User Guide for Danfoss models including: Optyma iCO2 Condensing Units, Optyma iCO2, Condensing Units, Units

Optyma™ iCO2


File Info : application/pdf, 10 Pages, 800.02KB

PDF preview unavailable. Download the PDF instead.

AX451923145808en-000102
Service Guide
OptymaTM iCO2
www.danfoss.com

Service Guide | OptymaTM iCO2
1. Transport (Page 7) ............................................................................................................................ 3 2. Mechanical installation (Page 7-11)................................................................................................ 3 3. Remove lower front- and backside panels ..................................................................................... 3 4. Module Controller installation (Page 22-23).................................................................................. 4 5. Leak detection (Page 12-13) ............................................................................................................ 5 6. Vacuum dehydration (Page 13-17).................................................................................................. 6 7. Refrigerant charge (Page 17-20; 23) ............................................................................................... 6 8. Controller setting (Page 23-29) ....................................................................................................... 7 9. See more informative info in instructions ..................................................................................... 8 10. Notes................................................................................................................................................ 9

* Page references in brackets are pointing to instructions file AN405821998738 2 | AX451923145808en-000102

© Danfoss | Climate Solutions | 2023.10

Service Guide | OptymaTM iCO2
1. Transport (Page 7) Move the condensing unit to its final destination and if possible, unpack the unit once in position to avoid transport damage.
2. Mechanical installation (Page 7-11) Provide sufficient space around the condensing unit and fix the unit in position. Connect the suction/liquid pipe and insulate both. Install the supplied liquid line filter dryer. Connect to max. 8 evaporators with AK-CC55 controls, software version 1.7. Max. total 100m pipe length. Dismount Compressor red support how prevent damage during transport

Max. height difference evaporator(s) above condensing unit 5m. Max. height difference evaporator(s) below condensing unit 22m. Note. When using more than one evaporator ­ DO NOT install them above and below the condensing unit.
3. Remove lower front- and backside panels Electrical installation (Page 21-23): Provide proper power supply from grid via earth leakage breaker (30A type B 30mA), circuit breaker (25A class C, contact gap cat.3), main switch and supply cable 5G10mm² and connect it to provided terminals (L1, L2, L3, N) and grounding screw (PE). Switch ON the power supply and leave the control switch (CNS2) OFF, to active the crankcase heater for at least 6hours.

Power supply Modbus terminal Interface board PCB

Control switch (CNS2)

© Danfoss | Climate Solutions | 2023.10

AX451923145808en-000102 | 3

Service Guide | OptymaTM iCO2
4. Module Controller installation (Page 22-23) Install the Module controller (MC) metal bracket beside the unit controller electrical box with self-tapping crews and install the Module Controller electrical box on this bracket. Make the following connections for the Module controller: · Provided MC power supply cable with unit controller power supply terminals L1 and N. · Provided MC Modbus cable RS485-2 with the unit controller Modbus PCB terminals A+ to A+ and B- to B-. · MC Modbus terminals RS485-3 (terminated) in series with Modbus AK-CC55 evaporator controllers and terminate the last one. · Option if AK-SM800(A) installed: MC Modbus terminals RS485-1 (terminated) with System manager AK-SM800(A).
Internal wires are 1,5mm²

+V -V

RJ12
Module Controller
UNIVERSAL GATEWAY INPUT: 12V DC

N L

GND A+ BGND A+ BGND A+ B-

RS485-1 RS485-2

RS485-3 PWR
-+

M25

M20

4 additional knock-outs (M20) are available

M20

M20

Power supply to CDU 230V AC 1,2m cable for this is included. Caution: IF the cable needs to be replaced, it must be either be shortcircuit proof or it must be proctected by a fuse on the other end

Modbus to System Manager
Power supply to CDU Short-circuit proof cable NSGAFÖU 1,8/3kV 2 x 1,5mm² 1,2m (in PVC sleeve)

Modbus to evaporator controllers
Communication to CDU Twisted pair, shielded cable UNITRONIC® BUS LD 1 x 2 x 0.22 1,8m

RS485-2 Modbus interface for connection to the CDU, 1,2 m cable for this is included
RS485-1 Modbus interface for connection to the system manager

4 | AX451923145808en-000102

© Danfoss | Climate Solutions | 2023.10

Service Guide | OptymaTM iCO2
5. Leak detection (Page 12-13) Open valves for pressure equalization, if no power supply with a special magnet on solenoid valve SV-INJ, or with power supply open stepper and solenoid valves via following procedure · Unit power supply switched OFF · Move DIP-switch 5-7 from OFF to ON position · Turn power ON to open the stepper valves · Test the system with 80bar Nitrogen - only charge nitrogen from the medium/high pressure service ports. · You can check all the pressure points in the system on the module controller by reading the U parameters ­ all should read the same
if system is equalised in pressure. · Close the stop valve (connected to the safety valve) during air tightness test. THE PRV set point is 80 bar. After these test/charge
process, ensure to open the stop valve and seal it with appropriate material to secure the unit.
Note: The condensing unit is pressure tested from the factory. Be sure to test the field piping / evaporates at the correct pressure depending on evaporator M.W.P 60 or 80 bar. Always increase pressure slowly
Solenoid valve for hot gas bypass (SV-HG)

