WS9 SERIES WALL MODULE

FOR USE WITH FAN COIL UNITS

PRODUCT INFORMATION

Display:

24.6 °C

Honeywell Logo

SCOPE OF APPLICATION

The WS9 Series wall module is a temperature control device with an LCD display designed on the basis of the standard 86 wall-mount installation box. The units feature Modbus communications, monitor the actual room temperature and the set temperature in real time to control the opening/closing of the valves in the fan coil units to regulate the room temperature. The WS9 Series wall modules provide anti-freeze protection, as well as manual and automatic fan speed control.

The WS9 Series wall modules work with fan coil units and regulate the room temperature by controlling the fan speed and the opening/closing of the valves. The modules usually work with the fan coil unit control valves.

PERFORMANCE HIGHLIGHTS

TECHNICAL PARAMETERS

Communication protocol: RS485 Modbus
Baud rate: 4800/9600 (default)
OPERATING VOLTAGES: 100-240VAC 50/60HZ
24VAC±10% 50/60HZ
CONTROL ACCURACY: +1°C
CONTROL SIGNAL: ON/OFF OUTPUT
LOAD CAPACITY FAN: RESISTIVE LOAD 3A
INDUCTIVE LOAD 1A
VALVE: RESISTIVE LOAD 2A
INDUCTIVE LOAD 0.6A
PROTECTION RATING: IP20
TEMPERATURE SETTING RANGE: 10-32°C
TEMPERATURE DISPLAY RANGE: 0-37°C
OPERATING TEMPERATURE: -10 to 49°C
SHIPPING TEMPERATURE: -30 to 60°C
RELATIVE HUMIDITY: 5-90% RH NON-CONDENSATING
REMOTE SENSOR TYPE: NTC20K

ORDERING PART NUMBERS

PART NUMBER OPERATING VOLTAGES APPLICATIONS BACKLIGHT VENTILATION MODE
WS9B2WB 100-240VAC 2-pipe White Yes
WS9B4WB 100-240VAC 4-pipe White Yes
WS9E2WB 24VAC±10% 2-pipe White Yes
WS9E4WB 24VAC±10% 4-pipe White Yes

Note: The default Baud rate is 9,600 bit/s. If you require units with a Baud rate of 38,400 bit/s, please contact the marketing department.

PRODUCT DETAILS

OUTLOOK DESIGN

LCD

OFF SET OFF

18 H TEST SET UP E

AUTO

Honeywell Logo

Key Lock Indicator

Anti-Freeze Protection

Set Up

Temperature Display

Power Off

Set Point

Operation Modes

Valve Status (flashes when open)

Fan Status

FUNCTION

VALVE AND FAN CONTROL

The wall module reads the room temperature from the built-in sensor and maintains the set temperature by sending on/off commands to the valve. There are three fan speeds which can be set manually or automatically. In manual mode, the fan speed is adjusted by FH, FM and FL outputs. In automatic mode, the fan speed will be decided by the difference between the room temperature and the set value. The fan will shut down when the valve is not operating.

Figure 1. Automatic Fan Speed Control Algorithm

Difference between room and the set value

1°C: High fan speed

0.5°C: Medium fan speed

Low fan speed

Set value

-0.5°C: Medium fan speed

-1°C: High fan speed

Cooling

Heating

TEMPERATURE DISPLAY

Either the room temperature or the set temperature can be displayed. This can be done when installing and setting up the wall module.

BACKLIGHT

The backlight is activated when any button is pressed. It remains on for 8 seconds after the last button pressed. In setup mode, the backlight remains on for 60 seconds after the last button pressed.

KEYPAD LOCKOUT

It is possible to lock or unlock the keypad while the device is not in setting mode. When locked out, the keypad will be not respond when any of the buttons are pressed.

PRODUCT SIZE (mm)

Diagram showing dimensions: 86.0mm width, 64.0mm height, 10.4mm depth. Other dimensions indicated are 47.0mm, 32.6mm, 15.2mm, 18.0mm, 90.0mm.

OPERATION MODES

COMFORT MODE

In Comfort Mode, press the Up or Down button to set the temperature. Comfort Mode includes cooling, heating and automatic functions.

24.8 °C

Honeywell Logo

VENTILATION MODE

Press the mode key to enter Ventilation Mode. In Ventilation Mode, the fan will run at the manually set speed, with the valves shut down.

24.8 °C

Honeywell Logo

ANTI-FREEZE MODE

Anti-Freeze Mode is an option when heating. In Anti-Freeze Mode, when the room temperature falls below 6°C, the wall module (in OFF status) will begin heating automatically until the room temperature reaches 8°C.

OFF

05.0 °C

Honeywell Logo

PRODUCT WIRING DIAGRAM

Part number: WS9B2WB/U

Two-Pipe Application
WIRING DIAGRAM

220V 2-wired

Motorized valve wiring diagram

Diagram showing connections for a two-pipe application with a 220V supply, including motorized valve, fan, room key card/NTC20K, and Modbus connections.

