop Data comparing Greenheck VCD-33 to a competitor.

To illustrate the cost saving benefits of a damper with lower pressure loss, Greenheck's VCD-33 control damper was tested. Greenheck's VCD-33 requires 30% less energy consumption to achieve the same CFM as the competitor. Based on an energy rate of $.10 per kWh, continuous operation (24 hours per day, 365 days per year) for one damper, a realized savings of $173.76 can be obtained.

Infographic showing energy consumption comparison: Greenheck VCD-33 uses 665 Watts, Competitor uses 863 Watts, a 30% difference.

Pressure Drop Performance

Pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft³ (1.2 kg/m³). Actual pressure drop found in an HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in an HVAC system.

Figure 5.3 illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.

Diagram for Figure 5.3: Fully ducted damper.

Figure 5.2 illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.

Diagram for Figure 5.2: Ducted damper exhausting into an open area.

Figure 5.5 illustrates a plenum mounted damper. This configuration has the highest pressure drop because of high entrance and exit losses due to the sudden changes of area in the system.

Diagram for Figure 5.5: Plenum mounted damper. Includes formula for calculating duct length.

AMCA Certified Pressure Drop Data

Greenheck Fan Corporation certifies that the model VCD-20 and VCD-40 shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to Air Performance ratings only.

Greenheck Fan Corporation certifies that the model VCD-23, 33, 34, 43, SEVCD-23 and 33 shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to Air Performance ratings only.

Greenheck Fan Corporation certifies that the model ICD-44 and ICD-45 shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to Air Performance ratings only.

ICD-44 and ICD-45

Pressure Drop Data for ICD-44 and ICD-45
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .03 .01 .05 .02 .01 .05 .01 .01 .04 .01 .01 .04 .03 .01 .05
1000 .11 .04 .23 .08 .03 .21 .05 .02 .14 .06 .02 .18 .14 .06 .22
1500 .25 .09 .52 .19 .08 .47 .11 .04 .33 .14 .06 .42 .32 .14 .51
2000 .45 .17 .93 .34 .14 .84 .21 .08 .58 .25 .10 .74 .57 .25 .90
2500 .71 .26 1.44 .53 .22 1.32 .33 .12 .91 .40 .17 1.16 .89 .40 1.41
3000 1.03 .38 2.08 .77 .32 1.90 .47 .18 1.31 .57 .24 1.68 1.29 .58 2.04
3500 1.40 .52 2.83 1.05 .43 2.59 .64 .24 1.79 .78 .33 2.28 1.76 .79 2.78
4000 1.83 .67 3.70 1.37 .57 3.39 .84 .32 2.34 1.02 .43 2.98 2.30 1.03 3.70
Diagrams of ICD-44 and ICD-45 dampers.

VCD-20, 23, 33, 34, 40, 42, 43 and VCD-23V, 33V, 34V, 43V

Pressure Drop Data for VCD Series
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03
1000 .05 .03 .13 .03 .02 .12 .02 .02 .12 .03 .03 .12 .03 .02 .12
1500 .11 .08 .30 .06 .04 .26 .05 .03 .28 .07 .06 .28 .07 .07 .27
2000 .19 .13 .53 .10 .07 .47 .09 .06 .50 .12 .10 .49 .15 .12 .47
2500 .29 .20 .82 .16 .11 .75 .14 .09 .78 .18 .16 .77 .22 .18 .75
3000 .41 .29 1.19 .23 .16 1.04 .19 .13 1.12 .26 .22 1.12 .32 .26 1.07
3500 .55 .40 1.62 .30 .21 1.41 .27 .19 1.53 .36 .30 1.53 .43 .36 1.45
4000 .72 .51 2.10 .40 .28 1.90 .35 .25 2.00 .47 .39 2.01 .56 .46 1.91

