Installation Instructions: Powertron Flood Light
Code: 11330/1/2
Revision: 3
Date: 05.07.2025
Important Information
Read these instructions before installation and retain for future reference. This equipment should be installed by a competent electrician.
We recommend that luminaires are installed by a qualified electrician, ensuring the installation complies with current IEE wiring regulations BS7671:2018 & local building control.
BELL will not accept responsibility for any claims arising from a poor installation.
IP Rating: IP66
This product may contain substances that can be hazardous to the environment if not disposed of properly. Electrical and electronic equipment should never be disposed of with general household waste but must be separated for its correct treatment and recovery. Where possible, recycle your packaging.
Available Wattages: 600W, 1200W, 1800W
Contact Information
Technical Helpline: +44 (0)1924 893380
Website: https://www.belllighting.co.uk
Company: British Electric Lamps Ltd
Address: BELL House, Foxbridge Way, Normanton Industrial Estate, Normanton, West Yorkshire. WF6 1TN
Tel: +44 (0)1924 893380
Fax: +44 (0)1924 894320
Email: sales@belllighting.co.uk
Physical Dimensions
Dimensions are provided in millimeters (mm) and inches (").
600W Model
Height: 604mm (23.7")
Width: 406mm (15.9")
Depth: 202mm (7.9")
Mounting Holes: 3 x Ø22mm (0.8")
1200W Model
Height: 641mm (25.2")
Width: 440mm (17.3")
Depth: 202mm (7.9")
Mounting Holes: 3 x Ø22mm (0.8")
1800W Model
Height: 746mm (29.3")
Width: 301mm (11.8")
Depth: 202mm (7.9")
Mounting Holes: 3 x Ø22mm (0.8")
Mounting and Adjustments
Rotatable Angle & Torque Settings
The floodlight features adjustable mounting points with specific torque recommendations for secure positioning:
- 600W: 5-8 N.m
- 1200W: 10-29 N.m
- 1800W: 6-8 N.m
Laser Device Mount
Provision for mounting a laser device is included. The laser device and its specific bracket must be purchased separately. Different optic lenses may require different angle laser brackets.
Safety Rope Mount
For enhanced safety, a mount for a safety rope is provided. This typically involves a 3mm x 3m safety steel wire rope and an 8mm x 80mm rigging keychain (components not included with the floodlight).
Visor Mount
A visor can be mounted using M4 screws (6 pieces required). The recommended tightening torque is 1.2 N.m.
Effective Projected Area (EPA)
EPA values indicate the wind load surface area for different tilt angles. Values are provided in square meters (m²) and square feet (ft²).
Lamp Type | Upward Tilt (a=25°) | Horizontal (a=0°) | Downward Tilt (a=25°) | ||||||
---|---|---|---|---|---|---|---|---|---|
S1 | S2 | S3 | S1 | S2 | S3 | S1 | S2 | S3 | |
600W | 0.16m² / 1.71ft² | 0.21m² / 2.20ft² | 0.05m² / 0.65ft² | 0.30m² / 3.06ft² | 0.38m² / 3.93ft² | 0.10m² / 1.63ft² | 0.44m² / 3.81ft² | 0.55m² / 5.97ft² | 0.15m² / 3.81ft² |
1200W | 0.12m² / 1.19ft² | 0.23m² / 2.36ft² | 0.05m² / 0.65ft² | 0.17m² / 1.71ft² | 0.45m² / 4.56ft² | 0.10m² / 2.10ft² | 0.23m² / 1.19ft² | 0.66m² / 6.62ft² | 0.15m² / 1.19ft² |
1800W | 0.12m² / 1.71ft² | 0.21m² / 2.20ft² | 0.05m² / 0.65ft² | 0.16m² / 1.51ft² | 0.43m² / 4.42ft² | 0.10m² / 1.71ft² | 0.20m² / 2.88ft² | 0.65m² / 6.11ft² | 0.15m² / 2.77ft² |
Gear Tray Dimensions and Weight Capacity
Details on the gear tray size and the maximum weight it can support.
Lamp Type | Dimensions (mm/inch) | Weight Capacity |
---|---|---|
600W | Approx. 230mm (9.13") x 195mm (7.67") x 100mm (3.93") | <65kg |
1200W | Approx. 400mm (17.74") x 195mm (7.67") x 100mm (3.93") | <115kg |
1800W | Approx. 494mm (17.74") x 195mm (7.67") x 100mm (3.93") | <170kg |
Wiring Instructions
Wiring diagrams and specifications for connecting the floodlights.
600W Wiring
Input: L, N, GND
Connections:
- Input Cable (G07RN-F/3X1.5mm², L=1.0M) connects to Junction box.
- Junction box connects to LED board (LED+, LED-) and Lightning Protector.
- LED+ is typically Brown wire, LED- is typically Blue wire.
- ACL Driver is used.
1200W Wiring
Input: L, N, GND
Connections:
- Input Cable (H07RN-F/3x1.5mm², L=0.65M) and (G07RN-F/3X1.5mm², L=1.0M) connect to Junction box.
- Junction box connects to two LED boards (A and B), each with LED+ and LED-.
- LED+ is typically Brown wire, LED- is typically Blue wire.
- ACL Driver is used.
1800W Wiring & Remote Driver Unit
The 1800W model uses a remote driver unit.
Remote Driver Unit Dimensions:
- Length: 490mm (19.2") / 466mm (18.3")
- Width: 138mm (5.4") / 158mm (6.2")
- Height: 107mm (4.2")
Cable Glands:
- Output Section: M32 Cable gland (Clamping range: 10-13mm or 8-10mm x3). Tightening force: 8NM.
- Input Section: M25 Cable gland (Clamping range: 13-18mm). Tightening force: 7.5NM.
- Control Section: M16 Cable gland (2x) (Clamping range: 6-10mm). Tightening force: 2.5NM.
Connections: Supports AC, DMX, and LED connections for paralleling.
Clearance Distance Recommendations
When gear trays or remote drivers are installed in confined spaces, ensure minimum installation clearance. Make sure that the measured temperature (5 cm far away from each other) is not higher than the Ta max temperature of the lamp. Please refer to the distance instruction on the right.
Recommended Clearances: 200mm, 100mm, 70mm.
Circuit Breaker (MCB) Recommendations
The following table provides guidance on Miniature Circuit Breaker (MCB) types and quantities for connecting the floodlights. This is for reference only; final selection must be based on approved electrical system design.
Lamp Type | MCB Type | Input Voltage | Max Quantity per Breaker |
---|---|---|---|
600W | B 16 | 220-277V | 3 |
600W | B 32 | 220-277V | 6 |
600W | C 16 | 220-277V | 3 |
600W | C 32 | 220-277V | 7 |
1200W | B 16 | 200-277V | 1 |
1200W | B 32 | 200-277V | 3 |
1200W | C 16 | 200-277V | 1 |
1200W | C 32 | 200-277V | 3 |
1800W | B 16 | 200-420V | 1 |
1800W | B 32 | 200-420V | 3 |
1800W | C 16 | 200-420V | 1 |
1800W | C 32 | 200-420V | 3 |
Disclaimer: The quantity of luminaires per circuit breaker must be based on the electrical design approved by a qualified electrical system design engineer.