User Manual for COOPER Lighting Solutions models including: LRM347, LRM Lighting Relay Module, LRM347 LRM Lighting Relay Module, Lighting Relay Module, Relay Module, Module

Greengate

greengate, controls, control, system, room, room based, panel based, lighting, automatic, occupancy, vacancy, emergency, dlvp, room controller, lite keeper, control keeper, sensors, dimmers, switchpacks, ul924 emergency, bacnet, dmx, office, education, retail, hospitality, commercial, residential, industrial, indoor

Cooper Lighting Solutions

Greengate - Cooper Lighting

1 oct. 2022 — Top Product Features. • The Lighting Relay Module (LRM) is available in 347 VAC input voltage. • The LRM is designed to force all relays in a lighting ...

Greengate - LRM - Cooper Lighting

2022-10-12 — Top Product Features. • The Lighting Relay Module (LRM) is available in 347 VAC input voltage. • The LRM is designed to force all relays in a lighting ...


File Info : application/pdf, 2 Pages, 246.41KB

PDF preview unavailable. Download the PDF instead.

greengate lrm spec sheet
Project Prepared by

Catalog # Notes

Type Date

Greengate
LRM ­ Lighting Relay Module
The LRM provides a dry contact closure to the ControlKeeper M and MB panels when normal (grid) power is lost.
Typical Applications Office · Education · Healthcare · Hospitality · Retail · Industrial · Manufacturing

Interactive Menu
· Order Information page 2 · Wiring Diagrams page 2 · Product Warranty page 2

Product Certification

Top Product Features
· The Lighting Relay Module (LRM) is available in 347 VAC input voltage
· The LRM is designed to force all relays in a lighting control panel to an ON or Closed state, regardless of the control panel programmed relay status. This allows the closure of relays during loss of normal (grid) power to allow an alternate power source to drive the lighting loads. Once the LRM senses the normal power returning, the control panel will return to the normal programmed operating mode.
· This contact closure forces a hardware override of all relays in the enclosure to the ON state. This override condition takes priority over any relay commands from the system controller and will remain in effect until the contact closure from the LRM is removed.
· The LRM provides a dry contact closure to the ControlKeeper M and MB panels when normal (grid) power is lost.
· This contact closure forces a hardware override of all relays in the enclosure to the ON state. This override condition takes priority over any relay commands from the system controller and will remain in effect until the contact closure from the LRM is removed.
· UL 924 Listed Accessory (ControlKeeper M Series Panels only)
· Detects loss of power and auto sends signal to lighting control panel
· Allows Greengate panels to be listed as UL 924 when LRM is connected

additional product diagrams
PS50302222 page 1
October 2022

Greengate

LRM ­ Lighting Relay Module

Order Information
This is an accessory for the ControlKeeper M and ControlKeeper MB lighting control panels. When ordering, specify the LRM as a separate system accessory.

Catalog Number
Catalog Number LRM347

Description Lighting Relay Module

Rating 347 VAC

Product Specifications
Electrical Power Sources: Lighting Control Panels must be fed from alternate power Connection: Connects to normal power
Compatibility ControlKeeper M, ControlKeeper MB

Standards/Ratings · UL Approved · UL 924 Listed
Warranty Consult website for warranty information

Installation
The LRM can be installed next to the lighting control panel enclosure.
Wiring Diagrams
ControlKeeper M Motherboard

TO CCM

USB

RS-232

USB

HOST

DEVICE

J14 GND CAN-L SHIELD CAN-H +24V

+
TB2
+

--

CCM PWR

SH RS485

SH RS485

ETHERNET

MOR/RIM

OFF +24 ON

232 OPT R35

RIGHT RELAYS

LEFT RELAYS

NET-RX 1
NET NET HEART TX

LED7

LED6
DISPLAY

J9
ALL-OFF ALL-ON
1
S1 1

J6

RESETA B C J11

C67

J7

U35

D
SW5
RS232 Boot Mode

HEART
A B BEAT

U34

SW2

SW4

SW3

SW6

U37 1

U32

5001-000006-05

NET ADDRESS
SW1

1 2 4 8 16 32 64 128

C149 J15

C158A R25

GND +24 GND PG +5

LED11 SCM PWR

Off

+24

MOR/LRM MOR/LRM

On

For Emergency panel configurations, ensure the ControlKeeper M lighting control panel is fed from an emergency power source.
The LRM needs to provide a dry contact maintained closure to the On and +24 terminals on the ControlKeeper M motherboard MOR connector.

On

+24

Off

LRM Lighting Relay Module

Yellow (18 AWG)
NC C
NO

To override On: Connect dry contact between the On terminal and the +24 VDC terminal. When contact closes, all relays are forced On. Contacts within the LRM will automatically close when normal power is lost
To Normal Power Circuit 347 VAC = Brown
Neutral = White

Cooper Lighting Solutions 1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.cooperlighting.com

© 2022 Cooper Lighting Solutions All Rights Reserved.
Specifications and dimensions subject to change without notice.

Control Systems
· Greengate · DLVP
PS50302222 page 2
October 2022



References

Adobe PDF Library 16.0.7