User Guide for EKC models including: EKC 361 Media Temperature Controller, EKC 361, Media Temperature Controller, Temperature Controller, Controller
User Guide Media temperature controller EKC 361 The controller and valve can be used where there are stringent requirements to accurate temperature control in connection with refrigeration. E.g.: · Cold room for fruits and food products · Refrigerating systems · Work premises in the food industry · Process cooling of liquids Features · The temperature is kept within an accuracy of ±0.25°C or better after a transient phenomenon. · The evaporator's temperature is kept as high as possible, so that the air humidity is kept high and waste is limited. · A transient phenomenon can be controlled with the adaptive function. Select either: - Fast build-up where underswings are allowed - Not quite so fast build-up where under swings are less pronounced - Build-up without underswings · PID regulation · p0 limitation © Danfoss | DCS (ADAP-KOOL®) |2015-11 DKRCI.PS.RP0.B2.02 | 1 User Guide | Media temperature controller, EKC 361 Introduction Functions · Modulating temperature control · Digital ON/OFF input for start/stop of regulation ICS/PM or forced closing of ICM · Alarm if the set alarm limits are exceeded · Relay output for fan · Relay output for solenoid valves · Analog input signal that can displace the temperature reference · Analog Output signal corresponding to selecting temperature as running display value. Please observe : Not possible if ICM is selected as valve ICS or PM Start/ stop © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 2 User Guide | Media temperature controller, EKC 361 Application examples ICS/PM ISC/PM with CVQ is a pilot-operated and pressure-dependent valve for controlling media temperature. The ICS or PM must be equipped with a CVQ pilot valve in order to position ICS or PM. The CVQ valve is operated by the EKC 361 controller. Please notice that a power failure will cause the CVQ pilot valve to fully open ICS/PM. If it is required that ICS/PM must close at power failure, the pilot valve type EVM-NC can be installed. If the Digital Input is ON, it releases the ICS/PM for controlling temperature. If the Digital Input is OFF, if stops controlling PM/ICS, but EKC 361 will maintain a CVQ minimum temperature. (Parameter n02) Please see separate literature for ICS/PM ICS : DKRCI.PD.HS0.APM : DKRCI.PD.HL0.A- ICM ICM is a direct activating and pressure independent valve for controlling media temperature. When ICM is selected, the ICM is positioned directly via the analog output 0/4-20mA output from the EKC 361. If the Digital Input is ON, it releases the ICM for controlling temperature. If the Digital Input is OFF, the ICM is forced to close. The opening degree OD 0-100 % can be limited by parameter n32 and n33. Please see separate literature for ICM ICM : DKRCI.PD.HT0.A- General for ICS/PM and ICM The EKC 361 can also operate a solenoid valve in the liquid line (Digital output on terminal 9 and 10). It will follow the status of Digital Input, however if a low temperature alarm is detected (A2 alarm) the solenoid valve in the liquid line will be closed. The EKC 361 can also operate a fan (Digital output on terminal 8 and 10). It will follow the status of Digital Input. The Parameter (r12) must be ON in order to ensure general operation. If Parameter (r12) is OFF, EKC 361 will operate corresponding to if Digital Input is OFF As media temperature sensor is Sair is used. Please observe that Sair can also be used to control liquid. As option an auxiliary temperature sensor Saux can be installed but only for monitoring. Sair/Saux can both be shown as running display value selected by parameter o17. The selected sensor (Sair or Saux) will be sent out on the Analog Output as 0/4-20 mA. Temperature scaling with parameter o27 and o28. Please observe by ICM the Analog Output is not available for sending temperature signals (Sair or Saux). It is normally recommended, on a aircooler, to install Sair, at the evaporator air outlet side. Extra options · PC operation The controller can be provided with data communication, so that it may be hooked up with other products in the ADAPKOOL® range of refrigeration controls. Operation, monitoring and data collection can then be performed from a PC - either in situ or at a service company. © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 3 User Guide | Media temperature controller, EKC 361 Function Very accurate temperature control With this system where controller, pilot