User Manual for SIEMENS models including: 289X, 2AL8A289X, QAA2890WI, QFA2890WI, QPA2892WI, Symaro Thread Room Sensor, Symaro Room Sensor, Thread Room Sensor, Room Sensor, Sensor

023 QxA289x WI A6V12871702 en-- a

Product Manual

Beijing Siemens Cerberus Electronics Ltd. 289X 2AL8A289X 2AL8A289X 289x


File Info : application/pdf, 12 Pages, 454.93KB

PDF preview unavailable. Download the PDF instead.

GetApplicationAttachment.html?id=6119675
SymaroTM
Thread room sensor
QAA2890/WI, QFA2890/WI, QPA2892/WI

Thread room sensor
 Wireless communication KNX IoT over Thread  Battery-powered:
QAA2890/WI, QFA2890/WI: 3 x alkaline batteries type AAA, 1.5 V QPA2892/WI: 2 x alkaline batteries type AA, 1.5 V
 Temperature accuracy: ±0.3 K@21...25 °C, ±0.7 K@15...21 °C/25...35 °C, ±1 K@0...15 °C/35...50 °C
 Relative humidity accuracy: ±2 % r.h.@30...70 % r.h., ±5 % r.h.@0...30 % r.h./70...100 % r.h.
 CO2 accuracy: ±50 ppm / ±2 % m.v. @0...2000 ppm  Range of use: -15...+50 °C / 0...100 % r.h. (non-condensing) / 0...5000 ppm

A6V12871702_en--_a 2022-05-10

Smart Infrastructure

Use
Sensors acquire the following values in ventilation and air conditioning plants:  Temperature  Relative humidity  CO2 concentrations Wireless communication KNX IoT over Thread exchanges sensor data with controllers, tools or the cloud over a wireless Thread network.

Functions

Relative humidity The sensor acquires relative humidity via a digital capacitive relative humidity sensor with bandgap temperature sensor. The electronic measuring circuit converts the sensor element's humidity signal to a wireless digital signal (0...10000), corresponding to a relative humidity range of 0...100 %.
Temperature The sensor acquires the temperature via a digital humidity and temperature sensor. The temperature signal from sensing element is converted to wireless digital signal (0...10000), corresponding to a temperature range of 0...50 °C.
CO2 concentration The SymaroTM air quality sensor acquires the CO2 concentration by infrared absorption measurement (NDIR). The resulting wireless digital output signal (0...5000) is proportional to the CO2 content of the ambient air, corresponding to a CO2 concentration range of 0...5000 ppm.

Mechanical design
Thread room sensors are designed for wall mounting, flush mounting and tape mounting. They are suitable for use with most commercially available recessed conduit boxes. The device has 2 parts:  Plastic housing with electronic components  Mounting plate

Type summary

Product number
QAA2890/WI

SSN NO.

Temperature Humidity

measuring measuring

range

range

S55720-S550 0...50 

---

QFA2890/WI S55720-S551 0...50 

0...100 %

QPA2892/WI S55720-S552 0...50 

0...100 %

CO2 measuring range

Operating Output signal voltage

---

DC 4.5 V (3 x Wireless

1.5 V AAA

digital signal

alkaline

batteries)

---

DC 4.5 V (3 x Wireless

1.5 V AAA

digital signal

alkaline

batteries)

0...5000 ppm

DC 3 V (2 x 1.5 V AA alkaline batteries)

Wireless digital signal

2 Siemens Smart Infrastructure

A6V12871702_en--_a 2022-05-10

Inbox items

Delivery When ordering, specify name and product number, e.g.: Thread room sensor QFA2890/WI.

Name Sensor Mounting plate Set of screws and plastic insert Mounting instructions Batteries
Tape

Quantity
1 1 1
1 QAA2890/WI, QFA2890/WI: 3 x 1.5 V AAA alkaline batteries QPA2892/WI: 2 x 1.5 V AA alkaline batteries
1

Equipment combinations

Type of units KNX-IoT to BACnet gateway 1) Thread mesh extender

Product number OCT200.KNBA OCT100.R

SSN NO. S55812-Y102 S55812-Y101

1) Power adapter needs to be ordered separately. All documents can be downloaded from http://siemens.com/bt/download.

