DMeXit Emergency Controller

Installation Guide

OVERVIEW
The Pathway DMeXit is a UL924 certified controller designed to send a control signal to DMX lighting in emergencies to satisfy minimum luminance levels for egress lighting. DMeXit may be triggered using a wet or dry contact closure from other building management systems, or the integrated phase loss detection device. Upon trigger, a user-recordable snapshot of a single universe DMX will be transmitted to four separate data runs. The outputs are optically isolated to ensure maximum reliability and are fully RDM compliant so that your entertainment console or architectural controller still has maximum flexibility when it comes to commissioning and monitoring your system during normal operation. There are multiple options for restoring normal operation after conditions have been cleared, including user programmable time delays, sensing of valid input signal from the normal controller or a remote restore button for facilities or stage managers.
IMPORTANT SAFEGUARDS
1. All servicing should be performed by qualified service personal. 2. When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS. a. Do not use outdoors. b. Do not mount near gas or electric heaters. c. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel. d. The use of accessory equipment not recommend by the manufacturer may cause an unsafe condition. e. Do not use this equipment for other than its intended use. 3. The Emergency Circuits for this panel, must be fed from a UPS, generator, or other guaranteed source of power during emergency and power outage situations. 4. CAUTION - This equipment may be fed by more than one power supply source. To reduce the risk of electric shock, both normal and emergency sources feeding this unit should de-energized before servicing any equipment connected inside the marked high voltage compartments. 5. Pathway assumes no responsibility for claims arising out of improper or careless installation or handling of this product. Failure to follow any of these instructions could void product warranty.
Always read complete installation instructions prior to installation!
SAVE THESE INSTRUCTIONS

STATUS INDICATORS

External Indicators

PWR - Green

Green. Steady glow indicates emergency power source is OK; off indicates no emergency power source. If all LEDs are off, check that the module
is receiving power.

DMX Amber

Steady glow indicates active DMX source is present.

EM - Red

Red. Not lit when system in is normal mode. Flashes red when Emergency mode has been activated. Solid red when emergency condition has cleared and system restore is pending
timeout or user intervention.

Internal Indicators

Processor

Green. Steady glow indicates that board is working. Off when in Emergency mode.

Record Custom Green. Steady glow only if a custom snapshot

Snapshot

has been recorded.

Optional PWACC EMRR Remote Restore

Green

System is in normal operation.

Red - Flashing

System in in emergency mode.

Red - Solid

System is ready to be restored to normal operation.

Red/Green Flashing

System is set to automatically restore without the use of the EMRR Button.

BUTTONS

Test

External
Press for a 30s test of emergency snapshot.

RECORD CUSTOM SNAPSHOT
DEFAULT SNAPSHOT

Internal
Press and hold for three seconds to save incoming DMX signal. LED will illuminate.
Press and hold for 10 seconds to restore snapshot to default with all levels to full. Custom Snapshot LED will blink and go out.

Part No. 912-00431-001 March 16, 2023

Page 1

DMeXit Emergency Controller

Installation Guide

WALL MOUNT INSTALLATION INSTRUCTION

MOUNTING

LOW VOLTAGE CONNECTIONS

PWEMDMX WM is designed for indoor use in a dry location. Mount the DMX IN is wired to the control console output or enclosure to the wall with appropriate fasteners. Run conduit into the to another DMX source. Follow connector, cable,

box through the side or top knockouts provided. Low voltage knock- and pinouts specifed below.

outs are marked yellow; ensure that line voltage wiring is kept inside DMX OUT connectors are wired to the remote

the barriered power supply section.

DMX devices/RDM responders.

LINE VOLTAGE CONNECTIONS
PS50X MVOLT is wired to the single phase emergency power source in the top left section. Labeled terminations for two 6 to 20 AWG solid or stranded power wires. One grounding lug for 6 to 14 AWG solid or stranded ground wire. PLD OPTION is wired to normal power source in the top right section with labeled terminations for 12 to 20 AWG solid or stranded. Please refer to PLD wiring diagram details. One grounding lug for 6 to 14 AWG solid or stranded ground wire.

