Instruction Manual for MEAN WELL models including: 2400W, Power Supply, Single Output, RSP-2400 series, MW, MEAN WELL
REMOTE SENSE. Compensate voltage drop on the load wiring up to 0.25V. Please refer to the Function Manual. Parameter. Parameter. ESD. Radiated. EFT / Burst.
27 ago 2021 —
File Info : application/pdf, 10 Pages, 1.21MB
DocumentDocument2400W Power Supply with Single Output RSP-2400 series CNS14336-1 UL62368-1 Bauar t gepruft Sicherheit egelma ge od o s be wac g www. tuv.com ID 2000000000 EN62368-1 TPTC004 IEC62368-1 File Name:RSP-2400-SPEC 2020-09-29 2400W Power Supply with Single Output RSP-2400 series SPECIFICATION MODEL RSP-2400-12 RSP-2400-24 RSP-2400-48 DC VOLTAGE RATED CURRENT CURRENT RANGE 12V 166.7A 0 ~ 166.7A 24V 100A 0 ~ 100A 48V 50A 0 ~ 50A RATED POWER 2000.4W 2400W 2400W RIPPLE & NOISE (max.) Note.2 150mVp-p 150mVp-p 200mVp-p OUTPUT VOLTAGE ADJ. RANGE 10.8 ~ 13.2V VOLTAGE TOLERANCE Note.3 ±1.0% LINE REGULATION ±0.5% LOAD REGULATION ±0.5% 22 ~ 28V ±1.0% ±0.5% ±0.5% 43 ~ 56V ±1.0% ±0.5% ±0.5% SETUP, RISE TIME 1000ms, 80ms at full load HOLD UP TIME (Typ.) 12ms at full load VOLTAGE RANGE 180 ~ 264VAC 254 ~ 370VDC FREQUENCY RANGE 47 ~ 63Hz INPUT POWER FACTOR (Typ.) EFFICIENCY (Typ.) 0.95/230VAC at full load 88% 90.5% 91.5% AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 15.5A/180VAC 60A/230VAC 12A/230VAC LEAKAGE CURRENT <2.0mA / 240VAC OVERLOAD (OLP) 100 ~ 112% rated output power User adjustable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover PROTECTION OVER VOLTAGE OVER TEMPERATURE OUTPUT VOLTAGE PROGRAMMABLE(PV) 13.8 ~ 16.8V 28.8 ~ 33.6V Protection type : Shut down o/p voltage, re-power on to recover Shut down o/p voltage, recovers automatically after temperature goes down 2.4 ~ 13.2V 4.8 ~ 28V Please refer to the Function Manual. 57.6 ~ 67.2V 9.6 ~ 56V CURRENT SHARING FUNCTION AUXILIARY POWER REMOTE ON-OFF CONTROL REMOTE SENSE ALARM SIGNAL OUTPUT WORKING TEMP. WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE ISOLATION RESISTANCE Up to 7200W or (2+1) units. Please refer to the Function Manual. 12V@0.1A(Only for Remote ON-OFF control) Please refer to the Function Manual Compensate voltage drop on the load wiring up to 0.25V. Please refer to the Function Manual. Power OK signal. Please refer to the Function Manual -20 ~ +70 (Refer to "Derating Curve") 20 ~ 90% RH non-condensing -40 ~ +85, 10 ~ 95% RH non-condensing ±0.05%/ (0 ~ 50) 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes UL62368-1, CSA C22.2 No. 62368-1, TUV EN62368-1, EAC TP TC 004, BSMI CNS14336-1 approved I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH Parameter Standard Test Level / Note Conducted EN55032 (CISPR32) Class B EMC EMISSION SAFETY & EMC (Note 4) Radiated EN55032 (CISPR32) Harmonic Current EN61000-3-2 Voltage Flicker EN61000-3-3 EN55024 , EN61204-3, EN61000-6-2, BSMI CNS13438 Parameter Standard ESD EN61000-4-2 Class A --------- Test Level / Note Level 3, 8KV air ; Level 2, 4KV contact EMC IMMUNITY Radiated EFT / Burst Surge EN61000-4-3 EN61000-4-4 EN61000-4-5 Level 3 Level 3 Level 3, 2KV/Line-Earth ; Level 2, 1KV/Line-Line Conducted EN61000-4-6 Level 