valve and main valve have been adapted for optimum use in the refrigerating plant, the refrigerated products may be stored with temperature uctuations of less than ±0.25°C. High air humidity As the evaporating temperature is constantly adapted to the refrigeration needs and will always be as high as possible with a very small temperature uctuation, the relative air humidity in the room will be kept at a maximum. Drying-out of the products will in this way be reduced to a mini- mum. Temperature is quickly attained With the built-in PID control and the possibility of choosing between three transient phenomena, the controller can be adapted to a kind of temperature performance that is optimum for this particular refrigerating plant. See parameter (n07). · Fastest possible cooling · Cooling with less underswing · Cooling where underswing is unwanted. Regulation ICS/PM with CVQ The controller receives signals from room sensor Sair. This room sensor must be placed at the air outlet from the evaporator to obtain the best possible regulation. The controller sees to it that the required room temperature is maintained. Built-in between the controller and the actuator is a so-called inner control loop which constantly checks the temperature (pressure) in the actuator's pressure vessel. In this way a very stable control system is obtained. If there is a deviation between the required and the registered temperature the controller will immediately send more or fewer pulses to the actuator to counteract the error. A change of the number of pulses will act on the temperature and hence the pressure in the pressure vessel. As the charging pressure and the evaporating pressure p0 follow each other, a changed charging pressure will produce the e ect that the valve's opening degree is also changed. The ICS/PM with CVQ system maintains the pressure in the evaporator whatever pressure changes there may be on the suction side (on the ICS/PM valve's outlet). Evaporating pressure limitation (p0 limitation) The inner control loop mentioned above also causes the evaporating pressure to stay within a xed limit. In this way the system is safeguarded against a too low supply air temperature. It o ers the following advantages: - High-temperature systems can be connected to low-temperature compressor units - Protection against icing on evaporator - Frost protection of liquid coolers The allowed temperature in the actuator determines the evaporating pressure Actuator temperature Regulation with ICM When using ICM as selected valve the system will still control ICM in order to maintain Sair according to entered setpoint. This system does not include any inner control loop. It is a direct operating and pressure independent valve for controlling media temperature. (Sair). © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 4 User Guide | Media temperature controller, EKC 361 Survey of functions Function Normal display Normally Sair (017=Air) will be shown as running display value. If lower button is activated Saux will be displayed for 5 sec, and then return to Sair If (017=Au) Saux will be shown as running display value. If lower button is activated Sair will be displayed for 5 sec, and then return to Saux Para- Parameter by operation via data commeter munication Air temp. If ICM has been selected (n03=6) If (017=Air) Sair (017=Air) will be shown as running display value. If lower button is activated OD (u24) will be displayed for 5 sec, and then return to Sair. If (017=Au) OD (u24) will be shown as running display value. If lower button is activated Sair will be displayed for 5 sec, and then return to OD (u24) Reference Setpoint Regulation is performed based on the set value provided that there is no external contribution (o10). (Push both buttons simultaneously to set the setpoint). Temperature unit Here you select whether the controller is to indicate the temperature values in °C or in °F. If indication in °F is selected, other temperature settings will also change over to Fahrenheit, either as absolute values or as delta values. External contribution to the setpoint This setting determines how large a contribution (in °C/°F) is to be added to the set setpoint when the input signal is max. (20 mA). Correction of signal from Sair (Compensation possibility through long sensor cable). Correction of signal from Saux (Compensation possibility through long sensor cable). Start/stop of refrigeration With this setting refrigeration can be started and stopped. Start/stop of refrigeration can also