Gree DC Inverter U-Match Series Service Manual
3. Troubleshooting
3.1 Wiring Diagrams
The following electric diagrams are for reference only. Please refer to the diagrams sticked on the unit as the latest version.
3.1.1 Wiring Diagrams of ODUS
Model: GUD50W/NhB-S
The diagram illustrates the wiring connections for the outdoor unit (ODU) and indoor unit (IDU). It details power supply connections, component layouts, and various sensors and control elements. Key components include the compressor (COMP), fan motor (M), main control board (AP), wiring board (XT1, XT2, XT3), and various sensors like temperature sensors (T-SENSOR, 20K, 15K, 50K) and pressure switches (HP, LP). The diagram also indicates specific wiring notes for independent power supply, outdoor unit powering the indoor unit, units with earthing wire motors, and units with electric heating belts.
A component table lists symbols and their corresponding names, such as:
- COMP: Compressor
- AP: Main control board
- XT1, XT2: Wiring board
- EH: Electric heating belt of chassis
- SAT: High pressure switch
- LP: Low pressure switch
- RT (20K): Speed adjustment temperature sensor
- 20K: Defrosting temperature sensor
- 15K: Ambient temperature sensor
- 50K: Discharge temperature sensor
- EKV: Electronic expansion valve coil
- 4YW: 4-Way valve
- XT3: Network interface
Model: GUD71W/NhB-S
Similar to the GUD50W/NhB-S, this diagram shows the ODU and IDU wiring. It includes the same types of components and notes regarding power supply and specific unit features.
Model: GUD100W/NhB-S
This section details wiring diagrams for various GUD models, including GUD100W/NhB-S, GUD125W/NhB-S, GUD140W/NhB-S, and GUD160W/NhB-S. The diagrams illustrate the connections between the outdoor and indoor units, highlighting components like the compressor, fan motors, control boards, and various sensors and valves. Notes explain specific wiring configurations for different unit features.
Model: GUD125W/NhB-S, GUD140W/NhB-S, GUD160W/NhB-S, GUD160W/NhB-X
These diagrams cover a range of models and their respective wiring configurations. They include detailed schematics for the outdoor unit and indoor unit, showing connections for power, control signals, sensors, and actuators. The diagrams also feature component layout maps and tables explaining the function of various symbols and interfaces.
Model: GUD50T/B-S, GUD71T/B-S, GUD100T/B-S, GUD125T/B-S, GUD140T/B-S
This section presents wiring diagrams for the Indoor Units (IDUs) of the T-series models. It shows the internal wiring of the IDU, including connections for power, sensors (e.g., ambient temperature, evaporator temperature), motors (DC motor, swing motor), and optional accessories like wired controllers and WIFI modules. Notes provide specific instructions for units with water pumps, gate control, iron shell motors, and other features.
Model: GUD50P/B-S, GUD50PS/B-S, GUD71PH/B-S, GUD71PHS/B-S, GUD100PH/B-S, GUD100PHS/B-S, GUD125PH/B-S, GUD125PHS/B-S, GUD140PH/B-S, GUD140PHS/B-S, GUD160PH/B-S, GUD160PHS/B-S
These diagrams focus on the indoor units of the P/PS/PH/PHS series. They illustrate the internal wiring, including connections for power, sensors, motors, and various control interfaces. The diagrams also detail the placement of components on the PCB and provide notes on optional accessories and specific unit configurations.
Model: GUD50ZD/B-S, GUD71ZD/B-S, GUD100ZD/B-S, GUD125ZD/B-S, GUD140ZD/B-S
This section provides wiring diagrams for the indoor units of the ZD series. It shows the internal wiring of the IDU, including connections for power, sensors, motors, and control interfaces. The diagrams also feature PCB layouts with numbered interfaces and corresponding descriptions, such as power supply, DC motor output, water level switch, and communication interfaces.
Model: GUD160W/NhB-X
This section includes wiring diagrams for the drive board of the GUD160W/NhB-X model. It details the connections for power input, compressor phase terminals, and communication interfaces. The diagram also shows the layout of components on the drive board.
3.2 PCB Layout
3.2.1 Interface
Indoor unit for GUD50ZD/B-S, GUD71ZD/B-S, GUD100ZD/B-S, GUD125ZD/B-S, GUD140ZD/B-S
The PCB layout for these indoor units is shown with numbered interfaces and a table detailing their functions. Key interfaces include:
- CN6: Power supply
- PUMP: DC water pump
- WATER_DTCT: Water level switch
- DOOR_C: Access control interface
- COM1, COM2: Accessories communication interface
- COM_MANAUL: Wired control communication interface
- DISP2, DISP3: Light board interface
- ROOM: Ambient temperature sensor interface
- DC_MOTOR: DC motor output
- UD_SWING1, UD_SWING2: Vertical swing output
- COM_BMS: MODBUS gateway interface
- COM_OUT: ODU communication interface
- TUBE: Evaporator temperature sensor
- HEAT: Electric heating interface
- X3: Ground wire
Indoor unit for GUD50T/B-S, GUD71T/B-S, GUD100T/B-S, GUD125T/B-S, GUD140T/B-S
The PCB layout for these indoor units is presented with numbered interfaces and a table of their functions. Interfaces include AC-L, AC-N, DC_MOTOR, SS, UD_SWING2, UD_SWING1, DOOR_C, COM_BMS, COM1, COM2, COM_OUT, COM_MANUAL, TUBE, DISP2, DISP3, SWING_OUT1, SWING_OUT2, PUMP, HEAT, WATER_DTCT, and CN7.
Indoor unit for GUD50P/B-S, GUD71PH/B-S, GUD100PH/B-S, GUD125PH/B-S, GUD140PH/B-S, GUD160PH/B-S, GUD50PS/B-S, GUD71PHS/B-S, GUD100PHS/B-S, GUD125PHS/B-S, GUD140PHS/B-S, GUD160PHS/B-S
The PCB layout for these indoor units is detailed with numbered interfaces and their corresponding functions. These include AC-L, AC-N, PE, DC-MOTOR, CN6, COM-OUT, COM-MANUAL, COM1, COM2, COM_BMS, DOOR_C, ROOM, TUBE, WATER_DTCT, HEAT, JUMP, and PUMP.
3.3 Error Code
This section lists various error codes and their corresponding descriptions for the Gree DC Inverter U-Match Series air conditioning units. The errors relate to different operational aspects and sensor readings:
- E1: Compressor high pressure protection
- E2: Indoor anti-freeze protection
- E3: Compressor low pressure protection, refrigerant lack protection and refrigerant collection mode
- E4: Compressor air discharge high-temperature protection
- E6: Communication error
- E8: Indoor fan error
- E9: Water-full protection
- F0: Indoor ambient temperature sensor error
- F1: Evaporator temperature sensor error
- F2: Condenser temperature sensor error
- F3: Outdoor ambient temperature sensor error
- F4: Discharge temperature sensor error
- F5: Wired controller temperature sensor error