3 Magnetic Field EN61000-4-8 Level 4 Voltage Dips and Interruptions EN61000-4-11 >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods OTHERS NOTE MTBF 234.1K hrs min. Telcordia SR-332 (Bellcore) ; 83.9K hrs min. MIL-HDBK-217F (25) DIMENSION 278*177.8*63.5mm (L*W*H) PACKING 3.3Kg; 4pcs/14.2Kg/1.81CUFT Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx File Name:RSP-2400-SPEC 2020-09-29 2400W Power Supply with Single Output RSP-2400 series Block Diagram I/P EMI FILTER ACTIVE INRUSH CURRENT LIMITING RECTIFIERS & PFC POWER SWITCHING RECTIFIERS & FILTER PFC CONTROL O.T.P. O.L.P. PWM CONTROL LOAD SHARING AUX FAN POWER O.V.P. DETECTION CIRCUIT REMOTE CONTROL RECTIFIERS & FILTER PFC fosc : 88KHz PWM fosc : 100KHz +S +V -V -S PV P OK RC CS AUX POWER Static Characteristics 100 90 80 70 60 50 180 185 190 195 200 210 220 230 240 250 264 INPUT VOLTAGE (V) 60Hz MODEL INPUT 12V 180~264VAC 2000.4W 166.7A 24V 2400W 100A 48V 2400W 50A Derating Curve Efficiency vs Load (48V Model) 92 100 90 EFFICIENCY (%) 88 80 86 84 60 50 82 40 80 78 20 76 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% -20 0 10 20 30 40 50 60 70 (HORIZONTAL) AMBIENT TEMPERATURE () LOAD The curve above is measured at 230VAC. LOAD (%) LOAD (%) File Name:RSP-2400-SPEC 2020-09-29 2400W Power Supply with Single Output Function Manual 1. Remote Sense The Remote Sense compensates voltage drop on the load wiring up to 0.25V RSP-2400 series CN2 PIN7 -S +V PIN8 +S +V LOAD -V -V Sense lines should be twisted in pairs to minimize noise pick-up. Caution: The power supply, by factory default(also the assumption for other sections), is shipped with, -S & -V on CN2, as well as +S & +V, shorted by connector. When activating the Remote Sense, the +S signal should be connected to the positive terminal of the load whereas -S signal to the negative terminal. 2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim) In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 20~110%(Typ.) of the nominal voltage by applying EXTERNAL VOLTAGE. CN2 PIN7 -S +V PIN8 +S PIN3 PV -V EXTERNAL VOLTAGE (DC) PIN5 -S Connecting an external DC source between PV & -S on CN2, and +S & +V, -S & -V also need to be connected as exhibited above. OUTPUT VOLTAGE (%) OUTPUT CURRENT (%) Vout 120 OVP >120% 100 100 80 Non-Linear 60 40 80 MODEL 12V 24V 48V 60 PV Range 2.4 ~ 13.2V 4.8 ~ 28V 9.6 ~ 56V 40 20 20 V 1 2 3 4 56 EXTERNAL VOLTAGE (DC) V 20 40 60 80 100 120 OUTPUT VOLTAGE (%) Please do not adopt PWM signal as the EXTERNAL VOLTAGE. The rated current should change with the Output Voltage Programming accordingly. Caution: (1)By factory default, the Output Voltage Programming is not activated, and PV(PIN3) and PS(PIN4) of CN2 are shorted by connector. Whenever this function is not needed to activate, as assumed in other sections' diagrams, please keep PV(PIN3) and PS(PIN4) of CN2 shorted ; otherwise, the power supply will have no output. (2)PV(PIN3) and PS(PIN4) of CN1 or CN2 must be disconnected if "Output Voltage Programming" function is used; otherwise, the internal electrical components may be damaged, and the power supply unit may thus be out of order. File Name:RSP-2400-SPEC 2020-09-29 2400W Power Supply with Single Output RSP-2400 series 3.Remote ON-OFF Remote ON-OFF is activated by the configuration with respect to CN1,CN2 and CN3 as shown in the following diagram. CN2 Example 3.2(A): Using external voltage source Internal 12V typ. PIN1 RCG PIN2 RC CN3 PIN7 AUXG PIN8 AUX By factory default, PV(PIN3) and PS(PIN4) on CN2 are shorted by connector; likewise, OLP(PIN9) and OL-SD(PIN10) on CN3 are shorted when shipped. 