be accomplished with the external switch function. See also appendix 1. Alarm The controller can give alarm in di erent situations. When there is an alarm all the light-emitting diodes (LED) will ash on the controller front panel, and the alarm relay will cut in. Alarm for upper deviation The alarm for too high Sair temperature is set here. The value is set in Kelvin. The alarm becomes active when the Sair temperature exceeds the actual reference plus A01. (The actual reference (SP + r06) can be seen in u02). Alarm for lower deviation The alarm for too low Sair temperature is set here. The value is set in Kelvin. The alarm becomes active when the Sair temperature drops below the actual reference minus A02. If a low temperature alarm is detected (A2 alarm) the solenoid valve in the liquid line (Digital output on terminal 9 and 10) will be closed Alarm delay If one of the two limit values is exceeded, a timer function will commence. The alarm will not become active until the set time delay has been passed. The time delay is set in minutes. Control parameters Actuator's max. temperature Set the temperature (°C) the actuator is to have at the limit of the regulating range. The setting ensures that the actuator will not become superheated and work itself away from the regulating range. Due to tolerances in the actuator the value must be set 10K higher than indicated in the curves on page 11. Actuator's min. temperature Set the temperature (°C) the actuator will have at the limit of the regulating range. The setting ensures that the actuator will not become too cold and work itself away from the regulating range. Due to tolerances in the actuator the value must be set 10K lower than indicated in the curves on page 11. - SP Temp. r05 Temp unit °C=0, °F=1 (In AKM only °C is displayed whatever the setting) r06 Ext. Ref.o set (°C/°F) r09 Adjust SAir (°C/°F) r10 Adjust SAux (°C/°F) r12 Main Switch A01 Upper deviation A02 Lower deviation A03 Temp alarm delay With data communication the importance of the individual alarms can be de ned. Setting is carried out in the "Alarm destinations" menu. See also page 10. n01 Q-max. temp. n02 Q-min. temp. © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 5 User Guide | Media temperature controller, EKC 361 Actuator type Here you de ne the actuator mounted in the system: 1: CVQ -1-5 bar 2: CVQ 0-6 bar 3: CVQ 1.7-8 bar 4: CVMQ 5: KVQ 6: ICM P: Ampli cation factor Kp If the Kp value is reduced the regulation becomes slower. n03 Valve type n04 Kp factor I: Integration time Tn The I-setting can be cancelled by setting the value to max. (600s). If it is set to 600s, parameter n07 must be set to "0". (If the Tn value is increased the regulation becomes slower). n05 Tn sec. D: Di erentiation time Td The D-setting can be cancelled by setting the value to min. (0). n06 Td sec. Transient phenomenon n07 Q-ctrl. mode If the refrigeration requires a very fast transient phenomenon or must not have an underswing or temperature shift, this function can be used. (see page 4) 0: Ordinary regulating technique 1: Fast building-up where a minor underswing is allowed 2: Not quite so fast building-up, but without underswing OD - Opening degree Max. Limitation - ICM only When ICM has been selected (n03=6) the Maximum OD can be entered. ICM will never go above this value. (If n32=n33, ICM is forced to this value) n32 ICM OD Max. OD - Opening degree Min. Limitation - ICM only When ICM has been selected (n03=6) the Minimum OD can be entered. ICM will never go below this value. (If n32=n33, ICM is forced to this value) n33 ICM OD Min. Miscellaneous Output signal The controller can transmit a current signal via the analog output (terminal 2 and 5). Range of current signal can be selected below: If (017=Air) Sair will send out to the analog output. If (017=Au) Saux will send out to the analog output Sair/Saux min. value (0 or 4 mA) will correspond to the setting in "o27" Sair/Saux max. value (20 mA) will correspond to the setting in "o28" o09 AO type If ICM has been selected (n03=6) OD (u24) to control ICM, is send out to the analog output (o27) and (o28) is not active Range for current signal: 0: No output signal 1: 4-20 mA 2: 0-20 mA Input signal If you wish to connect a signal that is to displace the controller's control reference, the signal must be de ned in this menu. 0: No signal 1: 4-20 mA 2: 0-20 mA (4 or 0 mA will not give a displacement. 