SEVCD-23

Pressure Drop Data for SEVCD-23
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03
1000 .03 .02 .12 .03 .02 .12 .02 .02 .12 .03 .03 .12 .03 .02 .12
1500 .07 .05 .27 .06 .03 .26 .04 .02 .21 .07 .04 .24 .04 .04 .24
2000 .13 .08 .48 .10 .05 .45 .07 .04 .38 .11 .08 .43 .08 .07 .44
2500 .19 .12 .74 .15 .09 .71 .11 .06 .58 .17 .12 .67 .12 .11 .68
3000 .26 .17 1.07 .21 .13 1.02 .15 .08 .85 .23 .17 .96 .16 .15 .97
3500 .35 .23 1.46 .28 .17 1.40 .20 .12 1.15 .31 .22 1.31 .21 .20 1.32
4000 .45 .30 1.91 .36 .22 1.89 .26 .15 1.52 .39 .29 1.71 .27 .25 1.73
Diagrams of VCD-20, 23, 33, 34, 40, 42, 43 and VCD-23V, 33V, 34V, 43V dampers.

AMCA Certified Pressure Drop Data

VCD-33 and 34 / SEVCD-33

Pressure Drop Data for VCD-33, 34 and SEVCD-33
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .01 .01 .03 .01 .01 .03 .01 .01 .02 .01 .01 .03 .01 .01 .03
1000 .03 .02 .12 .03 .01 .11 .02 .01 .09 .03 .02 .11 .02 .02 .11
1500 .07 .05 .27 .06 .03 .26 .04 .02 .21 .07 .04 .24 .04 .04 .24
2000 .13 .08 .48 .10 .05 .45 .07 .04 .38 .11 .08 .43 .08 .07 .44
2500 .19 .12 .74 .15 .09 .71 .11 .06 .58 .17 .12 .67 .12 .11 .68
3000 .26 .17 1.07 .21 .13 1.02 .15 .08 .85 .23 .17 .96 .16 .15 .97
3500 .35 .23 1.46 .28 .17 1.40 .20 .12 1.15 .31 .22 1.31 .21 .20 1.32
4000 .45 .30 1.91 .36 .22 1.89 .26 .15 1.52 .39 .29 1.71 .27 .25 1.73
Diagrams of VCD-33, 34 and SEVCD-33 dampers.

VCD-40

Pressure Drop Data for VCD-40
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .08 .05 .10 .01 .01 .03 .01 .01 .03 .01 .01 .03 .06 .03 .08
1000 .31 .20 .40 .05 .02 .12 .04 .02 .11 .05 .03 .12 .23 .13 .29
1500 .69 .45 .88 .11 .05 .29 .09 .04 .26 .11 .07 .27 .52 .29 .63
2000 1.19 .76 1.54 .19 .10 .52 .16 .07 .46 .20 .12 .49 .91 .51 1.12
2500 1.84 1.19 2.41 .30 .15 .80 .24 .10 .72 .30 .19 .76 1.43 .81 1.76
3000 2.67 1.70 3.45 .43 .22 1.14 .35 .15 1.04 .43 .26 1.11 2.05 1.16 2.52
3500 3.59 2.29 4.75 .58 .30 1.60 .48 .20 1.43 .59 .36 1.53 2.82 1.59 3.40
4000 4.64 2.97 6.09 .76 .40 2.14 .62 .27 1.87 1.01 .64 2.88 3.69 2.09 4.52

VCD-43

Pressure Drop Data for VCD-43
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .01 .01 .04 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03
1000 .06 .03 .14 .04 .02 .12 .03 .01 .10 .03 .02 .11 .03 .02 .11
1500 .13 .07 .31 .10 .04 .27 .06 .02 .22 .13 .06 .26 .07 .06 .26
2000 .23 .14 .55 .18 .08 .48 .12 .04 .39 .23 .11 .46 .10 .08 .46
2500 .35 .21 .86 .28 .13 .75 .18 .06 .61 .36 .17 .72 .16 .12 .72
3000 .50 .29 1.23 .40 .19 1.07 .26 .09 .87 .51 .25 1.05 .23 .18 1.02
3500 .68 .39 1.67 .54 .26 1.47 .35 .13 1.19 .71 .34 1.43 .30 .24 1.40
4000 .88 .51 2.19 .70 .34 1.91 .46 .17 1.56 .93 .45 1.87 .39 .31 1.83