Product documentation

Title Mounting instruction Quick start guide CE declarations RCM UKCA FCC Environmental product declaration

Document ID A6V12816395 A6V12905642 A5Wxxx A5Wxxx A5Wxxx A5Wxxx A5Wxxx

Related documents such as environmental declarations, CE declarations, etc., can also be downloaded at the following Internet address:
www.siemens.com/bt/download

Siemens Smart Infrastructure

3 A6V12871702_en--_a
2022-05-10

Notes Safety

CAUTION
National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage.  Observe national provisions and comply with the appropriate safety regulations.
WARNING
Explosion due to fire or short-circuit, even with discharged batteries Risk of injury due to flying parts  Prevent the batteries from coming in contact with water.  Do not recharge batteries.  Do not damage or disassemble batteries.  Do not heat batteries over 85 °C.
WARNING
Risk of explosion Personal injury and property damage  Install the battery at the correct polarity (+/-) using the illustration in the battery
compartment.  Install only the correct battery types according to the indication in the battery
compartment.  In case of a leakage, avoid contact with skin, eyes and mucous membranes.  Remove leaking battery from the battery compartment with a cloth.
Observe the following:  The batteries must be new and undamaged.  Do not mix new and used batteries.  Store, transport and dispose of the batteries in compliance with local requirements,
regulations and laws and observe the instructions of the battery manufacturer.
NOTICE
Radio frequency energy Interference to radio communications  Install and use equipment in accordance with installation guide.  Read all regulatory compliance information.

4 Siemens Smart Infrastructure

A6V12871702_en--_a 2022-05-10

Mounting
Location

Mounting instructions
Chemical vapors

 The device is designed for wall mounting, flush mounting and tape mounting.  Inside wall (not an outside wall!) of the room; not in recesses, behind curtains, above or
close to heat sources or shelves and not on walls where a chimney is located. Do not expose the unit to spot lights or direct sunlight.  Install the sensor in the occupied space about 1.5 m above the floor and at least 20 cm from the next wall.  Seal the end of the conduit at the sensor to prevent false measurements caused by draughts through the conduit.
Mounting instructions are enclosed in the package.
The humidity sensor is a sensitive measuring device and must be handled with care. Chemical vapors at high concentration in combination with long exposure times may distort the sensor reading.

NOTICE
Avoid direct contact with chemicals in any form. Do not touch sensitive components with bare hands or tools as this will negatively impact measurement accuracy.

Siemens Smart Infrastructure

5 A6V12871702_en--_a
2022-05-10

Colors and patterns
LED In the following table:  Short press (<2 s) means short press the push button  Long press (>20 s) means long press the push button

LED color

Device status

LED pattern

Push button operation

Off

Unpowered device /

Off

N/A

powered device without

display

Green

Start up (e.g. battery installation)

Fast flashing (100 ms on / 100 ms off) N/A for 3 s

Normal (connected) Joining

On for 8 s
Flashing 1 (¹/ s on / / s off) during joining and is timeout after 120 s

Short press to activate LED
Short press to activate LED, then short press within 8 s to join 1)

Orange

Initial state (no connection) On for 8 s

Short press to activate LED

Factory reset

Fast flashing (100 ms on / 100 ms off) Long press to start factory

for 8 s

reset

Red

Connection lost 4)

Flashing 1 (¹/ s on / / s off) for 8 s Short press to activate

Low battery / Hardware

LED Fast flashing (100 ms on / 100 ms off)

error

for 8 s

Programming mode

Permanent on during programming mode and is timeout after 4 minutes.

Short press to activate LED, then short press within 8 s to enter programming mode 2) 3)

SRP service registration failure

Fast flashing (100 ms on / 100 ms off) N/A for 8 s

Off and green Firmware update

Constant off during firmware

N/A

downloading, fast flashing (100 ms on

/ 100 ms off) during new firmware

startup.

Notes
Maintenance

1) Device is in initial state (no connection). 2) Before entering programming mode, device needs connect to Thread network. 3) Device can enter programming mode via gateway. For details, see Quick start guide. 4) If device connection is lost (LED flashes red) and users want to join, they need factory reset the device firstly.
Change of batteries Check battery power by short press of the push button to activate the LED. The batteries are almost empty if LED is red and keeps fast flashing (100 ms on / 100 ms off) for 8 s and must be replaced. For optimal performance, we recommend using high performance alkaline batteries.

6 Siemens Smart Infrastructure

A6V12871702_en--_a 2022-05-10

Disposal

This symbol or any other national label indicate that the product, its packaging, and, where applicable, any batteries may not be disposed of as domestic waste. Delete all personal data and dispose of the item(s) at separate collection and recycling facilities in accordance with local and national legislation. For additional details, refer to www.siemens.com/bt/disposal.

Regulatory compliance information
FCC Statement This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:  Reorient or relocate the receiving antenna.  Increase the separation between the equipment and receiver.  Connect the equipment into an outlet on a circuit different from that to which the receiver
is connected.  Consult the dealer or an experienced radio/TV technician for help. This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. this device must accept any interference received, including interference that may cause undesired operation
FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland Ltd. could void user authority to operate the equipment. United States representative https://new.siemens.com/us/en/products/buildingtechnologies/home.html
IC Statement
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device. Le present appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisee aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioelectrique subi, meme si le brouillage est susceptible d'en compromettre le fonctionnement.
Radiofrequency radiation exposure statement
This equipment complies with FCC and IC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with a minimum distance of 20 cm between the radiator and your body. This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.