20 mA will displace the reference by the value set in menu r06). Data communication If the controller is built into a network with data communication, it must have an address, and the master gateway of the data communication must then know this address. These settings can only be made when a data communication module has been mounted in the controller and the installation of the data communication cable has been completed. This installation is mentioned in a separate document "RC8AC". The address is set between 1 and 60 The address is sent to the gateway when the menu is set in pos. ON (The setting will automatically change back to O after a few seconds.) Language This setting is only required if data communication is connected to the controller. Settings: 0=English, 1=German, 2=French, 3=Danish, 4=Spanish and 6=Swedish When the controller is operated via data communication, the texts in the right-hand column will be shown in the selected language. When you change the setting to an other language you must activate o04 before "the new language" can be visible from the AKM program. Frequency Set the net frequency. o10 AI type Following installation of a data communication module, the controller can be operated on a par with the other controllers in ADAPKOOL® refrigeration controls. o03 o04 o11 Language o12 50 / 60 Hz (50=0, 60=1) © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 6 User Guide | Media temperature controller, EKC 361 Selection of running display value If Sair (017=Air) will be shown as running display value. If lower button is activated Saux will be displayed for 5 sec, and then return to Sair Sair will send out to the analog output. See also (o09),(o27),(o28) If (017=Au) Saux will be shown as running display value. If lower button is activated Sair will be displayed for 5 sec, and then return to Saux Saux will send out to the analog output. See also (o09),(o27),(o28) If ICM has been selected (n03=6) If (017=Air) Sair (017=Air) will be shown as running display value. If lower button is activated OD (u24) will be displayed for 5 sec, and then return to Sair If (017=Au) OD (u24) will be shown as running display value. If lower button is activated Sair will be displayed for 5 sec, and then return to OD (u24) (Setting for the function o09) Set the temperature value where the output signal must be minimum (0 or 4 mA) (Setting for the function o09) Set the temperature value where the output signal must be maximum (20 mA). (With a temperature range of 50°C (di erential between the settings in o27 and o28) the dissolution will be better than 0.1 °C. With 100°C the dissolution wil be better than 0.2°C.) Service A number of controller values can be printed for use in a service situation Read the temperature at the Sair sensor (calibrated value) Read the control reference (Setpoint + any contribution from external signal) Read temperature at the Saux sensor (calibrated value) (This showing can also be uploaded from the normal display, if you push the lowermost button for almost a second) Read valve's actuator temperature Read reference for valve's actuator temperature Read value of external current signal Read value of transmitted current signal Read status of input DI (start/stop input) ICM opening degree. Only active if (n03)=6 Operating status Operating status of the controller can be called forth in the display. Push brie y (1s) the upper button. If there is a status code, it will be shown on the display. (Status codes have lower priority than alarm codes. In other words, you cannot see a status code, if there is an active alarm). The individual status codes have the following meanings: S10: Refrigeration stopped by the internal or external start/ stop S12: Refrigeration stopped due to low Sair o17 Display Aux/Air Aux =0 Air = 1 o27 Temp. at AO min. o28 Temp. at AO max. u01 Air temp. u02 Air reference u03 Aux. temp. u04 Actuator temp. u05 Actuator Ref. u06 AI mA u08 AO mA u10 DI u24 OD% -- DO1 Alarm Read status of alarm relay -- DO2 Cooling Read status of relay for solenoid valve -- DO3 Fan Read status of relay for fan EKC State (0 = regulation) 10 12 © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 7 User Guide | Media temperature controller, EKC 361 Operation Display The values will be shown with three digits, and with a setting you can determine whether the temperature is to be shown in °C or in °F. Light-emitting diodes (LED) on front panel There are LED's on the front panel which will light up when the corresponding relay is activated. The three lowest LED's will ash, if there is an error in the regulation. In this situation you can upload the error code