Pressure Drop Data

VCD-33V and VCD-34V

Pressure Drop Data for VCD-33V and VCD-34V
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03
1000 .05 .03 .13 .03 .02 .12 .02 .02 .12 .03 .03 .12 .04 .03 .12
1500 .11 .08 .30 .06 .04 .26 .05 .03 .28 .07 .06 .28 .08 .07 .27
2000 .19 .13 .53 .10 .07 .47 .09 .06 .50 .12 .10 .49 .15 .12 .47
2500 .29 .20 .82 .16 .11 .75 .14 .09 .78 .18 .16 .77 .22 .18 .75
3000 .41 .29 1.19 .23 .16 1.04 .19 .13 1.12 .26 .22 1.12 .32 .26 1.07
3500 .55 .40 1.62 .30 .21 1.41 .27 .19 1.53 .36 .30 1.53 .43 .36 1.45
4000 .72 .51 2.10 .40 .28 1.90 .35 .25 2.00 .47 .39 2.01 .56 .46 1.91
Diagrams of VCD-33V and VCD-34V dampers.

VCD-42

Pressure Drop Data for VCD-42
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .05 .03 .07 .01 .01 .04 .01 .01 .02 .01 .01 .03 .03 .02 .05
1000 .18 .12 .28 .05 .03 .17 .04 .02 .12 .01 .04 .18 .11 .06 .19
1500 .43 .28 .62 .12 .06 .37 .09 .05 .28 .14 .09 .40 .25 .14 .44
2000 .76 .49 1.11 .22 .11 .66 .17 .08 .50 .25 .16 .72 .44 .25 .78
2500 1.19 .77 1.73 .34 .17 1.04 .26 .13 .78 .39 .25 1.12 .69 .39 1.21
3000 1.71 1.11 2.50 .49 .24 1.50 .38 .19 1.13 .57 .36 1.62 1.0 .57 1.75
3500 2.33 1.51 3.41 .66 .33 2.04 .51 .26 1.53 .77 .49 2.21 1.36 .77 2.38
4000 3.04 1.98 4.45 .87 .43 2.66 .67 .34 2.01 1.01 .64 2.88 1.78 1.01 3.11
Diagrams of VCD-42 dampers.

VCD-43V

Pressure Drop Data for VCD-43V
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .01 .01 .04 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03
1000 .06 .03 .14 .04 .02 .12 .03 .01 .10 .03 .02 .11 .03 .02 .11
1500 .13 .07 .31 .10 .04 .27 .06 .02 .22 .13 .06 .26 .07 .06 .26
2000 .23 .14 .55 .18 .08 .48 .12 .04 .39 .23 .11 .46 .10 .08 .46
2500 .35 .21 .86 .28 .13 .75 .18 .06 .61 .36 .17 .72 .16 .12 .72
3000 .50 .29 1.23 .40 .19 1.07 .26 .09 .87 .51 .25 1.05 .23 .18 1.02
3500 .68 .39 1.67 .54 .26 1.47 .35 .13 1.19 .71 .34 1.43 .30 .24 1.40
4000 .88 .51 2.19 .70 .34 1.91 .46 .17 1.56 .93 .45 1.87 .39 .31 1.83
Diagrams of VCD-43V dampers.

Pressure Drop Data

VCDR-50 and 53

Pressure Drop Data for VCDR-50 and 53
Dimension inches 12 24 36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .01 .01 .02 .01 .01 .02 .01 .01 .02 .01 .01 .02 .01 .01 .02
1000 .06 .02 .10 .04 .01 .09 .03 .02 .09 .03 .02 .09 .04 .01 .09
1500 .13 .05 .22 .08 .03 .20 .05 .03 .20 .08 .05 .20 .15 .06 .20
2000 .23 .08 .38 .15 .06 .36 .09 .05 .36 .15 .09 .44 .23 .08 .38
2500 .37 .13 .60 .23 .09 .56 .13 .09 .56 .23 .13 .57 .39 .13 .56
3000 .53 .19 .86 .33 .13 .81 .19 .13 .81 .33 .19 .81 .53 .19 .81
Diagrams of VCDR-50 and VCDR-53 dampers.

