Emergency Bulkhead Exit Light

Model Numbers: 5059340964287, 5059340964034

Important Safety Information

❗ IMPORTANT: These instructions are for your safety. Please read through them thoroughly prior to handling the product and retain them for future reference.

Parts Included

Tools Required

Technical Data

Supply voltage5059340964287: 220-240 V~ 50 Hz
5059340964034: 110 V~ 50 Hz
Bulb TypeLED (3.5 W)
Operation ambient temperature (ta)0 °C to 45 °C
BatteryType: 1 x 3.2 V 1500 mAh 18650 LiFePO4. Replace only with the same or equivalent type.
Charging time24 hours
Energy efficiency classThis product contains a light source of energy efficiency class <D>.
Control gearReplaceable control gear by a professional.
ClassificationClass II product - Double Insulated - No earth required.
Ingress ProtectionIP66 - Powerful water jet-proof
ComplianceThis product complies with the conformity requirements of the applicable European Regulations or Directives.
This product complies with the conformity requirements of the applicable UK Regulations.

Guarantee

This product is covered by a 7-year manufacturer's guarantee (4 years for the battery pack) against manufacturing defects from the date of purchase or delivery, for normal use. To make a claim, you must present proof of purchase. This guarantee applies only to new products and not to second-hand or display items. Any replacement product will only be guaranteed until the expiry of the original guarantee period. The guarantee covers product failures and malfunctions provided the product is used for its intended purpose and is installed, cleaned, and maintained according to the information in these terms, the user manual, and standard practice. It does not cover defects or damage caused by normal wear and tear, improper use, faulty installation or assembly, neglect, accident, misuse, or modification. Ancillary costs (shipping, labour, etc.) and indirect damage are not covered. Rights under this guarantee are enforceable in the country of purchase and are in addition to your statutory rights.

Installation Instructions

Follow these steps carefully for installation:

Step 01: Mounting Preparation

Ensure the power supply is turned OFF before commencing. Decide on the mounting location. If mounting on a surface other than masonry, appropriate fixings must be purchased and used. Prepare mounting holes as required (e.g., Ø20 mm for cable entry).

Step 02: Fixing the Product

Securely fix the product to the mounting surface using the supplied screws and wall plugs (suitable for masonry). Ensure the chosen fixing points can support the full weight of the light fitting.

Step 03: Wiring

Refer to the terminal markings on the product for correct wiring. Ensure all electrical connections are tight and that no loose strands are left exposed. The wiring diagram provided is for reference only.

Step 04: Securing the Product

Complete the mounting process by securing all components as shown.

Step 05A: Back Entry

Utilize the back entry for cable management as illustrated.

Step 05B: Side Entry

Use the side entry for cable management, ensuring correct torque is applied (5.5 Nm) where specified.

Step 05C: Besa Box Mounting

The product can be mounted using a Besa Box with 50.8 mm fixing centres.

Step 06: Wiring Terminations

For Non-Maintained Operation: Connect Neutral (N), Line (L), and CPC (E) for continuity.

For Maintained Operation: Connect Neutral (N), Line (L), and CPC (E) for continuity.

For Maintained (Switchable) Operation: Connect Neutral (N), Switched Line (Ls), Line (L), and CPC (E) for continuity.

Wire colour coding: L = Brown or Red, N = Blue or Black, E = Green/Yellow.

Use cables with a cross-section of 1.0-2.5 mm² and a diameter of Ø6-12 mm.

Step 07-08: Further Connections

Continue with the remaining wiring and connection steps as depicted in the diagrams.

Step 09: Test Button

Locate the TEST BUTTON for performing function and duration tests.

Step 10: Final Connections

Complete all final electrical connections to the luminaire.

Emergency Exit Light Pictograms

The luminaire is designed for wall mounting and includes pictograms for emergency exit indication. These are typically displayed within a 100 mm x 100 mm area for clear visibility.

Care & Maintenance

Battery Replacement

The battery type is 1 x 3.2 V 1500 mAh 18650 LiFePO4. It is crucial to replace the battery only with the same or an equivalent type.

  1. Disconnect the battery from the converter.
  2. Remove the old battery.
  3. Install the new battery.
  4. Connect the new battery to the converter.

Self-Test and Testing Record

The luminaire is equipped with an automatic self-test function. A weekly 1-minute function test checks battery connection and LED module integrity. A yearly 3-hour duration test also verifies battery and LED module connections. A manual test button is available for on-demand inspection.

Test Button Operation:

Indicator Status Descriptions:

Important Note: In non-maintained mode, a lamp failure typically shows a green indicator. This indicator will turn red during a weekly functional test. Any failure indication status should be checked and rectified as soon as possible.

Initial Test Procedure: When the fitting is first powered on, press the manual test button to perform an initial test. With mains power connected, the green indicator should remain permanently on, confirming battery and LED module connections.

Charging and Testing Requirements: For accurate testing, luminaires must be connected to the mains supply for at least 24 uninterrupted hours. If mains power is switched off during a test, the test will be postponed for 3 days and will automatically initiate after 24 hours of charging.

Timing Accuracy: The timing functions have an accuracy of ±75 seconds per week and will be retained through power supply failures or interruptions for up to 7 days.

Manufacturer Information

UK Manufacturer: Kingfisher International Products Limited, 1 Paddington Square, London, W2 1GG, United Kingdom

EU Manufacturer: Kingfisher International Products B.V., Rapenburgerstraat 175E, 1011 VM Amsterdam, The Netherlands

For product information and manuals, visit:

Made in China.

Models: LXEL01-BH, LXEL01-BH Emergency Rectangular LED Bulkhead, Emergency Rectangular LED Bulkhead, Rectangular LED Bulkhead, LED Bulkhead, Bulkhead

File Info : application/pdf, 5 Pages, 2.32MB

PDF preview unavailable. Download the PDF instead.

pa 3651651

References

pdftk 2.02 - www tk.com itext-paulo-155 (itextpdf.sf.net-lowagie.com)

Related Documents

Preview Kingfisher Product Conformity Declaration and Manufacturer Information - Models 1047B, V30621 BX220IM/B3
Official declaration of conformity for Kingfisher International Products, including manufacturer and importer details, compliance with European and UK regulations, and links to online resources for models 1047B and V30621 BX220IM/B3.
Preview Kingfisher Steel Panel Radiator Installation and Safety Manual
Comprehensive guide for the safe installation, operation, and maintenance of Kingfisher Steel Panel Radiators. Includes product details, safety warnings, assembly instructions, and warranty information.
Preview Side Self-Closing Ball Bearing Drawer Runners 450mm - Installation Guide
This guide provides detailed instructions for installing 450mm side self-closing ball bearing drawer runners. It includes safety precautions, a parts list, step-by-step assembly instructions, dimension details, and information on the 2-year manufacturer's guarantee. Content is provided in English and French.
Preview 370W Concrete Mixer NBB553BEQ - Safety, Operating, and Technical Manual
Comprehensive safety and operating manual for the 370W Concrete Mixer NBB553BEQ, including technical specifications, assembly instructions, troubleshooting, and guarantee information. This guide provides essential information for safe and effective use of the concrete mixer.
Preview Kingfisher Garden Shed 5059340875408 Assembly Instructions
Comprehensive assembly instructions and safety guide for the Kingfisher Garden Shed model 5059340875408. Includes parts list, step-by-step guidance, and warranty information.
Preview Electric Towel Warmer User Manual and Installation Guide
Comprehensive guide for the electric towel warmer, covering safety, installation, operation, programming, and maintenance. Includes technical specifications and warranty information.