on the display and cancel the alarm by giving the uppermost button a brief push. The controller can give the following messages: E1 Errors in the controller E7 E8 Error message E11 Cut-out Sair Short circuited Sair Valve's actuator temperature outside its range E12 Analog input signal is outside the range A1 Alarm message A2 High-temperature alarm Low-temperature alarm The buttons When you want to change a setting, the two buttons will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds - you will then enter the column with parameter codes. Find the parameter code you want to change and push the two buttons simultaneously. When you have changed the value, save the new value by once more pushing the two buttons simultaneously. Gives access to the menu (or cutout an alarm) Gives access to changes Saves a change Examples of operations Set set-point 1. Push the two buttons simultaneously 2. Push one of the buttons and select the new value 3. Push both buttons again to conclude the setting Set one of the other menus 1. Push the upper button until a parameter is shown 2. Push one of the buttons and nd the parameter you want to change 3. Push both buttons simultaneously until the parameter value is shown 4. Push one of the buttons and select the new value 5. Push both buttons again to conclude the setting © Danfoss | DCS (ADAP-KOOL®) | 2015-11 Menu survey Function Normal display Shows the temperature at the selected sensor At ICM valve OD also can be selected Reference Para- Min. meter SW =1.5x Fac. Max. setting - °C Set the required room temperature - -70°C 160°C 10°C Temperature unit r05 °C °F °C Input signal's temperature in uence r06 -50°C 50°C 0.0 Correction of the signal from Sair Correction of the signal from Saux Start/stop of refrigeration r09 -10,0°C 10,0°C 0.0 r10 -10,0°C 10,0°C 0.0 r12 OFF/0 On/1 On/1 Alarm Upper deviation (above the temperature setting) A01 0 50 K 5.0 Lower deviation (below the temperature setting) A02 0 Alarm's time delay A03 0 Regulating parameters 50 K 5.0 180 min 30 Actuator max. temperature n01 41°C 140°C 140 Actuator min. temperature n02 40°C 139°C 40 Actuator type (1=CVQ-1 to 5 bar, 2=CVQ 0 to 6 bar, 3=CVQ 1.7 to 8 bar, 4= CVMQ, 5=KVQ, 6= ICM) n03 1 6 2 P: Ampli cation factor Kp n04 0,5 50 3 I: Integration time Tn (600 = o ) n05 60 s 600 s 240 D: Di erentiation time Td (0 = o ) n06 0 s 60 s 10 Transient phenomenon 0: Ordinary control 1: Underswing minimised 2: No underswing OD - Opening degree - max. limit - ICM only OD - Opening degree min limit - ICM only Miscellaneous n07 0 2 2 n32 0% n33 0% 100% 100 100% 0 Controller's address (0-120) o03* 0 990 0 ON/OFF switch (service-pin message) o04* - - De ne output signal of analog output: 0: no signal, 1: 4 - 20 mA, 2: 0 - 20 mA o09 0 2 0 De ne input signal of analog input 0: no signal, 1: 4 - 20 mA, 2: 0 - 20 mA o10 0 2 0 Language (0=english, 1=German, 2=French, 3=Danish, 4=Spanish and 6=Swedish.)When you change the setting to an other language you must 011* activate o04 before "the new language" can be visible from the AKM program. Set supply voltage frequency o12 Select of running display value o17 0 50 Hz/0 Au/0 6 0 60 Hz/1 Air/1 0 Air/1 (Setting for the function o09) Set the temperature value where the output signal o27 must be minimum (0 or 4 mA) -70°C 160°C -35 (Setting for the function o09) Set the temperature value where the output signal o28 must be maximum (20 mA) -70°C 160°C 15 Service Read temperature at the Sair sensor u01 °C Read regulation reference u02 °C Read temperature at the Saux sensor u03 °C Read valve's actuator temperature u04 °C Read reference of the valve's actuator temperature u05 °C Read value of external current signal u06 mA Read value of transmitted current signal u08 mA Read status of input DI u10 on/o ICM opening degree. (only at ICM) u24 % *) This setting will only be possible if a data communication module has been installed in the controller. Factory setting If you need to return to the factory-set values, it can be done in this way: - Cut out the supply voltage to the controller - Keep both buttons depressed at the same time as you reconnect the supply voltage DKRCI.PS.RP0.B2.02 | 8 User Guide | Media temperature controller, EKC 361 Data Supply voltage Power consumption Input signal Sensor input Output signal Relay output Alarm relay 24 V a.c. +/-15% 50/60 Hz, 80 VA (the supply voltage is galvanically separated from the input and output signals) Controller Actuator 5 VA 75 VA Current signal 4-20 mA or 0-20 mA Digital input from external contact