VCDRM-53

Pressure Drop Data for VCDRM-53
Dimension inches 12 24 36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .04 .03 .05 .03 .02 .04 .05 .03 .02 .04 .05 .05 .06 .03 .05
1000 .15 .11 .18 .13 .10 .15 .19 .13 .10 .15 .19 .20 .25 .19 .20
1500 .33 .25 .42 .29 .21 .33 .42 .33 .42 .44 .57 .44 .57 .42 .44
2000 .59 .45 .75 .51 .38 .59 .75 .51 .59 .79 1.01 .79 1.01 .75 .79
2500 .93 .70 1.18 .79 .60 .92 1.18 .79 1.18 1.23 1.58 1.23 1.58 1.18 1.23

VCD-23V

Pressure Drop Data for VCD-23V
Dimension inches 12x12 24x24 36x36 12x48 48x12
AMCA figure 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5 5.2 5.3 5.5
Velocity (ft/min.) Pressure Drop in. wg
500 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03 .01 .01 .03
1000 .05 .03 .13 .03 .02 .12 .02 .02 .12 .03 .03 .12 .04 .03 .12
1500 .11 .08 .30 .06 .04 .26 .05 .03 .28 .07 .06 .28 .08 .07 .27
2000 .19 .13 .53 .10 .07 .47 .09 .06 .50 .12 .10 .49 .15 .12 .47
2500 .29 .20 .82 .16 .11 .75 .14 .09 .78 .18 .16 .77 .22 .18 .75
3000 .41 .29 1.19 .23 .16 1.04 .19 .13 1.12 .26 .22 1.12 .32 .26 1.07
3500 .55 .40 1.62 .30 .21 1.41 .27 .19 1.53 .36 .30 1.53 .43 .36 1.45
4000 .72 .51 2.10 .40 .28 1.90 .35 .25 2.00 .47 .39 2.01 .56 .46 1.91
Diagrams of VCD-23V dampers.

Air Leakage Performance

Air leakage is based on operation between 32° and 120°F (0 and 49°C). Tested for leakage in accordance with ANSI/AMCA Standard 500-D, Figure 5.5. Tested for air performance in accordance with ANSI/AMCA Standard 500-D, Figures 5.2, 5.3 and 5.5.

Torque

Data is based on a torque of 5.0 in-lb/ft² (0.56 N·m) applied to close and seat the damper during the test.

Leakage Class for VCD-23, SEVCD-23 and VCD-43
Leakage Class*
1 in. wg (0.25 kPa) 4 in. wg (1 kPa) 5 in. wg (1.2 kPa) 8 in. wg (2 kPa)
VCD-23, SEVCD-23
Maximum Damper Width
48 in. (1219 mm)
1A 1 1
VCD-43
Maximum Damper Width
60 in. (1524 mm)
1A 1 1 1

Data is based on a torque of 7.0 in-lb/ft² (0.79 N·m) applied to close and seat the damper during the test.

Leakage Class for VCD-33, VCD-34, SEVCD-33
Leakage Class*
1 in. wg (0.25 kPa) 4 in. wg (1 kPa) 8 in. wg (2 kPa)
VCD-33, VCD-34, SEVCD-33
Maximum Damper Width
60 in. (1524 mm)
1A 1 1

Data is based on a torque of 9.0 in-lb/ft² (1.02 N·m) applied to close and seat the damper during the test.

Leakage Class for ICD-44, 45
Leakage Class*
1 in. wg (0.25 kPa) 4 in. wg (1 kPa) 8 in. wg (2 kPa)
ICD-44, 45
Maximum Damper Width
48 in. (1219 mm)
1A 1 1

*Leakage Class Definitions

Maximum Leakage cfm/sq. ft. (cmh/sq.m)
Model @ 1 in. wg (0.25 kPa) @ 4 in. wg (1 kPa)
VCD-23V, 33V, 34V, 43V, VCD-40, VCDR-53, VCDRM-53 Class 1A Class 1

Specialty Control Dampers

ICD - Insulated Control Damper

Greenheck's ICD dampers were developed for applications where it is necessary to minimize thermal transfer and reduce condensation. ICD series dampers can be used in applications down to -70°F (-56°C) and up to 200°F (93°C) for:

Cross section of a thermally broken frame and blade.

AMCA Certified Energy Efficiency Performance

Greenheck Model ICD-44 has a Thermal Efficiency Ratio of 593%. Greenheck Model ICD-45 has a Thermal Efficiency Ratio of 941%. A damper's Thermal Efficiency Ratio (E) is a comparison of the thermal performance of the tested damper with that of a standard reference damper, which is a 3V blade damper with blade and jamb seals. A damper with the same thermal efficiency as the reference damper would have an E of 0%. A damper that is twice as efficient as the reference damper would have an E of 100%.