Remote Restore connector is wired to the optional PWACC EMRR using the V+ & V- terminals. CCI connector is wired to user provided contact closure for Emergency Activation or to the factory installed Phase Loss Detector
WARNING: DMX input/output ports must be connected to low-voltage data lines only. Do not connect DMX ports to high voltage sources.

347V Step Down Transformer is an option to power the system from

347 volts AC. Use a wirenut to connect a single phase to the red con-

nector on the transformer. The yellow wire will be connected to the

internal power supply.

Emergency Power
Knockouts

Normal Power Knockouts

Emergency Power
Knockout

#6 to 14 AWG solid or stranded
ground wire

#6 to 14 AWG solid or stranded
ground wire

1-3Ø #12 to 22 AWG 1Ø #6 to 20 AWG solid or stranded solid or stranded

Normal Power Knockout

High Voltage Normal Power High Voltage Emegency Power

Mounting Keyholes
12.00" [305 mm]

Low Voltage

Normal Power Phase Loss
Detection Device (PLD option) with 2 NO/NC contact inputs Single NO wet/dry
contact closure input (CCI option)
CSC connector 2-Wire
Remote Restore (PWACC EMRR) CSC connector

Low Voltage Knockouts
Part No. 912-00431-001 March 16, 2023

Cable Tie Lances

DMX/RDM DMR/RDM

IN

OUT (4)

IDC connector IDC connector

Mounting Keyholes 12.75"
[324 mm]

Low Voltage Knockouts

© 2023 Acuity Brands, Inc. · One Lithonia Way, Conyers GA 30012 Pathway Connectivity | Phone: + 1 866 617 3074 www.pathwayconnect.com
Page 2

DMeXit Emergency Controller

Installation Guide

FLUSH MOUNT INSTALLATION INSTRUCTION

MOUNTING
PWEMDMX FM is designed for indoor use in a dry location. Mount the enclosure between studs that are 16" on center. The lances on the side of the unit help guide placement appropriate for 1/2 drywall. Use two screws through the unthreaded holes on each side for fastening to studs. Do not use the three threaded holes. Run conduit into the box through the top or bottom knockouts provided. Low voltage knockouts are marked yellow; ensure that line voltage wiring is kept inside the barriered power supply section.
LINE VOLTAGE CONNECTIONS
PS50X MVOLT is wired to the single phase emergency power source. Labeled terminations for two 6 to 20 AWG solid or stranded power wires. One grounding lug for 6 to 14 AWG solid or stranded ground wire. PLD OPTION is wired to normal power source in the top right section with labeled terminations for 12 to 20 AWG solid or stranded. Please refer to PLD wiring diagram details. One grounding lug for 6 to 14 AWG solid or stranded ground wire. 347V Step Down Transformer is a selectable option to power system from 347 volts AC. Use a wirenut to connect a single phase to the red connector on the transformer. The yellow wire will be connected to the internal power supply.

LOW VOLTAGE CONNECTIONS
DMX IN is wired to the control console output or to another DMX source. Follow connector, cable, and pinouts specifed below. DMX OUT connectors are wired to the remote DMX devices/RDM responders. Remote Restore connector is wired to the optional PWACC EMRR using the V+ & V- terminals. CCI connector is wired to user provided contact closure for Emergency Activation or to the factory installed Phase Loss Detector
WARNING: DMX input/output ports must be connected to low-voltage data lines only. Do not connect DMX ports to high voltage sources.