1K AUX 12V RC SW RCG AUXG Example 3.2(B): Using internal 12V auxiliary output AUX Internal 12V typ. 1K RC RCG SW AUXG Example 3.2(C): Using internal 12V auxiliary output Internal 12V typ. 1K AUX 1K RC SW RCG Connection Method AUXG SW Logic Power supply output ON Power supply output OFF Example 3.2(A) SW Open SW Close Example 3.2(B) SW Open SW Close Example 3.2(C) SW Close SW Open File Name:RSP-2400-SPEC 2020-09-29 2400W Power Supply with Single Output RSP-2400 series 4.Alarm Signal Output Alarm signal is sent out through "P OK" & "P OK GND" and P OK2 & P OK GND2 pins on CN3. Please acknowledge an external voltage source is required for this function. CN3 PIN3 P OK GND2 PIN1 P OK GND PIN4 P OK2 PIN2 P OK By factory default, OLP(PIN9) and OL-SD(PIN10) on CN3 are shorted by connector when shipped. Function P OK Description The signal is "Low" when the power supply is above 80% of the rated output voltage, or, say, Power OK The signal turns to be "High" when the power supply is under 80% of the rated output voltage, or, say, Power Fail Output of alarm(P OK, Relay Contact) Low (0.5V max at 500mA) High or open (External applied voltage, 500mA max.) Output of alarm(P OK2, TTL Signal) Low (0.5V max at 10mA) High or open (External applied voltage, 10mA max.) Table 4.1 Explanation of alarm P OK P OK2 R V 0.1uF R V P OK GND External voltage and R (The max. sink is 500mA and 20V) Fig. 4.1 Internal circuit of P OK (Relay, total is 10W) P OK GND2 External voltage and R (The max. sink is 10mA and 30V) Fig. 4.2 Internal circuit of P OK2 (Open collector method) File Name:RSP-2400-SPEC 2020-09-29 2400W Power Supply with Single Output RSP-2400 series 5.Select Overload Protection Type (1)Insert the shorting connector on CN3 that is shown in Fig 5.1, the Overload Protection Type will be "constant current limiting with delay shutdown after 5 seconds, re-power on to recover". This is the factory default. (2)Remove the shorting connector on CN3 that is shown in Fig 5.2, the Overload Protection Type will be "continuous constant current limiting". OL-SD OLP OL-SD OLP Fig. 5.1 Insert the CN3 Overload Protection Type : constant current limiting with delay shutdown after 5 seconds Fig. 5.2 Remove the CN3 Overload Protection Type : constant current limiting 6.Current Sharing with Remote Sense RSP-2400 has the built-in active current sharing function and can be connected in parallel, up to 3 units, to provide higher output power as exhibited below : The power supplies should be paralleled using short and large diameter wiring and then connected to the load. Difference of output voltages among parallel units should be less than 0.2V. The total output current