User Guide for Carrier models including: TBPL-24-H-C, TBPL-24-HM-C, TBPL-H-C, TBPL-24-H, TBPL-H, TMPL-24-H, TMPL-HM, TBPL-24-H-C Automation System Thermostats, TBPL-24-H-C, Automation System Thermostats, Thermostats

i-Vu Building Automation System TB & TM Plus Series Thermostats

i-Vu Building Automation System TB ...


File Info : application/pdf, 2 Pages, 299.55KB

PDF preview unavailable. Download the PDF instead.

11-808-1164-01
i-Vu® Building Automation System TB & TM Plus Series Thermostats
Enhance occupant comfort and optimize energy efficiency in a wide range of HVAC applications with the Carrier TB and TM Plus thermostats. Available with BACnet (TBPL series) or MODBUS (TMPL series) communication protocols, the TB and TM Plus thermostats seamlessly integrate with your building management system (BMS) or provides standalone zone/room control. Leveraging the advanced capabilities of Carrier's i-Vu® platform, the TB and TM Plus deliver precise temperature control for any space.
Key Features
· Easy-to-use touchscreen display · Temperature, humidity, and motion onboard sensors for optimal control · BACnet or MODBUS communication protocol capable (depending on model) for flexible system integration · Configurable inputs and outputs for versatile control · Real-time clock maintains accurate time for up to 7 days during power outages · Flexible power supply options (24VAC or 110-220V)*
*depending on thermostat model
Applications
· Fan (FCUs): Enhance occupant comfort by providing individual control over fan speed and temperature · Rooftop Units (RTUs): Optimize RTU operation for energy efficiency through precise temperature and airflow
control · Heat Pumps: Maximize heat pump performance and efficiency with integrated control of heating and cooling
modes · Variable Frequency Drives (VFDs): Seamlessly integrate with VFDs to fine-tune motor speeds and optimize
energy consumption

TB & TM Plus Series Thermostats

Specifications
TB Plus Series (BACnet) Options Branded Unbranded Communication
TM Plus Series (MODBUS)
Options Unbranded Communication
Power Requirements
Display Sensing Element Temperature Humidity Range: 10-90% Accuracy: ± 3% Typical Motion
Sensor Type: PIR, quad, omnidirectional Distance: 16.4 ft. (5 m) Detection Range: 90 x 30 (HxV) Movement Speed: 2.62 ­ 3.94 ft/s (0.8 ­ 1.2 m/s) Detection Object: 15.75 x 9.84 in. (400 x 250 mm)
Inputs
Outputs
Environmental Operating Range Housing Mounting Compliance
Dimensions
Weight

Part#

24V, Temp., Humidity

24V, Temp., Humidity, Motion

110-220V, Temp. Only

-

TBPL-24-H-C

TBPL-24-HM-C

TBPL-H-C

-

TBPL-24-H

-

TBPL-H

-

BACnet MS/TP (subordinate device) Baud rates up to 76.8 kbps, detected and set automatically by the thermostat
Part#

24V, Temp., Humidity

-

-

TMPL-24-H

-

-

Modbus RTU (server) Baud rates up to 76.8 kbps, detected and set automatically by the thermostat

24 VAC ± 15% 4VA no load, 76 VA Full Load
Backlit, Resistive Touchscreen

110-220V, Temp., Humidity, Motion
TMPL-HM
110-220 VAC

Range: 41-95° (5-35°C), Accuracy: ± 1°F (0.5°C)

X

X

X

X

-

X

-

X

T1, 0 - Normally Open (NO) or Normally Closed (NC) dry contract, or 0-10 Vdc AI, or 50 kOhm thermistor @ 77°F (25°C) A, B - Communication +/- (RS485) In1, 0 - NO or NC dry contract, or 0-10 Vdc AI, or 50 kOhm thermistor @ 77°F (25°C) C, R ­ Power 24 VAC
11, 12, 13 ­ DO, 3A 14 ­ DO 0.3A 15, 16 - DO 0.3A or AO 0-10 Vdc, 5 mA max.,not isolated
50° to 122°F (10° to 50°C), 10 - 90% RH, non-condensing
Rectangular form factor, fire-retardant ABS plastic, UL94V-0
Installs to a standard wall box with mounting hardware included (consult technical instructions)
FCC CFR47, chapter 1, subchapter A, part 15, class B ICC, ICES-003, class B CE Mark LVD, 2014/35/EU RoHS 2011/65/EU C-Tick Mark, AS/NZS 61000-6-3 CA Prop. 65
3.15" W x 5.04" H x 0.62" D (8cm W x 12.8cm H x 1.55cm D) w/ PIR 3.15" W x 4.65" H x 0.62" D (8cm W x 11.81cm H x 1.55cm D) w/o PIR NOTE: Depth of unit that inserts into gang-box is 0.95" (2.4cm)
9.7 oz (0.28 kg)

©2025 Carrier. All Rights Reserved. Cat. No. 11-808-1164-01 Rev. 01/25 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs, without notice and without incurring obligations. All trademarks and service marks referred herein are property of their respective owners.

For more information, contact your local Carrier Controls Expert.
Controls Expert Locator: www.carrier.com/controls-experts

