CASPIAN SKYLINE CEILING 008
Caspian Skyline®
Education | Healthcare | Leisure and sport | Office | Hospitality | Retail | Showroom

Caspian Skyline CT60 fits into a 600mm x 600mm ceiling tile, providing easy access for both installation and maintenance. It's suitable for projects in schools, retail or food units or where the heating needs to complement the rest of the premise
The Caspian Skyline has been developed to provide a more easily installed ceiling tile fan convector to complement the Smith's range of Caspian commercial fan convectors and may be used alone or in tandem with other Smith's products
Plumbing easily into any wet central heating system, the Caspian Skyline will also work effectively and efficiently with renewable heat sources, such as air or ground source heat pumps
Available with Smart Control

Product Information
Motor EC (BMS compliant).
Finish Casing: galvanised steel 1.2mm. Grille: Eggcrate core, white RAL 9010 complete with touch catches.
Filter Class G2, 100% polyester, non-washable.
Installation Suitable for two-pipe central heating systems. Maximum installation height ­ 4m to underside. Unit must be earthed.
Commissioning Check water is hot enough to activate the low temperature cut-out thermostat.
Controls See accessories table.
Specification To specify state: Ceiling mounted Fan Convector with EC motor, in 1.2mm galvanised steel, egg crate core grille in white RAL 9010. To fit a standard 600mm x 600mm ceiling grid. With variable heat output controller. As Smith's Caspian Skyline CT60.

As part our commitment to continuous improvement Smith's Environmental Products may change the specifications of its products without prior notification or public announcement. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All dimensions are in mm unless otherwise stated. Please visit our website for the most up to date information.

Issue 008 | January 2025

+44 (0) 1245 324 900 | sales@smithsep.co.uk | SmithsEP.co.uk

Technical Data

Heat output

Model CASPIAN SKYLINE CT60

Heat Output at 80°

Low Medium High (kW) (kW) (kW)

3.1

4.1

5.1

Heat Output at 75°

Low Medium High (kW) (kW) (kW)

2.7

3.7

4.6

Heat Output at 70°

Low Medium High (kW) (kW) (kW)

2.3

3.2

4.1

Heat Output at 65°

Low Medium High (kW) (kW) (kW)

2.3

2.9

3.6

Heat Output at 60°

Low Medium High (kW) (kW) (kW)

2.2

2.6

3.1

Model CASPIAN SKYLINE CT60

Heat Output at 55°

Low Medium High

(kW)

(kW) (kW)

1.5

2.0

2.6

Heat Output at 50°

Low Medium High

(kW)

(kW) (kW)

0.8

1.4

2.1

Heat Output at 45°

Low Medium High

(kW)

(kW) (kW)

0.5

0.9

1.3

Heat Output at 40°

Low Medium High

(kW)

(kW) (kW)

0.2

0.4

0.5

Model CASPIAN SKYLINE CT60

Flow & return connections
22mm

Fused spur
3A

Low (Watts)
8

Total Power Consumption

Medium (Watts)

High (Watts)

Water Capacity (Litres)

24

40

0.75

High (dBA)
48

Sound Levels
Medium (dBA)
40

Low (dBA)
34

Heat output testing based on BS EN442 using mean water temperature, 18°C entering air temperature, 10° temperature drop. Sound levels measured at 3m.

Correction factors

EAT°C 15 21

Mean water temperature °C 80 to 40 1.10 0.93

Factor

Temperature drop °C

20

15

10

5

0.89

0.95

1.00

1.04

Grille colour
white

As part our commitment to continuous improvement Smith's Environmental Products may change the specifications of its products without prior notification or public announcement. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All dimensions are in mm unless otherwise stated. Please visit our website for the most up to date information.

Issue 008 | January 2025

+44 (0) 1245 324 900 | sales@smithsep.co.uk | SmithsEP.co.uk

Ordering Guide

Model CASPIAN SKYLINE CT60 EC

Packed Wt (kg)
20

Product Codes
HPCA29001

Accessories CASPIAN ADJUSTABLE LOW TEMPERATURE CUT-OUT CASPIAN EXTERNAL CONTROL HARNESS (EC) CASPIAN SKYLINE CT60 PROPORTIONAL HEAT OUTPUT CONTROLLER 15-25 (REMOTE SENSOR) CASPIAN SKYLINE CT60 PROPORTIONAL HEAT OUTPUT CONTROLLER 11-21 (REMOTE SENSOR) ROOM THERMOSTAT HARD WIRED ROOM THERMOSTAT TAMPER PROOF FLEXIBLE HOSES 22MM PAIR CASPIAN REMOTE SWITCHING ON/OFF RELAY (24V AC COIL) BLANK CONFIGURABLE PROPORTIONAL HEAT OUTPUT CONTROLLER (PROGRAMMED AT FACTORY) CASPIAN EC LINKING KIT (MASTER/SLAVE)

Product Codes HACA33001 HACA33004 HACA33125 HACA33123 HAGA95001 HAGA95004 HAGA95003 HACA33127 HACA33126 HACA33068

Dimensions

215 275

45 65

Heater unit 204

110
595 570 Hanging centres

563 500 Hanging centres

Grille 538

50 55

595

595

538

As part our commitment to continuous improvement Smith's Environmental Products may change the specifications of its products without prior notification or public announcement. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and shall not form part of any contract. All dimensions are in mm unless otherwise stated. Please visit our website for the most up to date information.

Issue 008 | January 2025

+44 (0) 1245 324 900 | sales@smithsep.co.uk | SmithsEP.co.uk