Drywall depth guide

High Voltage Emegency Power

#6 to 14 AWG solid or stranded 1Ø #6 to 20 AWG
ground wire solid or stranded
PLD intentionally not shown
Single NO wet/dry
contact closure input (CCI option)
CSC connector

Emergency Power
Knockout
16.25" [413 mm]

Low Voltage

Fastening holes

1/2" Drywall

14.25" [362 mm]

Cable Tie Lances

DMX/RDM DMR/RDM

IN

OUT (4)

IDC connector IDC connector

2-Wire Remote Restore (PWACC EMRR) CSC connector

Low Voltage Knockout

16" center metal or wood studs

Low Voltage Knockout

Part No. 912-00431-001 March 16, 2023

© 2023 Acuity Brands, Inc. · One Lithonia Way, Conyers GA 30012 Pathway Connectivity | Phone: + 1 866 617 3074 www.pathwayconnect.com
Page 3

DMeXit Emergency Controller

Installation Guide

RACK MOUNT INSTALLATION INSTRUCTION

MOUNTING

LOW VOLTAGE CONNECTIONS

PWEMDMX RM is designed for installing in a standard 19" equipment rack for indoor use in a dry location. Fasten the rack ears with the supplied hardware and mount the enclosure using 4 appropriate fasteners. This unit requires 8 RU. Run conduit into the the rear of the enclosure through the knockouts provided. Low voltage knockouts are marked yellow; ensure that line voltage wiring is kept inside the barriered power supply section.
LINE VOLTAGE CONNECTIONS
PS50X MVOLT is wired to the single phase emergency power source. Labeled terminations for two 6 to 20 AWG solid or stranded power wires. One grounding lug for 6 to 14 AWG solid or stranded ground wire. PLD OPTION is wired to normal power source in the top right section with labeled terminations for 12 to 22 AWG solid or stranded. Please refer to PLD wiring diagram details. One grounding lug for 6 to 14 AWG solid or stranded ground wire. 347V Step Down Transformer is a selectable option to power system from 347 volts AC. Use a wirenut to connect a single phase to the red connector on the transformer. The yellow wire will be connected to the internal power supply.

DMX IN is wired to the control console output or to another DMX source. Follow connector, cable, and pinouts specifed below. DMX OUT connectors are wired to the remote DMX devices/RDM responders. Remote Restore connector is wired to the optional PWACC EMRR using the V+ & V- terminals. CCI connector is wired to user provided contact closure for Emergency Activation or to the factory installed Phase Loss Detector
WARNING: DMX input/output ports must be connected to low-voltage data lines only. Do not connect DMX ports to high voltage sources.

Rack Screws

#6 to 14 AWG solid or stranded
ground wire

1-3Ø #12 to 22 AWG solid or stranded

Emergency Power
Knockouts

1Ø #6 to 20 AWG solid or stranded

Normal #6 to 14 AWG Power solid or stranded Knockouts ground wire

High Voltage Normal Power High Voltage Emegency Power

14.00" [356 mm]
8 RU

Low Voltage

Normal Power Phase Loss
Detection Device (PLD option) with 2 NO/NC contact inputs Single NO wet/dry
contact closure input (CCI option)
CSC connector 2-Wire
Remote Restore (PWACC EMRR) CSC connector

Cable Tie Lances
Low Voltage Knockouts

DMX/RDM DMR/RDM

IN

OUT (4)

IDC connector IDC connector

© 2023 Acuity Brands, Inc. · One Lithonia Way, Conyers GA 30012 Pathway Connectivity | Phone: + 1 866 617 3074 www.pathwayconnect.com

Part No. 912-00431-001 March 16, 2023

Page 4

DMeXit Emergency Controller

NORMAL POWER

PLD WIRING DETAILS

Installation Guide

LIINE NEUTRAL
Single Phase Wiring Detail

TO ADDITIONAL NORMAL POWERED
LUMINAIRES
LUMINAIRE LUMINAIRE LUMINAIRE

Phase Sense Circuits A~ B~ C~ Neutral

800.535.2465 LME-924

Phase Sense 120-277 VAC Max Input Current 3mA 50/60 Hz 1Ø - 3Ø

E71446

EM COM EM SW
24VDC IN COMMON

FACTORY INSTALLED WIRES
AUX #1 CCI AUX #2 CCI

Protect AC sense leads with 20A max fuse(s) and/or circuit breaker(s)