function 2 pcs. Pt 1000 ohm Current signal 4-20 mA or 0-20 mA Max. load: 200 ohm 2 pcs. SPST 1 pcs. SPST AC-1: 4 A (ohmic) AC-15: 3 A (inductive) Actuator Data communication Ambient temperature Enclosure Weight Mounting Display Terminals Input Temperature signal from sensor in the actuator Output Pulsating 24 V a.c. to actuator Possible to connect a data communication module During operation During transport -10 - 55°C -40 - 70°C IP 20 300 g DIN rail LED, 3 digits max. 2.5 mm2 multicore Approvals EU Low Voltage Directive and EMC demands re CE-marking complied with. LVD-tested acc. to EN 60730-1 and EN 607302-9 EMC-tested acc. to EN50081-1 and EN 50082-2 Capacitive load The relays cannot be used for the direct connection of capacitive loads such as LEDs and on/o control of EC motors. All loads with a switch mode power supply must be connected with a suitable contactor or similar. Ordering Type Function Code No. EKC 361 Evaporating pressure controller 084B7060 EKA 174 Data communication module (accessories), (RS 485 module) with galvanic separation 084B7124 Temperature sensor Pt 1000 ohm:..........Kindly refer to catalogue RK0YG... Valves: .............................................................DKRCI.PD.HT0.A Connections Necessary connections Terminals: 25-26 Supply voltage 24 V a.c. 17-18 Signal from actuator (from NTC) 23-24 Supply to actuator (to PTC) 20-21 Pt 1000 sensor at evaporator outlet 1-2 Switch function for start/stop of regulation. If a switch is not connected, terminals 1 and 2 must be short circuited. Application dependent connections Terminal: 12-13 Alarm relay There is connection between 12 and 13 in alarm situations and when the controller is dead 8-10 Relay switch for start/stop of fan 9-10 Relay switch for start/stop of solenoid valves 18-19 Current signal from other regulation (Ext.Ref.) 21-22 Pt 1000 sensor for monitoring 2-5 Current output for Sair/Saux temperature or ICAD actuator for ICM valve 3-4 Data communication Mount only, if a data communication module has been mounted. It is important that the installation of the data communication cable be done correctly. Cf. separate literature No. RC8AC.. Data communication CVQ/ CVMQ/ KVQ Wire length: See appendix 2 © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 9 User Guide | Media temperature controller, EKC 361 Data communication This page contains a description of a few of the possibilities you will have when the controller is provided with data communication. Examples If you want to know more about operation of controllers via PC, you may order additional literature. Each controller is provided with a plug-in module. The controllers are then connected to a two-core cable. The cable can be connected to a gateway type AKA 245. This gateway will now control the communication to and from the controllers. It will collect temperature values and it will receive alarms. When there is an alarm the alarm relay will be activated for two minutes The gateway can now be connected to a modem. When an alarm occurs from one of the controllers, the gateway will - via the modem - make a phone call to the service company. At the service company a modem, gateway and PC with system software type AKM have been installed. All the controllers' functions can now be operated from the various menu displays. The programme will for example upload all the collected temperature values once a day. Example of menu display · Measurements are shown at one side and settings at the other. · You will also be able to see the parameter names of the functions on page 5-7. Alarms If the controller is extended with data communication, it will be possible to de ne the importance of the transmitted alarms. The importance is de ned with the setting: 1, 2, 3 or 0. When the alarm then arises at some time, it will result in one of the following activities: 2 = Message The alarm text is transmitted with status value 2. Later, when the "message" lapses, the alarm text is retransmitted, but now with status value 0. 3 = Alarm As "1", but the master gateway's relay output is not activated. · With a simple change-over the values can also be shown in a trend diagram. · If you wish to check earlier temperature measurements, you can see them in the log collection. 1 = Alarm The alarm message is sent o with alarm status 1. This means that the gateway that is the master in the system will have its alarm relay output activated for two minutes. Later, when the alarm ceases, the alarm text will be retransmitted, but now with status value 0. 