Siemens Smart Infrastructure

7 A6V12871702_en--_a
2022-05-10

Déclaration d'exposition aux rayonnements de radiofréquence Cet équipement est conforme aux limites d'exposition aux rayonnements IC établies pour un environnement non contrôlé. Cet équipement doit être installé et utilisé avec un minimum de 20 cm de distance entre la source de rayonnement et votre corps. Ce transmetteur ne doit pas être placé au même endroit ou utilisé simultanément avec un autre transmetteur ou antenne.
United Kingdom conformity assessed Contact for regulatory topics: (GB) Siemens plc, Sir William Siemens House, Princess Road, Manchester, M20 2UR
Radio equipment directive
Simplified EU Declaration of Conformity Hereby, Siemens Switzerland Ltd declares that the radio equipment type QAA2890/WI, QFA2890/WI and QPA2892/WI are in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: https://siemens.com/bt/download.
IMDA standards The device complies with IMDA standards.

Warranty

Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used.

Technical data
Power supply Operating voltage QAA2890/WI, QFA2890/WI QPA2892/WI
Battery life QAA2890/WI
QFA2890/WI
QPA2892/WI
Power consumption QAA2890/WI, QFA2890/WI QPA2892/WI

DC 4.5 V (3 x 1.5 V AAA alkaline batteries) DC 3 V (2 x 1.5 V AA alkaline batteries)
10 years (10 minutes transmission rate with COV on) 10 years (10 minutes transmission rate with COV on) 9 years (10 minutes transmission rate with COV on and CO2 indicator off)
Max. 20 mA Max. 250 mA

8 Siemens Smart Infrastructure

A6V12871702_en--_a 2022-05-10

Radio communication Frequency range Maximum transmission power Range
Protocol MAC protocol Zigbee channels
Functional data of sensor Humidity sensor Range of use Measuring range Measuring accuracy at 30...70 % r.h. 0...30 % r.h./70...100 % r.h. Time constant t63 Output signal Temperature sensor Range of use Measuring range Measuring accuracy at 21...25 °C 15...21 °C/25...35 °C, 0...15 °C/35...50 °C Time constant t63
Output signal CO2 sensor Range of use Measuring range Measuring accuracy at 0...2000 ppm Time constant t63 Output signal
Siemens Smart Infrastructure

2400...2483.5 MHz 7.73 dBm  10 m, depending on application and building Open Thread IEEE 802.15.4 11...26
0...100 % r.h. (non-condensing) 0...100 % r.h.
±2 % r.h. ±5 % r.h. 20 s Wireless digital signal (0...10000)
-15...+50 °C 0...50 °C
±0.3 K ±0.7 K ±1 K  8.5 min (depending on air movement and thermal coupling to the wall) Wireless digital signal (0...10000)
0...5000 ppm 0...5000 ppm
±50 ppm / ±2 % m.v. 5 min Wireless digital signal (0...10000)
9 A6V12871702_en--_a
2022-05-10

Ambient conditions and protection classification

Protection degree of housing

IP30 according to EN60529

Protection class

III according to EN60730

Environmental conditions Storage Climatic conditions Temperature Humidity Mechanical conditions Transport Climatic conditions Temperature Humidity Mechanical conditions Operation Climatic conditions Temperature (housing with electronics) QAA2890/WI & QFA2890/WI QPA2892/WI Humidity Mechanical conditions

-15...+50 °C 0...95 % r. h. (non-condensing) Class 1M2
-25...+70 °C <95 % r.h. Class 2M2
-15...+50 °C 0...50 °C 0...95 % r. h. (non-condensing) Class 3M2

Standards, directives and approvals

Product standard

EN 60730-1 EN 301489-1 EN 301489-17 EN IEC 62311 EN 300328

Electromagnetic compatibility (Applications) For use in residential, commerce, lightindustrial and industrial environments

EU conformity (CE)

xx *)

RCM conformity

xx *)

UKCA conformity

xx *)

FCC

xx *)

10 Siemens Smart Infrastructure

A6V12871702_en--_a 2022-05-10

Standards, directives and approvals UL RoHS
Environmental compatibility

UL 60730, http://ul.com/database
Directive 2011/65/EU restriction of the use of certain hazardous substances in electronic equipment
The product environmental declaration (xxx *) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).

Dimensions

General
Materials and colors
Sensor (complete assembly)
Packaging
Weight including package QAA2890/WI QFA2890/WI QPA2892/WI

Makrolon 6485, RAL9003 Silicone Corrugated cardboard
Approx. 204.6 g Approx. 204.6 g Approx. 226.3 g

*) The documents can be downloaded from http://siemens.com/bt/download.

Dimensions in mm

Type

D

QAA2890/WI, QFA2890/WI

14

QPA2892/WI

18

Siemens Smart Infrastructure

11 A6V12871702_en--_a
2022-05-10

Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies

Document ID Edition

A6V12871702_en--_a 2022-05-10

© Siemens Switzerland Ltd, 2022 Technical specifications and availability subject to change without notice.



References

Microsoft Word for Microsoft 365 Microsoft Word for Microsoft 365