1Ø #12 to 22 AWG

AUX IN

SOLID OR STRANDED

NO/NC TEST

STATUS

LINE JUMPED TO ALL PHASES CONFIG BUTTON INDICATORS

NORMAL POWER

PHASE A PHASE B PHASE C NEUTRAL
Three Phase Wiring Detail

TO ADDITIONAL NORMAL POWERED
LUMINAIRES

LUMINAIRE LUMINAIRE LUMINAIRE

800.535.2465 LME-924

Phase Sense 120-277 VAC Max Input Current 3mA 50/60 Hz 1Ø - 3Ø

E71446

EM COM EM SW
24VDC IN COMMON

FACTORY INSTALLED WIRES
AUX #1 CCI AUX #2 CCI

Phase Sense Circuits A~ B~ C~ Neutral

Protect AC sense leads with 20A max fuse(s) and/or circuit breaker(s)

Part No. 912-00431-001 March 16, 2023

3Ø #12 to 22 AWG SOLID OR STRANDED

AUX IN

NO/NC TEST

STATUS

CONFIG BUTTON INDICATORS

© 2023 Acuity Brands, Inc. · One Lithonia Way, Conyers GA 30012 Pathway Connectivity | Phone: + 1 866 617 3074 www.pathwayconnect.com

Page 5

DMeXit Emergency Controller

Installation Guide

PLD WIRING DETAILS
Auxiliary Contacts from Fire Alarm Control Panels, Security Systems, or a remote test switch may trigger emergency mode if connected using the auxiliary contact closure input terminals on the LME 924. Dry contact relays or maintained switches may be used. Consult equipment manuals to verify auxiliary switches are dry contacts and maintained when active. When contact is made by the auxiliary equipment the LME 924 will trigger emergency mode and hold that mode until the contact(s) opens and the Restore time of how you have DIP switches 5,6, &7 set expires. For example if the LME 924 opens the contacts and your Restore Time is set to Factory Default of 10 seconds, it will take an additional 10 seconds before it returns to DMX pass-thru rather than emergency. There are (2) auxiliary contacts on the LME 924 which share equal priority. When EITHER auxiliary contact is closed emergency mode will be triggered. If your system is equiped with a PLD do not use parallel connections from an auxiliary source to the CCI connection on the electronics, wire them to the auxiliary connection on the LME 924.

800.535.2465 LME-924

Phase Sense 120-277 VAC Max Input Current 3mA 50/60 Hz 1Ø - 3Ø

E71446

EM COM EM SW 24VDC IN COMMON

DRY CONTACT
ONLY

Phase Sense Circuits A~ B~ C~ Neutral

Protect AC sense leads with 20A max fuse(s) and/or circuit breaker(s)

AUXILIARY CONTROL EQUIPMENT
Notes: 1. All wiring to dry contact closures is Class 2 2. Auxiliary dry contacts must be maintained

DIP SWITCH SETTINGS

IN #1 TYPE IN #2 TYPE

12

NORMALLY CLOSED NORMALLY CLOSED

ON

IN #1 TYPE IN #2 TYPE

12

NORMALLY OPEN NORMALLY OPEN

ON

IN #1 TYPE IN #2 TYPE

12

NORMALLY CLOSED NORMALLY OPEN

Auxiliary equipment may use maintained normally closed or maintained normally open contacts. The DIP switches on the LME 924 select whether the Aux 1 or Aux 2 inputs are normally open or closed. Use the chart at left to configure appropriately

ON

IN #1 TYPE IN #2 TYPE

12

NORMALLY OPEN NORMALLY CLOSED

ON

Test Button
Press to activate emergency look, it will last for 30s. + Restore mode as determined by DIP switches 5,6,& 7.
Press and hold for 3s to end test + Restore mode as determined by DIP switches 5,6,& 7.