Face & Bypass Dampers

The face and bypass dampers are used in applications where two dampers are connected together allowing one damper to open while the other damper closes.

Face & Bypass Damper Specifications
F & B Style Blade Profile Blade Material Seals Bearings Axles Linkage Material Sizing Max. Velocity Ratings ft/min. (m/s) Max. Pressure in. wg (kPa)
Minimum Size (inches) Maximum Single Section Size (inches) Maximum Multiple Section Size (Face Only) FBH-23 FBH-33 FBH-43 FBV-23 FBV-33 FBV-43
Horizontal X X X X X X 8x6 (203x152) 48x74 (1219x1880) 96 x 74 (2438 x 1880) X X X 3000 (15.2) 5 (1.2)
Vertical X X X X X X 8x6 (203x152) 60x74 (1524x1880) 96 x 74 (2438 x 1880) X X X 4000 (20.3) 8 (2)
3V X X X X X X 8x6 (203x152) 60x74 (1524x1880) 96 x 74 (2438 x 1880) X X X 3000 (15.2) 5 (1.2)
Airfoil X X X X X X 8x6 (203x152) 48x74 (1219x1880) 96 x 74 (2438 x 1880) X X X X X X 4000 (20.3) 8 (2)
Galvanized X X X X X X 8x6 (203x152) 48x74 (1219x1880) 96 x 74 (2438 x 1880) X X X 3000 (15.2) 5 (1.2)
Aluminum X X X X X X 8x6 (203x152) 60x74 (1524x1880) 96 x 74 (2438 x 1880) X X X 4000 (20.3) 8 (2)
TPE X X X X X X 8x6 (203x152) 48x74 (1219x1880) 96 x 74 (2438 x 1880) X X X X X X 3000 (15.2) 5 (1.2)
Silicone O O O O O O 8x6 (203x152) 60x74 (1524x1880) 96 x 74 (2438 x 1880) O O O O O O 4000 (20.3) 8 (2)
Synthetic X X X X X X 8x6 (203x152) 48x74 (1219x1880) 96 x 74 (2438 x 1880) X X X X X X 3000 (15.2) 5 (1.2)
316 Stainless Steel O O O O O O 8x6 (203x152) 60x74 (1524x1880) 96 x 74 (2438 x 1880) O O O O O O 4000 (20.3) 8 (2)
Steel X X X X X X 8x6 (203x152) 48x74 (1219x1880) 96 x 74 (2438 x 1880) X X X X X X 3000 (15.2) 5 (1.2)
316 Stainless Steel O O O O O O 8x6 (203x152) 60x74 (1524x1880) 96 x 74 (2438 x 1880) O O O O O O 4000 (20.3) 8 (2)
Steel X X X X X X 8x6 (203x152) 48x74 (1219x1880) 96 x 74 (2438 x 1880) X X X X X X 3000 (15.2) 5 (1.2)
316 Stainless Steel O O O O O O 8x6 (203x152) 60x74 (1524x1880) 96 x 74 (2438 x 1880) O O O O O O 4000 (20.3) 8 (2)
Diagrams of FBH and FBV dampers.

Manual Balancing Dampers

Manual balancing dampers are control dampers that regulate the flow of air but are not intended to be used in applications as a positive shut-off or for automatic control. These dampers are shipped with manual hand quadrants that can be locked in place. There are three balancing damper models available.

Illustrations of MBD-10, MBD-15, and MBDR-50 balancing dampers.

Cable Operator Option

The cable operator is ideal for applications where it is difficult to get access to manually adjust the damper and balance airflow. They are adjusted via cable actuation using a 1/4 in. nut driver at the ceiling or wall.

Bowtie Damper

The BTDR-50 is a cable operated radial blade balancing damper (also known as a bowtie damper) that is designed for easy airflow adjustment at an air outlet or plenum neck. They are adjusted using a nut driver or screwdriver.

Diagrams illustrating the Cable Operator Option and the BTDR-50 Bowtie Damper.