0 = Suppressed information The alarm text is stopped at the controller. It is transmitted nowhere. © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 10 User Guide | Media temperature controller, EKC 361 Appendix 1 Interaction between internal and external start/stop functions and active functions. Appendix 2 Cable length for the CVQ actuator The actuator must be supplied with 24 V a.c. ± 10%. To avoid excessive voltage loss in the cable to the actuator, use a thicker cable for large distances. Internal Start/stop External Start/stop Refrigeration Actuator Actuator temperature Fan relay Expansion valve relay Temperature monitoring Sensor monitoring O O On O On O O Stand-by "n02" O O No Yes On On On Regulating "n02" to "n01" On On Yes Yes Wire cross section Cable length Appendix 3 Connection between the evaporating temperature and the actuator's temperature (the values are approximate). n01: The highest regulated room temperature will have a belonging to value which in turn indicates the value of the n01 setting. Due to tolerances in the actuator, the setting value must be 10 K higher than shown in the curve. n02: The lowest occurring suction pressure will have a belonging to value which in turn indicates the value of the n02 setting. Due to tolerances in the actuator, the setting value must be 10 K lower than shown in the curve. CVMQ CVQ KVQ © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 11 User Guide | Media temperature controller, EKC 361 Start of controller When the electric wires have been connected to the controller, the following points have to be attended to before the regulation starts: 1. Switch o the external ON/OFF switch that starts and stops the regulation. 2. Follow the menu survey on page 7, and set the various para- meters to the required values. 3. Switch on the external ON/OFF switch, and regulation will start. 4. If the system has been tted with a thermostatic expansion valve, it must be set to minimum stable superheating. (If a speci c T0 is required for the adjustment of the expansion valve, the two setting values for the actuator temperature (n01 and n02) can be set to the belonging value while the adjustment of the expansion valve is carried out. Remember to reset the values). 5. Follow the actual room temperature on the display. (On terminals 2 and 5 a current signal can be transmitted which represents the room temperature. Connect a data collection unit, if applicable, so that the temperature performance can be followed). If the temperature uctuates When the refrigerating system has been made to work steadily, the controller's factory-set control parameters should in most cases provide a stable and relatively fast regulating system. If the system on the other hand oscillates, you must register the periods of oscillation and compare them with the set integration time Tn, and then make a couple of adjustments in the indicated parameters. If the time of oscillation is longer than the integration time: (Tp > Tn , (Tn is, say, 4 minutes)) 1. Increase Tn to 1.2 times Tp 2. Wait until the system is in balance again 3. If there is still oscillation, reduce Kp by, say, 20% 4. Wait until the system is in balance 5. If it continues to oscillate, repeat 3 and 4 If the time of oscillation is shorter than the integration time: (Tp < Tn , (Tn is, say, 4 minutes)) 1. Reduce Kp by, say, 20% of the scale reading 2. Wait until the system is in balance 3. If it continues to oscillate, repeat 1 and 2 Trouble shooting - ICS/PM with CVQ In addition to the error messages transmitted by the controller, the table below may help identifying errors and defects. Symptom Media temperature too low. Actuator feels cold. Defect Short-circuited NTC resistor in actuator. Defective PTC resistor (heating element) in actuator. Media temperature too low. Actuator fells warm. Undersized cable to CVQ. Undersized 24 V transformer. Media temperature too high. Actuator feels cold. Media temperature too high. Actuator feels warm. Loss of charge in actuator. Fault in refrigerant plant. Cut out NTC resistor in actuator. Con rmation of defect If less than 100 ohm is measured across terminals 17 and 18 (disassemble the lead), the NTC or the leads are short-circuited. Check the leads. If more than 30 ohm or 0 ohm is measured across terminal 23 and 24 (disassemble the lead), either the PTC or the leads are defective. Check the leads. Measure voltage across terminals 77 and 78 (min. 18 V a.c.). Measure resistance in power cables to CVQ (max. 2 ohm) Measure voltage across