EM Status Aux In #1 Aux In #2 Phase Power Test Mode

LED Status Summary

Red Green Green Green Green

ON - When emergency is active OFF - no emergency
Solid - When active (maintained) Off - aux input not maintained
Solid - When active (maintained) Off - aux input not maintained
On - when phase power is detected Off - when phase power is low*
Blink - Flashes when test is active Off - in normal mode
* Line voltage may still be present, but too low.

© 2023 Acuity Brands, Inc. · One Lithonia Way, Conyers GA 30012 Pathway Connectivity | Phone: + 1 866 617 3074 www.pathwayconnect.com

Part No. 912-00431-001 March 16, 2023

Page 6

DMeXit Emergency Controller

Installation Guide

PWACC EMRR INSTALLATION INSTRUCTION

MOUNTING
PWACC EMRR is designed for indoor use in a dry location, typically mounted in a single gang standard backbox. Mount the push button in a location that is accessible to restore the system from Emergency to Normal mode by qualified personnel. Run two-conductor wire from the back of the button to the Remote Restore terminal block. Wire may be twisted or non-twisted pair, 12-24 AWG not to exceed 300ft. DIP switches 5,6,& 7 must all be set to the ON position when using the EMRR.

LOW VOLTAGE CONNECTIONS
Remote Restore connector is wired to the optional PWACC EMRR using the V+ & V- terminals. Steady Green LED
Normal Operation Flashing Red LED
Emergency Operation Solid Red LED
Pending Restore
If during normal operation you have a steady Red LED your V+ & V- are reversed and need to be swapped.

If LED is continually flashing red and green, DIP switches 5,6, & 7 have not been set to ON.

WARNING:Remote Restore must be connected to low-voltage data wire. Do not connect Remote Restore to high voltage sources.

1.31" [33mm]

LIGHTING SYSTEM RESTORE

4" [103mm]

Green - Normal Flashing Red - EMG
Press to restore
ALL FAULTS MUST BE CLEARED

1.7" [43mm]

1.33" [38mm]

3.8"

2.63"

[97mm] [67mm]

4.5" [114mm]

2.75" [70mm]
PWFP G1 1 Gang

Part No. 912-00431-001 March 16, 2023

© 2023 Acuity Brands, Inc. · One Lithonia Way, Conyers GA 30012 Pathway Connectivity | Phone: + 1 866 617 3074 www.pathwayconnect.com
Page 7

DMeXit Emergency Controller

Installation Guide

DMX SPEED - DIP Switch 1 & 2

Restore Time - DIP Switch 5,6,7

ON

ON

12

MAXIMUM

1 SECOND

56 7

ON

12

FAST

ON

12

MEDIUM
*
SLOW

ON

12

2 3 42 3 4

CONTACT - DIP Switch 3

DRY CONTACT

ON



WET CONTACT

ON



Restore Mode - DIP Switch 4

DEFAULT

ON

*

5 SECONDS
*
10 SECONDS 30 SECONDS
1 MINUTE 5 MINUTES

56 7

56 7

ON 56 7

56 7

ON

ON

ON

ON

56 7

3 4 53 4 5

ON 56 7

ON

DMX REQUIRED
Trigger - DIP Switch 8
*
CCI ONLY CCI OR NO DMX IN

ON 78

ON 78

ON 56 7

10 MINUTES
REMOTE RESTORE
Example DIP switch setup for slow DMX speed, wet contact, 10 second restore time, and CCI only to trigger Emergency mode.

ON 1 2 3 45 678

* - FACTORY DEFAULT  - FACTORY DEFAULT WITHOUT PLD  - FACTORY DEFAULT WITH PLD
Part No. 912-00431-001 March 16, 2023

SLOW WET DMX
10 SECOND CCI ONLY
Note: Black is where the DIP switch position should be. On is to the right.
© 2023 Acuity Brands, Inc. · One Lithonia Way, Conyers GA 30012 Pathway Connectivity | Phone: + 1 866 617 3074 www.pathwayconnect.com
Page 8

DMeXit Emergency Controller

Installation Guide

In permanent installations, DMX512-A cables may be either one of two basic cable types: cables specified for use with EIA-485/EIA-485-A or EIA-422, and cables specified as EIA/TIA568 Category 5 or higher. Category cable meeting the requirements of a category higher than Category 5 is permissible. For DMeXit installations, we recommend Category cable and the supplied Insulation Displacement Contact (IDC) connectors.