Remote Balancing Dampers

Remote balancing dampers offer the same function as a manual balancing damper plus the added benefit of controlling the damper remotely at a diffuser or wall plate. These remote balancing dampers are ideal for applications where it is difficult to gain access to manually adjust the dampers to balance airflow. The "EZ Balance" remote control operates the damper motor by connecting to the wall, ceiling, or diffuser mounted RJ11 connector. There are three remote balancing damper models available.

Illustrations of RBD-10, RBD-15, and RBDR-50 remote balancing dampers.

Accessories

A wide variety of accessories are available for the RBD and RBDR series.

Illustrations of accessories: Plenum rated cables, Round ceiling plate, Wall plates with ports, and EZ Balance remote.

Automatic Balancing Dampers

The automatic balancing dampers (ABD) automatically adjust to system pressure changes to maintain a constant airflow to compensate for changes in pressure, reducing the amount of energy required to ventilate a space while improving the indoor air quality.

Diagram comparing a Traditional Balancing System with an unbalanced airflow to a Balanced System with automatic adjustment.

Automatic Balancing Dampers

ABD

Model ABD is an automatic balancing damper designed to maintain constant airflow volume in HVAC applications. The damper blade is calibrated to automatically adjust to changing pressures. This damper can be used in supply or exhaust applications.

Illustration of the ABD damper.

ABD-FD

Model ABD-FD is an automatic balancing damper with a UL 555 rated 1½ or 3 hour static fire damper. The ABD-FD is designed to maintain a constant airflow volume in HVAC applications. The damper blade is calibrated to automatically adjust to changing pressures. The assembly will include a UL 2043 rated ABD, flanged sleeve, UL 555 rated curtain fire damper (FD-150 or FD-350), and optional grille.

Illustration of the ABD-FD damper.

ABD-T

Model ABD-T is an automatic balancing damper with a square transition. The transition can be removed and flipped to the other side of the damper using a factory-supplied quick adapter plate. The ABD-T can be used in both supply and exhaust applications.

Illustration of the ABD-T damper.

ABD-RB

Model ABD-RB combines an automatic balancing damper (model ABD) with the convenience of a factory-supplied register box. The ABD-RB can be configured for supply or exhaust applications and can be mounted in both walls and ceilings. In addition, the ABD can be mounted in either the side or the back of the register box. All ABD models maintain a constant CFM independent of the system pressure to prevent over or under ventilation. The ABD-RB is also available with a factory-supplied grille.

Illustrations of ABD-RB damper mounted on a wall and ceiling.

ABD-Z1

Model ABD-Z1 is designed to provide on/off control to a ventilation system. The ABD-Z1 has a shutoff damper with an electric actuator, automatic balancing damper (ABD), and a plenum box as one assembly.

Illustration of the ABD-Z1 assembly.

ABD-Z2

The ABD-Z2 is an automatic balancing damper that includes a two-position actuator which allows the unit to toggle between two user defined constant CFM set point minimum and a boosted on demand CFM. The ABD-Z2 is ideal for helping achieve the requirements of ASHRAE 62.2 for acceptable indoor air quality. Optional return/exhaust grille is available.

Illustration of the ABD-Z2 damper.

ABD Installation for Supply and Exhaust Applications

The ABD may be installed with a UL 555C rated ceiling radiation damper (CRD). This allows for a compact assembly designed to maintain a constant airflow volume in HVAC applications, while also limiting the radiant heat transfer through openings in the ceiling membrane of fire resistance-rated floor/ceiling assemblies of three hours or less.

Grilles

The following grilles are available on ABD-FD, ABD-RB, ABD-Z1, and ABD-Z2:

Illustrations of available grilles: Return/Exhaust Grille Surface Mount, Double Deflection Grille Vertical Blades, Single Deflection Grille Vertical Blades, and Double Deflection Grille Horizontal Blades.