transformer output terminals (24 V a.c. +10/ -15%) under all working conditions. If voltage drops under some working conditions the transformer is undersized. Replace actuator. Examine plant for ther defects. If more than 200 kohm is measured across terminals 17 and 18 (disassemble the lead), either the NTC or leads are disconnected. Check the leads. © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 12 User Guide | Media temperature controller, EKC 361 Fine adjustments When the system has been operating for a while, it may be required for some systems to optimise some of the adjustments. Below we have a look at settings having an in uence on the speed and accuracy of the regulation. Adjustment of the actuator's min. and max. temperatures At the rst setting these values were set to 10 K outside of the expected temperature in order to eliminate the tolerances in the actuator. By adjusting the two values to the values where the valve is exactly in mesh, the valve will all the time remain active in its regulation. If the actuator is replaced at a later date, this procedure must be repeated for the new actuator. Min. By adjusting the actuator's min. temperature you obtain a limit for how low a pressure can occur in the evaporator (the point is where the valve starts a limitation of the refrigerant ow). The system must be put in an operating situation where max. capacity is called for (large refrigeration need). The min. temperature must now be changed upwards step by step, at the same time as the evaporating pressure is read on the system's manometer. When a change of the evaporating pressure is registered, this is the point where the valve is exactly in mesh. (If frost protection is required for the system, the value can be raised to the belonging value). Max. By adjusting the actuator's max. temperature you obtain a limit for how high a pressure can occur in the evaporator (the refrigerant ow is blocked completely). The system is put in an operating situation where there is no call for refrigeration capacity (no refrigerant ow). The max. temperature is now changed downwards step by step, at the same time as the evaporating pressure is read on the system's manometer. When a change of the evaporating pressure is registered, this is the point where the valve opens. Adjust the setting a little upwards, so that the valve will again close completely for the refrigerant ow. (If the actual application has a requirement regarding max. evaporating pressure, a lower setting may of course be selected, so that the pressure is limited). Method for xing Kp, Tn and Td Described below is a method (Ziegler-Nichols) for xing Kp, Tn and Td. 1. The system is made to regulate the temperature at the required reference with a typical load. It is important that the valve regulates, and that it is not fully open. 2. Parameter u05 is read. The actuator's min. and max. setting is adjusted, so that the average of the min. and max. values is equal to the read u05. 3. The controller is set, so that it will regulate as a P-controller. (Td is set to 0, Tn in pos. OFF (600), and Q-Ctrl.mode is set at 0). 4. The stability of the system is examined by stopping the system for, say, one minute (using the start/stop setting or the switch). Now check how the building-up of the temperature proceeds. If the building-up peters out, raise Kp a little and repeat the start/stop operation. Continue with this until you obtain a building-up which does not peter out. 5. Kp is in this case the critical ampli cation (Kpcritical) and the building-up time for the continued oscillation is the critical buildingup time (Tcritical). 6. Based on these values, the regulating parameters can now be calculated and subsequently set: · If PID regulation is required: Kp < 0.6x Kpcritical Tn > 0.5x Tcritical Td < 0.12x Tcritical · If PI regulation is required: Kp < 0.45x Kpcritical Tn > 0.85x Tcritical 7. Reset the values for the controller's min. and max. temperatures and Q-Ctrl.mode. © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 13 User Guide | Media temperature controller, EKC 361 © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 14 User Guide | Media temperature controller, EKC 361 © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 15 User Guide | Media temperature controller, EKC 361 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in speci cations already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. © Danfoss | DCS (ADAP-KOOL®) | 2015-11 DKRCI.PS.RP0.B2.02 | 16Danfoss A/S GPL Ghostscript 9.55.0