must not exceed the value determined by the following equation: Maximum output current at parallel operation=(Rated current per unit)×(Number of unit)×0.9 When the total output current is less than 3% of the total rated current, or say (3% of Rated current per unit)×(Number of unit) the current shared among units may not be fully balanced. No.1(Master) AC/L AC/N No.2(Slave) +V -V When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unit Sense lines should be twisted in pairs to minimize noise pick-up. +S +V Load -V -S AC/L AC/N No.3(Slave) +V -V +V -V AC/L AC/N +S,-S and CS on CN1 or CN2are connected mutually in parallel. Under parallel operation, the "output voltage programming" function is not available. File Name:RSP-2400-SPEC 2020-09-29 2400W Power Supply with Single Output RSP-2400 series 6.Three Phase Connect Users can exploit three units of RSP-2400(unit 1 ,unit 2,unit 3) to work with 3power system. Please refer to following diagrams for configuration. FIG. A: 33 wire 220VAC SYSTEM R 220V unit 1 L1 FG1 N1 unit 2 L2 FG2 N2 unit 3 L3 S FG3 N3 220V T FG FIG. B: 34 wire 220/380VAC SYSTEM R N S T 380V 220V unit 1 L1 FG1 N1 unit 2 L2 FG2 N2 unit 3 L3 FG3 N3 FG FIG. C: 34 wire 190/110VAC SYSTEM R N (N.C.) S T 190V 110V unit 1 L1 FG1 N1 unit 2 L2 FG2 N2 unit 3 L3 FG3 N3 FG File Name:RSP-2400-SPEC 2020-09-29 2400W Power Supply with Single Output Mechanical Specification 278 236.3 1 8-M4(Both Sides) L=5mm 4-M4 L=5mm 1 236.3 Air flow direction 1 162 7.9 RSP-2400 series 27 1 27 1 38 12.5 20 63.5 Case No.982B Unit:mm 40 2-M4 8.5 M3 CN1 CN2 CN3 8 6 4 2 8 6 4 2 10 8 6 4 2 7 531 7 5 31 9 75 31 OUTPUT +V -V CN1 CN2 CN3 8 6 4 2 8 6 4 2 10 8 6 4 2 7 531 7 5 31 97 5 31 177.8 LED SVR + 13 10 4 INPUT 1 16max. TB1 123 Mounting Instruction Hole No. Recommended Screw Size 1 M4 MAX. Penetration Depth L 5mm Recommended mounting torque 7~10Kgf-cm Control Pin No. Assignment (CN1,CN2) : HRS DF11-8DP-2DS or equivalent 82 Mating Housing HRS DF11-8DS or equivalent Terminal HRS DF11-**SC or equivalent 71 CN1 and CN2 are connected internally. Pin No. 1 2 3 4 5,7 6 8 Function RCG RC PV PS -S CS(Current Share) +S Description Remote ON-OFF Ground Remote ON-OFF Connection for output voltage programming Reference Voltage Terminal Negative sensing for remote sense Current Share Postive sensing for remote sense Mounting Surface Chassis of RSP-2400 Mounting Screw L File Name:RSP-2400-SPEC 2020-09-29 2400W Power Supply with Single Output Control Pin No. Assignment (CN3) : HRS DF11-10DP-2DS or equivalent 10 2 91 Mating Housing HRS DF11-10DS or equivalent Terminal HRS DF11-**SC or equivalent Pin No. 1 2 3 4 5 6 7 8 9 10 Function P OK GND P OK P OK GND2 P OK2 RCG RC AUXG AUX OLP OL-SD Description Power OK Ground Power OK Signal (Relay Contact) Power OK Ground Power OK Signal (TTL Signal) Remote ON-OFF Ground Remote ON-OFF Auxiliary Ground Auxiliary Output Overload(OLP) type select AC Input Terminal Pin No. Assignment Pin No. Assignment Diagram 1 AC/L 2 AC/N 3 FG Maximum mounting torque 18Kgf-cm Installation Manual Please refer to : http://www.meanwell.com/manual.html RSP-2400 series File Name:RSP-2400-SPEC 2020-09-29