OVIA REX - Installation Instructions
WIRING INSTRUCTIONS
Suitable cable and power is to be supplied to the point of installation using IP rated connectors/junction boxes used where required. To remove terminal cover, grab the two sides of the ratchet clips. Once terminated ensure cover is pushed firmly over the wires to secure them in place, add a screw for additional security to maintain the IP rating. Depending on the fitting being installed, the cable can be terminated as follows:

STANDARD FITTINGS
L - (Brown) Switched Live E - (Green/Yellow) Earth N - (Blue) Neutral

EMERGENCY BATTERY BACKUP FITTINGS
See Notes Below
L - (Black) UnSwitched Live
Ls- (Brown) Switched Live
E - (Green/Yellow) Earth
N - (Blue) Neutral

NOTE: The emergency battery only fitting can be wired as maintained or non-maintained: · Maintained - The LED driver connects to `Switched Live' with `Unswitched' permanent live to the emergency inverter. (Luminaire can be switched on/
off, but will illuminate at a lower level on power failure) · Non-Maintained - The LED driver is not connected to `Switched Live' with `Unswitched' permanent live to the emergency inverter (luminaire only
illuminates on power failure). To enable the MANUAL emergency fittings to be tested, a keyswitch must be fitted inline with the Permanent Live input in to the luminaire.

EMERGENCY BATTERY BACKUP - MANUAL TESTING
On first operation a 24 hour charge will be required to fully charge the batteries. Failure to provide a permanent live will cause the batteries to power the fitting when it is switched off. This is not recommended as it will reduce the lifetime of the batteries. This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed. Recommended routine emergency test procedure in accordance with BS 5266. · Daily check - check that the status GREEN LED indicator is illuminated. · Monthly functional test - simulate a mains supply failure for approx. 30 secs by operation of key switch or switching off a circuit breaker.
Ensure normal supply is restored after test and the indicator status LED is illuminated. · Annual full three hour duration test - conduct a three hour continuous duration test. Simulate a mains supply failure for three hour continuous test by
operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and the indicator status LED is illuminated. If the luminaire fails any of the function or duration tests, please contact a qualified electrician.

SPECIFICATIONS:
Product Code Wattage
Dimensions IP Rating
Colour Temperature Dimmable
Emergency Fitting Battery Specification
Fitting Net Weight Input Voltage/Frequency
Body Material Warranty

OR5 5W
No N/A 0.446Kg

OR5-E
7.5W
244mm x 125mm x 96mm IP65
CTA Switchable - 3000K, 4000K & 6500K
No
Yes 6.4V 1500mAH LiFePO4
0.646Kg
220-240V~ 50/60Hz Polycarbonate 3 Years

COMPLIANT WITH:
The Rectangular LED Bulkheads have been tested and comply with the following statutory instruments, directives & standards:

· LV (2014/35) & EMC (2014/30) · BS EN 60598-1 · BS EN 60598-2-1

· IEC 62471 · BS EN 55015 · BS EN 61000-3-2

· BS EN 61000-3-3 · BS EN 61547

Errors & Omissions excluded. Specification is subject to change without notice.

OVIA Limited, Scolmore House, Mariner, Lichfield Road Ind. Estate, Tamworth, Staffordshire, B79 7UL

Telephone: 01827 300640 E-mail: technical@oviaUK.com

Website: www.oviaUK.com

V1

Installation, Technical & Safety Information Sheet

REX

OR5 & OR5-E Range of 230V~ 5W CTA Switchable Rectangular LED Bulkheads (Standard or Emergency)

GENERAL INFORMATION

PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCE.

Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or use of this product, consult a competent electrician.
· Before commencing any electrical work, to prevent the possibility of receiving an electric shock, ensure the mains isolator on the consumer unit is in the `OFF' position and safely isolated in accordance with Best Practice Guide 3.
· If in doubt consult a qualified electrician. The luminaire must be installed in accordance with the latest IET Wiring Regulations, BS7671. If this product is being fitted as a replacement part to an existing installation account must be taken to the version of the wiring regulations it was installed to.
· Before commencing installation, ensure the fitting is complete with the fixings required. · The fitting should be mounted on a smooth, flat surface, noting the position of any pipes or wiring behind the fixed surface to prevent the risk of
damage. · The LED light source is not dimmable. · The LED light source is not user-replaceable. · The LED light source is replaceable by professionals only. · The LED light source contained within this luminaire has an energy classification value of D.

INSTALLATION
Fig 1.

Fig 2.

Fig 3.

Fig 4.

Fig 1. Loosen the four screws and remove diffuser.
Fig 5.

Fig 2. Unlock LED array by sliding the PCB board over, allowing the screw heads to pass through the
larger holes. Fig 6.

Fig 3. Lift LED array away from base.
Fig 7.

Drill holes Fig 4. Drill the 4 fixing points out of
the base of the fitting.
Fig 8.

Fig 5. Choose cable entry point by removing either the rear or side knockouts. Gland M20 (not supplied) must be used for all
side knockouts. Fig 9.
Fig 9. Slide LED array back into original position to lock into place.

Fig 6. Using the 4 x fixing screws provided, fix the fitting onto the
mounting surface. Fig 10.

Fig 7. On the back of the LED array, terminate the cable
accordingly and secure via the cable clamp.
Fig 11.

Fig 8. Refit the LED array into the base.
Additional Accessories

ON

12
1 2 CCT ON OFF3000K ON ON 4000K OFF ON 6500K
Fig 10. Set colour temperature by adjusting the DIP switches
accordingly

OR5BT - Black Rectangular Trim

Fig 11. Refit the diffuser and secure with the four securing screws
supplied (Standard or Anti-Tamper)

OR5RD - Red Rectangular Diffuser

