1. DESCRIPTION

The 230mm and 300mm fans are axial extract fans suitable for commercial applications such as offices, clubs, restaurants, commercial kitchens, etc., where the ventilation requirements are high. The components are shown schematically in Fig. 1.

Fig. 1 Exploded View of Wall Model

The diagram shows the components of a wall-mounted fan, including an external grille, wall tube segment, wall plate, motor, and base.

For overall dimensions, refer to Fig. 2. Before commencing work, check that the fan will fit in the position proposed.

For best results the fan should be fitted to a wall but if this is not feasible, all models except the pull-cord actuator type can be fitted to the ceiling.

Fig. 2 Construction and Dimensional Specification

FAN SIZE (mm)230300
Grille Width (mm)340403
Grille Height (mm)340403
Wall Model, hole dia. (mm)280337
Wall Model, max. wall thickness (mm)305305
No. of Wall Tube Segment1417
Window Model, glass hole dia. (mm)260337
Window Model, glass thickness range (mm)5 to 326 to 32
Number of Window Kit Fasteners34

2. FITTING INSTRUCTIONS

A. Wall Model

  1. Cut the required diameter hole in the wall, Fig. 2. If the fan is to be fitted into the ceiling, ensure that the hole is between the joists.
  2. Construct the wall tube by assembling the wall tube segments in the correct orientation as shown in Fig. 3. For the 230mm fan the segment striations are on the internal diameter of the assembled tube. For the 300mm fan the segment striations are on the external diameter of the assembled tube. For wall thicknesses less than 305mm, the wall tube segments will need to be cut to length before assembling the tube.
  3. If the tube needs to be cemented in, it may be necessary to construct formers to ensure the tube stays circular during the time that the cement sets.
  4. Unclip the grille from the wall plate by pressing down the two fixing clips with a suitable tool. (A new UK 50p coin is ideal for this purpose).
  5. From outside, hold the wall plate against the wall locating the flange inside the wall tube. Mark the 4 positions holding the wall plate to the wall, drill, plug and screw the wall plate into position ensuring that the "this way up" arrow is pointing up.
  6. Clip the external grille in position by locating the recessed grille slots on the two arms on the underside of the wall plate, rotating the grille and closing the clip fixings. The grille louvres should be pointing down.
  7. Unclip the grille from the motor body by pressing down the two fixing clips with a suitable tool.
  8. From inside, hold the motor body against the internal wall, locating the fan spigot/flange inside the wall tube. With the "this way up" arrow pointing up, mark the 4 screw hole positions that hold the motor body. Drill, plug and screw the motor body into position.
  9. After installation, ensure that the impeller rotates freely.
  10. Connect the fan to the mains supply as outlined in the Wiring Instructions, Section 3.
  11. Fit the internal grille in position by locating the recessed grille slots on the two arms at the top side of the motor body, rotating the grille and closing the clip fixings. The grille louvres should be pointing upwards.

Fig. 3 Wall Tube Assembly

The diagram illustrates the assembly of wall tube segments for 230mm fans (internal striations) and 300mm fans (external striations), showing how the tube connects to the wall plate and motor body.

B. Panel Model

This model may be installed as a Panel installation by discarding the wall tube segments, the external grille and the wall plate. Install as in A above for the internal motor body and grille.

C. Window Model

This requires the wall model plus a window kit. Discard the segmented wall tube.

  1. Cut a suitable sized hole in the glass, Fig. 2.
  2. Fix one strip of self-adhesive foam to the back of the wall plate using the circular groove provided and the other strip of self-adhesive foam to the rear of the window box. Note the positions of the "this way up" arrows on both wall plate and window box ensuring that the join in the foam strip is at the bottom of each component.
  3. Snap fit 2 window fasteners in position in the wall plate (3 for 300mm fan), Fig. 4. Position the fasteners through the glass and locate into the window box unit, Fig. 4. Fit the adjuster nuts. To cater for the wide range of glass thicknesses possible, it may be necessary to change the adjuster nut around, Fig. 4.
  4. Fit the last fastener in position and tighten up all adjuster nuts.
  5. From the outside, fit the external grille. The grille louvres should be pointing down.
  6. From the inside, unclip the grille from the motor body and fit the motor body onto the window box. Locate motor body onto the two large clips on the window box and snap fit in position.
  7. After installation, ensure that the impeller rotates freely.
  8. Connect the fan to the mains supply as outlined in the Wiring Instructions, Section 3.
  9. Re-fit the internal grille. The grille louvres should be pointing upwards.

Fig. 4 Window Unit Assembly

The diagram shows the assembly of the fan unit for window installation, including the window box, adjuster nut, foam strips, toggle screw, impeller, motor, internal grille, external grille, and wall plate. It also indicates single glazing and double glazing configurations.

3. WIRING INSTRUCTIONS

WARNING: ENSURE THAT THE MAINS SUPPLY IS SWITCHED OFF BEFORE MAKING ELECTRICAL CONNECTIONS.