Part number: WS9E2WB/U

Two-Pipe Application
WIRING DIAGRAM

24V 2-wired

Motorized valve wiring diagram

Diagram showing connections for a two-pipe application with a 24V supply, including motorized valve, fan, room key card/NTC20K, and Modbus connections.

Part number: WS9B4WB/U

Four-Pipe Application
WIRING DIAGRAM

220V 4-wired

Motorized valve wiring diagram

Diagram showing connections for a four-pipe application with a 220V supply, including motorized valve (Vc1, Vo1, Vc2, Vo2), fan, room key card/NTC20K, and Modbus connections.

Part number: WS9E4WB/U

Four-Pipe Application
WIRING DIAGRAM

24V 4-wired

Motorized valve wiring diagram

Diagram showing connections for a four-pipe application with a 24V supply, including motorized valve (Vc1, Vo1, Vc2, Vo2), fan, room key card/NTC20K, and Modbus connections.

TERMINAL DEFINITION

SYMBOL DESCRIPTION
vC2 Cooling valve is closed (four-pipe only)
v02 Cooling valve is open (four-pipe only)
N Power neutral wire
vC1 Heating/cooling valve is closed
v01 Heating/cooling valve is open
L Power live wire
FH High fan speed
FM Medium fan speed
FL Low fan speed
GND
RSB/RS Room key card/NTC20K
D+ Modbus 485+
D- Modbus 485-

TROUBLESHOOTING

SYMPTOM SOLUTION
FAILS TO ACTIVATE
  • Press ➔ to set the operation mode to ❄ (Cooling Mode).
  • Check whether the set temperature is lower than the room temperature.
  • Check whether the valve status indicator is flashing.
  • Wait for 5 minutes and check whether the cooling system starts.
FAILS TO ACTIVATE
  • Press ➔ to set the operation mode to ☀️ (Heating Mode).
  • Check whether the set temperature is higher than the room temperature.
  • Check whether the valve status indicator is flashing.
  • Wait for 5 minutes and check whether the heating system starts.
DOES NOT WORK
  • Check whether the buttons are locked.
  • Check whether the unit is OFF.
DOES NOT WORK
  • Check whether the buttons are locked.
  • Check whether it is in mode.
  • Check whether the unit is OFF.

Honeywell Environmental and Combustion Controls (Tianjin) Co., Ltd.

No. 158, Nanhai Road, Tianjin Economic-Technological Development Area

Postal Code: 300457

Tel: +86-22-66287000

Fax: +86-22-25325214

All specifications are subject to change without notice.

HBT-G.C.-Building-FDFMD-APR-2020-EN01

THE FUTURE IS WHAT WE MAKE IT

Honeywell Logo

PDF preview unavailable. Download the PDF instead.

ba-bms-WS9-datasheet Adobe PDF Library 15.0

Related Documents

Preview Honeywell TF428WNM/U Communicating Fan Coil Thermostat Specifications and Features
Detailed specifications, features, installation, and wiring diagrams for the Honeywell TF428WNM/U Communicating Fan Coil Thermostat. Includes information on system types, fan control, temperature settings, and Modbus communication.
Preview Honeywell T6800 Series Large LCD Digital Thermostat Data Sheet
Comprehensive data sheet for the Honeywell T6800 Series Large LCD Digital Thermostat, detailing its features, applications in 2-pipe fan coil systems, technical specifications, installation guidelines, and troubleshooting tips.
Preview Honeywell TB6575 & TB8575 Digital Fan-Coil Thermostats: Product Overview and Specifications
Detailed information on Honeywell's TB6575 and TB8575 series digital fan-coil thermostats, covering features, applications, specifications, and compatible accessories for residential and commercial use.
Preview Honeywell XE99 Series Fan-Coil Thermostats: Product Specification Sheet
This document provides detailed specifications, features, applications, installation, operation, and wiring diagrams for the Honeywell XE99 Series of fan-coil thermostats. It covers 2-pipe and 4-pipe fan-coil control, including models with auxiliary electric heat and 2-stage control.
Preview Honeywell TB6575/TB8575 SuitePRO Digital Fan Coil Thermostats - Guide Specification
Detailed guide specification for Honeywell's TB6575/TB8575 SuitePRO Digital Fan Coil Thermostats, covering system applications, features, sequence of operations, and configuration options for HVAC control.
Preview Honeywell T6861 Series Large LCD Digital Thermostat Datasheet
Comprehensive datasheet for the Honeywell T6861 Series Large LCD Digital Thermostat, detailing features, applications, technical specifications, wiring diagrams, installation, and troubleshooting for 2-pipe and 4-pipe fan coil systems.
Preview Honeywell LP916A, B, & C Pneumatic Remote Bulb Thermostats: Specifications and Features
Detailed specifications, features, and model information for Honeywell's LP916A, B, and C series Pneumatic Remote Bulb Thermostats, used for HVAC control in induction units, fan coil units, and unit ventilators.
Preview Honeywell T6570, T8570 Series Digital Fan-Coil Thermostats Product Data
Detailed product data sheet for Honeywell T6570 and T8570 Series Digital Fan-Coil Thermostats, covering applications, features, specifications, installation, operation, and wiring.