Compressor Solenoid valve for middle pressure injection (SV-INJ)

Receiver
of middle pressure

Receiver inlet expression

High pressure side service

Middle pressure side service

Oil service port

DIP-switch 5-7

© Danfoss | Climate Solutions | 2023.10

AX451923145808en-000102 | 5

Service Guide | OptymaTM iCO2

6. Vacuum dehydration (Page 13-17) Valves are still open from leak detection step before. Evacuate the system from suction port with a vacuum pump down to 0,67mbar (abs). Note: 7 segment display only shows positive pressure so during vacuum will display 0 Before oil charging, if no power supply, open additionally the hot gas bypass and oil return solenoid valves with a special magnet

Solenoid valve for hot gas bypass (SV-HG)

Stop valve

Subcooled coil

Compressor Solenoid valve for middle pressure injection (SV-INJ)

Receiver
of middle pressure

Receiver inlet expression

High pressure side service

Middle pressure side service

Oil service port

Safety valve
Low pressure side service port

Suction pipe (D19.05)

Liquid pipe (D12.7)

Filter dryier

Accumulator

Calculate additional oil charge with provided Excel table or formula provided in instructions and charge it from oil service port. Confirm correct oil level if unit controller par. C32 shows 110 (oil level sufficient). See page 7, how to operate unit controller display. Charge additional oil slowly if par. C32 shows continuous 010 (oil level low), or alarm code oPE88-1 or error code E88-1 appears from continuous low oil level during operation. Consider max. oil charge!
7. Refrigerant charge (Page 17-20; 23) Calculate refrigerant charge with provided Excel table or formula in instructions. Consider calculated max. refrigerant charge! Never overcharge! · Unit power supply switched OFF · Move DIP-switch 5-7 from ON to OFF position · Change dip switch 5-6 to on (This will completely open the electromagnetic solenoid valves and electronic expansion valves except
for EEV-LB and SV-INJ not to charge liquid refrigerant to the compressor) · Turn power ON to open the stepper valves · You can double check with 7 segment PCB display to check situation of control valves open/close as required · Break the vacuum with refrigerant in gas phase · Charge in the middle pressure connection port · Charge vapour until 7 bar to be sure to be above triple point (dry ice) · Then charge 90% of calculated mass in liquid phase · Charge additional refrigerant later in gas phase from suction port, while unit is running. · Indication of sufficient charge while running  5min.: · Sub-cooling degree par. C46-C15 shall be  0 Kelvin (recommend 1...3 Kelvin). · Subcooling expansion valve EEVSC par. C23 shall be fully open at 470 steps · No bubbles visible on sight-glass, mounted directly before last evap. expansion valve. · During charging the evaporator controllers need to be operating · Once charging is complete, power down the condensing unit and Change dip switch 5-6 from ON to OFF position.

6 | AX451923145808en-000102

© Danfoss | Climate Solutions | 2023.10

Service Guide | OptymaTM iCO2

8. Controller setting (Page 23-29)

a) Condensing unit controller operation: The standard unit controller display shows rotating the low-, medium- and high-pressure data in MPa. Other parameters can be displayed and confirmed by the "unit control PCB" 7-segment display, LED's and operating buttons.

The display operation is performed by push buttons "SW7" to "SW9".

· SW9: Code display - tens digit setting button: Jump from parameter "C0x" to "C1x" ... "C9x", "P0x" ... "P9x" by pressing SW9 repeatedly.

· SW8: Code display - ones digit setting button: Jump from parameter "Cx0", "Cx1" ... "Cx9"or "Px0" ... "Px9" by pressing SW8 repeatedly.

· SW7: Data erase/write button:

- Select the parameter to change via SW8/9.

- Press SW7 for 3 seconds to activate erase / write mode. The display starts flashing 2Hz.

- Press SW9 and/or SW8 to change the data. - Press SW7 for 3 seconds or more to store the changed data to EEPROM, and
jump from data erase/write mode back to display mode.

SW9 7-segment

- The CDU is controlled from now on with the new parameter content. The

recorded content is retained even after the power is turned back on.

· Remark: The data erase/write mode will be terminated, if no switch input for 10

SW8

sec.

Following types of identification alphabets of the code display unit exist:

"C": C00 ... C99 Sensor-, Actuator-, Unit-, Control-, Error-counter information

"P": P00 ... P99 User- and Service-settings

"E": E00 ... E99 Error code information

,,oPx" or oPE-X": Caution display

See full parameter lists with descriptions for inspection and servicing in

SW7

instructions booklet and pasted on the e-box cover.