ISO/IEC Category 5 Cables Use Insulation Displacement Contact Connectors

RJ45 T-568B 1 2 3 4 5 6 7 8
Shell

Wire Color White Orange
Orange White Green
Blue White Blue
Green White Brown
Brown Bare Silver

Function Data + (true) Data ­ (complement) Not Assigned Not Assigned Not Assigned Not Assigned Data Common Not Assigned Not Assigned

Pathway IDC 3 2

XLR5 Equivalent Pin 3 Pin 2

1 Not Connected

Pin 1 Shell

Pathway Connectivity recommends you download and follow ANSI E1.27-2: Standard Wiring Practice for Permanently Installed Control Cables for Use with ANSI E1.11 DMX512-A available at https://tsp.esta.org/tsp/documents/published_docs.php.

Here are some additional notes abbreviated from the ANSI Standard. · Shields and drain wires exposed by the process of preparing the cable for termination should be insulated from accidental contact with
earth ground, data +, data - and data common. · Under no circumstance should any cable conductor or shield be connected to earth ground · Direct termination of a permanently installed cable on a male RJ-45 should not be allowed.

If using stranded twisted pair cables, you must use PWCON SPARE CSC3. See Pathway Accessories, Inserts and Spare Connectors table below for ordering information.

EIA-485 type cables (i.e., Belden, Proplex, etc) Use Compression Screw Connectors

XLR5 Pin

Wire

Function

Pathway CSC

Pin 1

Shield

Data Common

1 (black)

Pin 2

Pair 1

Data ­ (complement)

2 (green)

Pin 3

Pair 1

Data + (true)

3 (red)

Pin 4

n/a

Not Assigned

Pin 5

n/a

Not Assigned

Shell

Not Connected

Not Connected

Pathway Connectivity offers many `last mile' solutions for permanently installed cable plants. Listed below are just a few of the most popular products. Search our website for a complete listing of the following series: PWACC RJ45 Patch, PWCON Connector, PWINS Data Receptacles.

PWACC RJPATCH Q4 PWINS RJ45EC PD
PWINS RJ45EC RJ45R PWINS XLR5F IDC5 PWINS XLR5M IDC5
PWCON SPARE CSC3 Q4 PWCON SPARE IDC3 Q4 PWCON SPARE CSC5 Q4 PWCON SPARE IDC5 Q4

Pathway Accessories, Inserts and Spare Connectors Pathway Accessories, DIN RJ45 patch (3.5" of rail for 4), Qty (4) Insert, RJ45 EtherCON, Punch Down Insert, RJ45 EtherCON, RJ45 Female (Rear)
Insert, XLR 5-Pin Female, 5-Pin Insulation Displacement Contact Connector Insert, XLR 5-Pin Male, 5-Pin Insulation Displacement Contact Connector Connectors, Spare, 3-Pin Compression Screw Connector, Qty(4)
Connectors, Spare, 3-Pin Insulation Displacement Contact Connector, Qty (4) Connectors, Spare, 5-Pin Compression Screw Connector, Qty(4)
Connectors, Spare, 5-Pin Insulation Displacement Contact Connector, Qty (4)

Part No. 912-00431-001 March 16, 2023

© 2023 Acuity Brands, Inc. · One Lithonia Way, Conyers GA 30012 Pathway Connectivity | Phone: + 1 866 617 3074 www.pathwayconnect.com
Page 9



References

Adobe PDF Library 17.0 Adobe InDesign 18.1 (Windows)