The extract fan is suitable for connection to 220-240V/1/50Hz supply. It is a class II double insulated product and MUST NOT be earthed.

There are two methods of cable entry to the fan. If the wiring is recessed, then use the rear knockout. If surface wiring is used, then the grommet should be pierced to permit entry from the top. A cable clamp is provided.

Electrical connections depend upon the type of fan being installed and the required mode of operation. After wiring is complete, replace the grille(s), turn on mains supply and check operation.

Fig. 5 Wiring Diagrams

The diagrams illustrate different wiring configurations. A note specifies that for "extract" operation, a link wire is required between D and M2, and for "intake" operation, a link wire is required between D and M1.

A. Basic Fan/Fan with Automatic Shutters

Single speed fan controlled by remote switch (e.g., light switch or auto-sensor). In addition to the L & N cable entry connections, it is necessary to insert a link between D and M2 for normal extract operation. If intake operation only is required, insert the link between D and M1 instead.

B. Shuttered Fan with Pull-Cord Actuator

Single speed fan. Pullcord actuator used to open shutters and start fan. Repeat pullcord application to stop fan. No remote switching is possible.

C. External Fan Control

An external fan control is available as an additional accessory for on/off, 2 speed operation, and intake/extract functions. It is suitable for use with the Basic Fan and Fan with Automatic Shutters. It is not suitable for use with pull-cord actuator fans.

4. CLEANING

Apart from removing odours, the fan also extracts airborne impurities such as dirt, dust, and grease. These gradually build up and detract from the efficiency and appearance of your fan. Therefore, to ensure peak performance of your fan, it should be regularly cleaned by a competent person.

Dis-Assembly

IMPORTANT: SWITCH OFF AND ISOLATE FROM MAINS SUPPLY. KEEP ELECTRICAL COMPONENTS AWAY FROM WATER.

  1. Remove the internal grille.
  2. Disconnect the electrical connections from the terminal block, noting which wire goes in each position.
  3. Remove the whole fan unit. See fitting instructions for guidance.
  4. Grasp the impeller firmly and pull from the motor shaft.
  5. The grille and impeller may be washed in warm water using a mild detergent.
  6. Wipe the motor housing assembly and shutter blades (when fitted) with a damp cloth.

Re-Assembly

  1. Press the impeller firmly back on to the motor shaft.
  2. Refit the fan unit into position following the fitting instructions. Ensure that the impeller rotates freely.
  3. Reconnect the electrical connections to the terminal block, ensuring that the wires are inserted into the correct positions.
  4. Replace the grille(s).
  5. Switch on mains supply and check fan operation.
Models: 230 300 Fans, 230 300, Fans

PDF preview unavailable. Download the PDF instead.

A700000010485425 Acrobat Distiller 10.1.5 (Windows)

Related Documents

Preview RS PRO Axial Fans - Technical Specifications and Product Information
Detailed specifications, features, and product comparison for RS PRO Axial Fans, including dimensions, electrical characteristics, and approvals. Learn about their suitability for cooling applications.
Preview RS PRO 300mm Commercial Extractor Fan with Fixed Grille - Product Overview
Detailed product information for the RS PRO 300mm Commercial Extractor Fan with Fixed Grille, including features, specifications, and applications. Suitable for panel or wall mounting.
Preview RS PRO Axial Fans - Datasheet and Specifications
Comprehensive datasheet for RS PRO Axial Fans, detailing features, general and mechanical specifications, approvals, and a comparison with similar models. Includes dimensional drawings and purchase information.
Preview RS PRO Axial Fans - Product Overview and Specifications
Detailed specifications and features for RS PRO Axial Fans (Stock No. 2557319), including dimensions, electrical data, airflow, and operating conditions. Information on similar models and compliance standards.
Preview RS Pro Floor, Heavy Duty Fan 400mm - Product Datasheet
Datasheet for the RS Pro Floor, Heavy Duty Fan. Features a 400mm blade diameter, 3 speed settings, 230V operation, and a Type G British 3-pin plug. Includes product details, benefits, and specifications for office use.
Preview RS Pro Floor Heavy Duty Fan 400mm Blade Diameter - Product Datasheet
Detailed datasheet for the RS Pro Floor Heavy Duty Fan, featuring a 400mm blade diameter, 230V power, Type C European plug, 3-speed settings, and adjustable height. Includes product specifications and features.
Preview RS PRO Pressure Mat Surface Mount 250mA, 25V dc - Product Specifications and Features
Detailed information on the RS PRO Pressure Mat Surface Mount, a 250mA, 25V dc sensor designed for commercial and residential applications. Features include seam-welded PVC construction, IP64 rating, and specific electrical and mechanical specifications.
Preview RS PRO 9kW Industrial Fan Heater (1746571) - User Manual and Safety Guide
Comprehensive user manual for the RS PRO 9kW Industrial Fan Heater (Model 1746571). Covers safety regulations, operating instructions, technical specifications, maintenance, and troubleshooting for industrial environments.