Alarm/Error code reset*: · Press SW8 and SW9 will change display to "P20" · Press SW7 for > 3seconds, 7-Segment display will start flashing · Press SW8 to change alarm/error from 1 to 0 · *: Error reset can be done also via digital input (CNS3) activated with P08 = 3

b) Low pressure cut-out setting (page 36-37): Low pressure cut-out (pump-down) setting via DIP switches SW4-7 and SW4-8 located on unit controller, depend on Low Pressure Set Point (LPSP) according below table
c) Module Controller operation:

5

SW1
0

5

SW2
0

Insert tip of flat hInesaedrt(tpipreocfiflsiaotnh)ead s(cprreewcisdiorinv)esrcirnewthdirsiver silnotth, iasnsdlota,dajnudstadajtuast naut ma nbuemr.ber.

Evaporation temp. to set
5°C -5°C -10°C -40°C

SW1 (Tens place)
7 0 1 4

SW2 (Ones place)
5 5 0 0

SW

SW

4-7

4-8

OFF

OFF

ON

OFF

OFF

ON

ON

ON

Low pressure setting OFF value "X" 29.45 bar > LPSP
13.3 bar Pressure equivalent to "Evaporation temperature (setting value) -5 °C" Pressure equivalent to "Evaporation temperature (setting value) -10 °C" Pressure equivalent to "Evaporation temperature (setting value) -15 °C"

LPSP  29.45 bar 13.3 bar 25.47 bar 21.89 bar 18.68 bar

Low pressure control setting pressure (LPSP) LPSP  18.7 bar
18.7 bar > LPSP  13.3 bar 13.3 bar > LPSP

Low pressure setting OFF value X bar 9.0 bar 6.0 bar

© Danfoss | Climate Solutions | 2023.10

AX451923145808en-000102 | 7

Service Guide | OptymaTM iCO2
Note: Low pressure error cut-out at LP  5,8 bar
The Module Controller 3.5 digit 7-segment MMILDS display shows the saturated suction temperature Ts in °C. The display operation is performed by three push buttons, upper, middle, and lower. · Press upper button ~ 5 seconds to move from standard display to the 1st parameter r01 · Press upper or lower button to select other parameters · Press middle button to display parameter value · Press upper or lower button to modify a parameter · Press middle button to confirm the modified value. After 10 seconds without any action on push buttons jumps it back to standard display.
d) Required Controller settings during commissioning: The compressor frequency is suction pressure controlled, measured by the suction pressure transmitter. The suction pressure reference is set with two parameters, the upper and lower setpoint in bar(g). The arithmetic middle of those two values is the reference setpoint. Following Module Controller parameters need to be set during commissioning: · Set Par. r28 to 1 to activate the Module Controller as the reference setpoint device. · Modify Par. r01 for the correct lower setpoint in bar(g) · Modify Par. r02 for the correct upper setpoint in bar(g) The condensing unit requires communication to evaporator controllers for a proper oil return, which needs to be established from the Module Controller. · Scan for connected evaporator controllers with Par. n01 set to 1 · Check Modbus address of all connected evaporator controllers with par. Io01, Io02, Io03 ... all need to be visible! Start the condensing unit: · Set condensing unit ON/OFF-switch to ON and Module controller par. R12 to 1 Remark: You will find a complete Parameter and Error code list with short explanation on instructions page 26-29, and on a sticker pasted on the e-box cover.
9. See more informative info in instructions · Detailed explanation of CDU control (page 30-34): · Checks before turning ON power supply (page 35-36): · Trouble shooting / error codes (page 42-43): · External Input installation (page 46): · External output installation (page 47):

8 | AX451923145808en-000102

© Danfoss | Climate Solutions | 2023.10

Service Guide | OptymaTM iCO2

10. Notes · Settings as delivered from factory
- Main switch on PCB board will be 0 (CNS2) - Module controller will be R12 = 0 - The unit controller is factory configured on parameter r28 to 1 which means the evaporating temperature can be set by the display
on the module controller with parameters r01 & r02 · A joint (Reducer) to install on the service valve is included in the accessories · Pressures displayed in unit controller in Mpa (1MPa = 10 bar) · Pressures displayed in module controller in bar · If the unit will only start by setting in the module controller (R12 = -1) it will not start & no alarms visible on either unit controller or
module controller · When operating with CO2, set MOP on case controller, and set to lowest room / cabinet temperature ­ it is useful to reduce liquid
flood back to the compressor when all valves are opening. · Do not overcharge with CO2 ­ risk of liquid flood back ­ check suction superheat by measuring return gas temperature on the
suction strainer on the side of the compressor. · U parameters on module controller

Service Read discharge pressure Read gascooler outlet temp. Read receiver pressure Read receiver pressure in temperature Read discharge pressure in temperature Read suction pressure Read suction pressure in temperature Read discharge temperature Read suction temperature Read controller software version

u01

Pc

u05

Sgc

u08

Prec

u09

Trec

u22

Tc

u23

Po

u24

To

u26

Sd

u27

Ss

u99

© Danfoss | Climate Solutions | 2023.10

AX451923145808en-000102 | 9

AX451923145808en-000102

© Danfoss | Climate Solutions | 2023.10


Danfoss A/S Adobe PDF library 16.07