User Guide for VISIONIS models including: VIS-AXESS-2D-ETL-PCB, VS-AXESS-2D-ETL-PCB-version2, VIS-AXESS-2D-ETL-PCB Two Door Network Access Control PCB Board Controller, Two Door Network Access Control PCB Board Controller, Network Access Control PCB Board Controller, Control PCB Board Controller, Board Controller, Controller
VIS-AXESS-2D-ETL-PCB Two Door Network Access Control PCB Board Controller TCP IP - Visionis
Access Controllers
File Info : application/pdf, 1 Pages, 15.51MB
DocumentDocumentDevice Parameter Working Voltage: DC 12V Working Current: Non-loaded <200mA Working Temperature: -20°C - 50°C (-4°F - 122°F) Working Humidity: 10° - 90° Power Consumption: <3W Size: 123 x 120 x 20mm (4.84 x 4.72 x 0.79in.) Communication Mode: TCP/IP Communication Rate: 10/100M (TCP/IP) Extension Communication: RS485 Users Capacity: 20.000 Users Capacity: 70.000 records Max. Doors: 2 Dry Contact Input: 6 Dry Contact Output: 3 Access Group: 200 Groups Default IP Address: 192.168.0.245 Default Communication Password: NULL Basic Function · First card open · Multi-card open · Anti-passback · Multi-door interlock · Card, password, card+password, card or password open mode · Different time differente open mode · Transmission encryption setup · Self-checking function · Remote control · Wiegand format can be self-defined · Add card without software · Multi-channel conection (max. 3 channels) · Real-time events active or passive upload · Arm/disarm by card · Arm/disarm by software · Relieve alarm by software · Multi-event linkage alarm · One event related to multi-relay trigger · Alarm delay turn off · Capacity can be expanded IMPORTANT: These access control panels (Version 2.0) are only compatible with access control panels (Version 2.0) and with the Titan VSAxess software. They are not compatible with access control panels (Version 1.0) nor with VSAxess software. · Self-defined door lock relay · Self-defined control door quantity · Door latch mode · Active door normal open mode by card · Timed automatic normal open mode · Timed invalid for exit button · Normal open time · Normal open holiday forbidden schedule · Access time schedule · Forbid access holiday schedule · Door lock delay setup · Access group setup · Threaten code setup · Force open/close door · Open door by software · Relieve normal open by card · Relieve card and card valid date setup · Expand RS485 communication · Real-time monitoring door and relay state Commercial Access Control VIS-AXESS-2D-ETL-PCB User Guide www.visionistech.com Wiring Introduction Wiring Position Power Supply - Access Controller Access Controller - Reader Access Controller - Electric Lock Access Controller - Exit Button Access Controller - IR Alarm Access Controller - Sound-light Alarm RS485 Communication Cable TCP/IP Communication Cable Wire Model RVV2*1.0 RVV4*0.5 RVV4*1.0 (Door-magnet feedback) RVV2*0.5 RVV2*1.0 RVV2*1.0 RVVP2*1.0 CAT-5 Remark Distance < 100M Distance 60M, max. can not over 100M. Distance < 150M Distance < 200M Distance < 200M Distance < 150M Distance < 1000M, shield layer connect to ground Distance < 100M Disclaimer The document provides information according to products specification. Visionis does not undertake any type of guarantee, express or implied warranties, including any implied merchantability, specific purposes or the infringement. The information in the document are changed without prior notice. Visionis and its associated sales agents special statement does not assume the result of the use of Visionis equipment of any and all direct, indirect, special, in general, by chance, inevitably, punitive damages. Any user's improper operation or use of the environment problem caused by direct or indirect losses, user pays full responsibility, equipment manufacturers and related sales agents does not undertake any responsability. Connection I/O Input Output Input Output Input Input Input Device Reader Electric Lock Door-magnet Sound-light alarm IR Sensor/Smoke Sensor/Others Exit button RS485 device Standard Wiegand 26-40 Switch Signal Switch Signal Switch Signal Switch Signal Switch Signal Communication Quantity 2 1/2 1/2 1/2 2 1/2 1 Setup as function as doors Support Support LED&Button Instruction LED One-door RL1 Lock1 RL2 Magnet Alarm1 RL3 Alarm Output1 Two-door Lock1 Lock2 Magnet Alarm1 · Power: 12V power LED · RUN: Device run LED · RDOK: Read card status LED · 2DOOR: The status LED of 2 doors · RDOK + RUN: Device enter online upgrade mode. · RESET Key: It is used to reboot device and clear communication password. After power off, power on device again and press RESET button for 3 seconds, then you can clear communication password Wiring Diagram of Access Controller Alarm Output Lock Lock 2 Fail-secure Lock 1 MODE RESET Port of Lamp Panel GND 485_B 485_A 3NO 3NC 3C 2NO 2NC 2C 1NO 1NC 1C GND GND 12V 12V 1RD 1RD + 1RD0 1RD1 1BUZ NULL 2RD 2RD + 2RD0 2RD1 2BUZ NULL AN1 GND D_S1 AN2 GND D_S2 ALR1 GND ALR2 TITAN VSAxess It applies to Windows 2000, Windows XP, Windows Server 2003, Windows Vista, Windows 7, Windows 10. Subsystem: · Access Control