First Alert FA1600C Integrated Fire and Burglary Control

Overview

The FA1600C is a powerful integrated fire and burglary control panel that incorporates advanced technology to simplify end-user operations in demanding applications. It offers eight partitions in a UL listed Commercial Fire and Burglary control panel. The system supports up to 128 zones using basic hardwired, polling loop, and wireless technologies. It also accommodates indicating circuits, phone lines, keypads, RF receivers, and relays. The control offers scheduling capabilities and allows defined operations to be automated. It is available in either 12 or 24 volt models.

Key Features

Patented V-plex Global Polling Technology

Up to 120 additional zones can be added using the on-board multiplex circuit. This technology requires RPM (Remote Point Module) devices, individually assignable to one of eight partitions. It offers faster processing speeds (eight times faster than conventional multiplex systems) and a longer transmission distance (8,000 feet capability on twisted pair).

Fire Detection Features

User Codes

Accommodates 150 user codes, each capable of operating any or all partitions.

System Features

Common Lobby Logic

Allows for "First-in/Last-out" arming of all partitions. This simplifies end-user operation by automating system functions.

Scheduling and Relay Control

Simplifies end-user operation by automating system functions, including scheduling and relay control.

False Alarm Prevention Features

The control includes several features to help reduce false alarms caused by user error during the exit process:

8 Partitions

Provides the ability to control 8 separate areas independently, each functioning as its own separate control. A "Common Lobby" partition can be programmed to arm automatically when the last partition sharing the common lobby is armed and disarm when the first partition sharing the common lobby is disarmed.

Peripheral Devices

Supports up to 16 addressable devices, including keypads (FA550KP), RF receivers (4281/5881/5881EH), and relay modules (4204/4204CF). Each device is set to an individual address and enabled in the system via Device Programming Mode. Devices are typically connected to Keypad Port 1, with the exception of the alpha keypad which connects to Keypad Port 2.

Keypad Feature

Notification Appliance Circuit

Provides two class B supervised notification outputs on the control panel. A 4204CF Relay Module can supply two additional supervised bell outputs.

Auxiliary Relay

Provides a built-in "Form C" relay for alarm activation, trouble/supervisory activation, 4-wire smoke detector reset, or battery saving.

Optional Output Relays

Accommodates 16 relay outputs that can respond to system events, activate using time intervals, or be used for additional supervised bell outputs (4204CF only). Relays can be manually activated and supervised by control panels, each with an alpha descriptor.

Optional Voice Module

Supports the FA4285 telephone module, allowing users to obtain system status, arm/disarm the system, and control relays remotely.

Access Control

When programmed, users can activate a relay for two seconds to open access doors. Each partition can be assigned an access control relay. The VGM Vista Gateway Module allows full integration with the PassPoint access control system.

Event Log

Stores a log of up to 224 events, including arming/disarming, reporting, troubles, and alarms. The log can be viewed at the keypad, via a local printer, or through a downloader.

Scheduling

Provides scheduling capabilities for:

Agency Listings

Burglary: UL 609 Grade A Local Mercantile Premises and Mercantile Safe and Vault. UL 1610 Grades A, AA Central Station. UL 365 Grades A, AA Police Connect.

Fire: UL 864-NFPA 72 Local Central Station and Remote Station.

Communication Formats

Supports Ademco high speed, Ademco 4+2 express, Ademco low speed, Ademco contact ID, Sescoa, and Radionics low speed communication formats.

Electrical Specifications

Primary Power:

Backup Battery:

Alarm Power: 12VDC, 1.7 amps max.

Aux. Standby Power: 12VDC, 1 amp max.

Total Power: Combined auxiliary standby and alarm currents must not exceed 2.3 amps.

Standby Time: 24 hours, or 60 hours depending on battery size and load.

Fusing: Battery input, auxiliary, and bell power outputs are protected using PTC circuit protectors. All outputs are power limited.

Specifications

Control Dimensions: 18" H x 14.5" W x 4.3" D

Ordering Information

Diagram Description

The system diagram illustrates the FA1600C control panel as the central hub. It connects to various peripheral devices including keypads (FA550KP), polling loop devices, glass break detectors (7500GB, 9500GB), smoke detectors (various models like 2100, 2100T, 1100, 1151, 2151, 2400, 2400TH, 1400, 2451DH), addressable PIR/motion detectors (4275EX, 4278EX, 4278EX-SN, 998MX), addressable glassbreak/shock detectors (9500), and expansion devices like zone expanders (4209U, 4208U) and relay modules (4204, 4204CF). Communication modules such as the phone module (4285), dialer module (5140DLM), and serial module (4100SM) are also shown connected. The diagram highlights the connections for bell outputs and RF receivers (5881L, M, H, EH).

PDF preview unavailable. Download the PDF instead.

FA1600C Spec Sheet Acrobat Distiller 3.01 for Power Macintosh QuarkXPressª 4.03

Related Documents

Preview First Alert FA1600C/CA/CB Programming Guide
A comprehensive programming guide for the First Alert FA1600C/CA/CB Fire and Burglary Partitioned Security Systems with Scheduling. This document details system-wide and partition-specific programming fields, commands, and procedures for setting up and configuring the security system.
Preview First Alert Fire Extinguisher User Manual: FE4A60BCA & FE2A10GRA Operation and Safety Guide
Comprehensive user manual for First Alert fire extinguishers (Models FE4A60BCA, FE2A10GRA). Learn about installation, operation, inspection, maintenance, fire safety tips, and warranty information.
Preview First Alert P1210 Smoke and Fire Alarm User Manual and Installation Guide
Comprehensive guide for the First Alert P1210 10-year sealed battery photoelectric smoke alarm, covering introduction, key features, fire safety tips, installation instructions, recommended locations, operation, maintenance, troubleshooting, and limited warranty.
Preview First Alert Smoke Alarm User Manual - Installation & Operation Guide
Comprehensive user manual for First Alert Smoke Alarms, covering installation, operation, maintenance, troubleshooting, and safety guidelines for optimal home fire protection. Learn about recommended placement, features, testing procedures, and warranty information for models like M08-179722.
Preview First Alert PR710A Photoelectric Smoke Alarm: User Manual & Installation Guide
Comprehensive guide for the First Alert PR710A 10-year sealed battery photoelectric smoke alarm. Covers features, installation, testing, maintenance, safety, limitations, and warranty.
Preview First Alert FA2000C Control/Communicator Installation Instructions
Comprehensive installation guide for the First Alert FA2000C Control/Communicator, detailing setup, wiring, programming, and system operation for professional security systems.
Preview First Alert BRK Dicon Smoke Alarms Owners Manual - Installation, Operation & Safety
Comprehensive owners manual for First Alert BRK Dicon battery-operated smoke alarms (M300, M300AP, M300i, SA200, SA900, SA900Si, SA300, SA300L). Includes installation, location, testing, maintenance, troubleshooting, and fire safety tips.
Preview First Alert SM200 Smoke Alarm User Manual
User's manual for the First Alert SM200 Battery-Operated Smoke Alarm. Provides installation, operation, maintenance, and safety information.