Ratings

ABD Ratings
ABD ABD-FD ABD-RB ABD-T ABD-Z1 ABD-Z2
Pressure Rating
0.2 in. wg to 2 in. wg (0.05 kPa to 0.5 kPa)
Volume
25 cfm to 425 cfm (.012 m³/s to .201 m³/s)
Volume
25 cfm to 275 cfm (.012 m³/s to .130 m³/s)
Temperature
25°F to 150°F (-4°C to 65°C)

Airflow Range by Size

ABD Airflow Range by Size
ABD Diameter in. (mm) Individual Set Points Airflow Range CFM* (m3/s)
ABD ABD-FD ABD-RB ABD-T ABD-Z1 ABD-Z2
4 (102) 20 25 to 130 (.012 to .061)
5 (127) 20 25 to 130 (.012 to .061)
6 (152 mm) 24 50 to 275 (.024 to .130)
8 (203) Exhaust 26 125 to 400 (.059 to .189)
8 (203) Supply 26 105 to 425 (.050 to .201)

* Note: Airflow range determined through +/- 10% of average airflow over the pressure range.

Drive Arrangement Definition

Each damper is given a drive arrangement code to help describe the construction of the damper. The following breaks down what each number and letter represents.

22-2FER-2

  1. Number of sections wide
  2. Number of sections high
  3. Number of actuators or manual quadrants
  4. Who supplies the actuators or manual quadrants (F - Factory, C - Customer Supplied (field mounted))
  5. Actuator or manual quadrant mounting (E - External, I - Internal, B - Both internal and external)
  6. Actuator or manual quadrant location (L - Left-hand drive, R - Right-hand drive, B - Both right and left)
  7. Number of jackshafts
Diagram illustrating the drive arrangement code components and damper dimensions.

Heavy-Duty Industrial Control Dampers

Industrial control dampers are for control and shut-off applications. There is a wide variety of configurations, options, accessories, and actuators available. These control dampers are capable of pressures up to 30 in. wg and velocities up to 7000 fpm.

Illustrations of HCD Series and HCDR Series heavy-duty industrial control dampers.

Our Commitment

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.

PDF preview unavailable. Download the PDF instead.

controldampers catalog ?sfvrsn=7d4d4369 8 Adobe PDF Library 17.0

Related Documents

Preview Greenheck Damper Coatings: Options and Selection Guide
Explore Greenheck's comprehensive range of damper coatings, including Anodize, Baked Enamel, Hi Pro Polyester, Hi Temp Silver, Hi Temp Flame Control, Industrial Epoxy, and Kynar/Hylar. Learn about their properties and applications for commercial and industrial HVAC systems.
Preview Greenheck VCD-20 Control Damper - Specifications and Performance
Detailed specifications, performance data, construction details, and application information for the Greenheck VCD-20 series 3V blade control damper, including AMCA ratings and actuator mounting guidelines.
Preview K6746MD Louver Installation Manual | GREENHECK
Comprehensive installation, operation, and maintenance manual for the GREENHECK K6746MD Channel Installation with VCD-40 Damper, including specifications, wind load data, and Miami-Dade approved anchor tables.
Preview Greenheck Damper Selection Guide: Metric Version - HVAC Air Control
A comprehensive selection guide for Greenheck dampers, providing metric specifications for a wide range of air control products including fire, smoke, control, backdraft, and relief dampers. Features model numbers, sizes, performance data, and links to technical documentation.
Preview Greenheck KSQ Series Rooftop Supply Mixed Flow Fans: Installation, Operation, and Maintenance Manual
Comprehensive guide for installing, operating, and maintaining Greenheck KSQ Series Rooftop Supply Mixed Flow Fans. Covers safety, handling, dimensions, installation steps, maintenance, and troubleshooting.
Preview Greenheck SDPF-U Spiral Duct Grille: Specifications, Features, and Dimensions
Comprehensive product information for the Greenheck SDPF-U Spiral Duct Grille, including features, available finishes, optional accessories, detailed dimensional diagrams, and a universal spiral table for supply and return applications.
Preview Greenheck SP-B150 Ceiling Exhaust Fan Submittal Data and Specifications
Detailed submittal data and technical specifications for the Greenheck SP-B150 ceiling exhaust fan, including construction features, performance curves, dimensional data, motor details, and the optional Round Duct Connector (RDC).
Preview Greenheck SP-B110 Ceiling Exhaust Fan Submittal and Specifications
Comprehensive submittal data for the Greenheck SP-B110 Ceiling Exhaust Fan, detailing standard features, optional accessories, dimensional information, performance curves, motor specifications, and the compatible Round Duct Connector (RDC). Complies with ASHRAE 62.2.