Management System · Attendance Management System · Real-time Monitor · Alarm Black Red Green White Keypad/Reader Reader 1 VIS-3100 Black Red Green White Reader 2 VIS-3000 Card reader state line Exit Button Exit Button 1 Magnet Door Magnet 1 Exit Button 2 Alarm Input Door Magnet 2 Smoke Alarm 1 (NO/NC) IR Alarm 2 (NO/NC) Quick Start Controller List Property Bar Dynamic Help Click to refresh All controllers in LAN will be shown in the list, left click to choose device. Click Network Controller Function Tree List Here you can see device type, version and MAC address. Here you can change the IP, sub-net mask and gateway. Task Report Communication setup-Network Controller Notice: 1. Controller IP must be the same as you set. 2. Controller model must be the same as device type. You can detect controller and check the device type in task report. 3. Usually we can use ping command to test the device physical connection. 4. Controller Address is only valid when use MS series controller or TCP/IP to RS485 connector, otherwise, the default is 0. 5. Wrong time may no access and incorrect access record. Please adjust the time. 6. Initialize the controller will clear the device records, please make sure the records are saved. Stop Button Card List Right Click Function Menu Present card to the reader which connect to controller, card number and add card time will display in the card list. Right click to choose the way of adding card. To choose a controller add card in pull down menu. Employee Setup-Card Notice: 1. If there are employees with the same name, you can separate them by code. Code is unique. 2. Card number is decimal number. 3. Default administrator access group can pass anywhere anytime, it is the top authority. 4. Each employee can access with a separate 6-digit password. 5. Impor from Excel can quick register employees. Click download setup Device List Right Click Function Menu Choose controller, then right click to download setup Task Report Current download process will be shown in the task report, green words mean successful. Red words mean operation fail. Other-Download Setup 1. Search Controller Notice: 1. Search function is only valid in the same LAN, as adopt UDP communication protocol, across gateway will forbid communication. 2. When connect network cable to device, Ethernet port green light is on, yellow light flash. 3. Please note that IP address can not be the same. 4. Domain name can be used in the software. Notice: Once installed the Titan Vsaxess Login information is: Username: Administrator Password: There is no default Password. Just click OK and you can login. You can set a Password under "Platform" and "Change password". 2. Add Controller 3. Add Card 4. Add Employee 5. Download Setup Notice: 1. Three download setup ways: Download setup, download all setups, smart download. Download setup refer to current device, download all setups and smart download refer to all devices. Smart download only download updated contents. Other two is download all setups. 2. When adopt smart download and download all setups, if there is a device offline, it will prompts error. 3. Default administrator access group can pass anywhere anytime, it is the top authority. Controller List Click disk icon to save. Right Click Function Menu Controller Property Click controller Right click to open function menu, choose add controller. Choose detect controller in right click menu, the function is detect device connection. Fill controller name model, door quantity and IP address, etc. Other property can refer to dynamic help. If connection OK, device model, version and door number will be shown in the report. Hardware Setup-Controller Notice: 1. Three ways to add card, card distributor add card, controller add card and add card manually. Card distributor add card need to choose our card distributor. 2. Same card can only add once. 3. Please note that delete card will clear the card related to employee. Employee List Save! Employee Property Click employee Right Click Function Menu Right click and choose add employee Input employee basic information. Click to enter card base Card Base Choose undistributed card to employee Employee Setup-Employee The manual is a quick start for system, the user can refer to software help file or other technical files for details. Important Notices · Power off when wiring. · Power on when wiring OK. · Power supply output current must 1.3 times bigger than device work current. · Lock should better use a separate power. · All devices must be connected to common GND. · RS485 communication must use hand to hand connection. · Between different reader should have 10cm to avoid interference. · As it is a current weak system, strong and weak isolation must be done. · The wiring of strong and weak should not be parallel and distance at least 20cm. · RS485 line should connect the cable shield to GND to avoid interference. · When RS485 line interface more devices, user can add a 120 resistance between 485+ and 485- of last device. · Reader can not nistall on the metal directly.