Fan Coil Unit Room Thermostat with BACnet MS/TP Communication


File Info : application/pdf, 18 Pages, 415.78KB

PDF preview unavailable. Download the PDF instead.

RDB160BNU
Fan Coil Unit Room Thermostat with BACnet MS/TP Communication
RDB160BNU

The RDB160BNU controls fan coil units with the following features:
 HVAC applications: 2-pipe, 2-pipe with electric heater, and 4-pipe  Communication: BACnet MS/TP  Operating voltage: AC 24 V  Fan: 1, 2, 3-speed or DC 0...10 V (automatic or manual)  Valve actuators: On/off, 3-position or DC...10 V  Electric heater: On/off  Built-in temperature sensor  Three configurable inputs for external room/return air temperature, supply air
temperature limitation, heating/cooling changeover, window contact, and occupancy sensor.
 Operating modes: Comfort, Standby (Economy), OFF, and mold protection  Room temperature control: Based on built-in temperature sensor or room/return
air temperature
 Heating/cooling changeover: manual, or automatic via water temperature sensor or digital input
 Supply air temperature limitation  Automatic valve exercise  Backlit LCD

A6V12045445_en--_a 2022-04-26

Smart Infrastructure

Use Functions

The RDB160BNU is suitable for commercial applications where communication to a building management system is required, such as offices, healthcare, education, retail, shopping malls or other commercial facilities.
Temperature control  Built-in temperature sensor or  External room/return air temperature
Operating modes  Comfort  Standby (Economy)  OFF mode  Mold protection (optional in OFF mode)
Additional functions  Heating/cooling changeover
­ Manual: via thermostat (P02) or BACnet object ­ Automatic: via water temperature sensor or digital input  Supply air temperature limitation function
Security functions  Lock buttons  Lock parameter menu access  Block device during fire alarms  Valve exercising feature
Energy efficiency functions  Setpoint limitation  Window state  Occupancy
Fan operation  Automatic and manual modes  Fan operation in dead zone (fan kick)  Fan over-run for electric heater
Fan blocking functions  Block fan speed control in Auto mode  Block fan speed control in Manual mode
BACnet MS/TP communication  BACnet MS/TP MAC address: set from 0 to 127. Factory setting is 127.  BACnet MS/TP device instance number: set from 0 to 4194302. Factory setting is 0.  Baud rate: selectable between 9600, 19200, 38400 and 76800 (default setting) bps.

2 Smart Infrastructure

A6V12045445_en--_a 2022-04-26

Applications

HVAC applications The RDB160BNU can control fan coil units of the following types:  2-pipe system  2-pipe system with electric heater  4-pipe system The applications can be configured using the local parameter menu or via BACnet objects:

HVAC applications
 2-pipe fan coil (P01 = 2)

 2-pipe fan coil with electric heater
(P01 = 4)

 4-pipe fan coil (P01 = 3)

B2
T
YHC

T
(B1)
M1
T
(B1)

YE B2
T
YHC

T
(B1)
M1
T
(B1)

YC YH

T
(B1)
M1
T
(B1)

YHC Heating/cooling valve actuator M1

YH

Heating valve actuator

B1

YC

Cooling valve actuator

B2

YE

Electric heater

Fan
Return air temperature sensor or external room temperature sensor (optional)
Changeover sensor (optional)

Smart Infrastructure

3 A6V12045445_en--_a
2022-04-26

Control applications
The RDB160BNU can control 29 different FCU control applications with up to 2 DC 0...10 V control outputs i.e., the control of a DC fan, DC cooling valve, and DC heating valve is not possible.

2-pipe

Fan

1/2/3-speed DC 0...10 V

Output #1

On/Off, PWM, 3-position, DC 0...10 V

Output #2

N/A

2-pipe with electric heater

4-pipe

1/2/3-speed DC 0...10 V 1/2/3-speed

DC 0...10 V

On/Off, PWM, DC 0...10 V On/Off

On/Off, PWM, DC 0...10 V

On/Off, DC 0...10 V PWM
On/Off, PWM

4 Smart Infrastructure

A6V12045445_en--_a 2022-04-26

Mechanical design The RDB160BNU consists of 3 parts:  Mounting plate with screw terminals  Plastic housing with electronics, buttons, display, and room temperature sensor  Frame
Buttons

1

On/Off

2

Up/down

3

Fan

1

2 3

Display

12

3

12 11 10

9

8

7

1 AUTO/MAN: Automatic or manual mode indication for the fan

4

2 Current fan speed (Low, Medium, High)

5

3 Up/Down buttons to adjust setpoints and parameters

4 Occupancy indication
6 5 Current room temperature or setpoint in °F or °C (one decimal point)

6 Open window

7 COOL/HEAT: Shows the current control mode

8 STANDBY: Economy mode indication
SERVICE: Commissioning mode (setting parameters)

9 OFF: OFF mode

10 Indoor / outdoor temperature

11 Setpoint temperature

12 Fan status

Smart Infrastructure

5 A6V12045445_en--_a
2022-04-26

Type summary

Type

Order number

RDB160BNU S55770-T437

Designation RDB160BNU BACnet FCU Room Thermostat

Equipment combinations
The thermostat can be combined with sensors and actuators with compatible signal types as listed in chapter 'Technical data'.

Product documentation

Topic Installation instructions Commissioning instructions

Document ID: A6V12045441 A6V12045450

The Installation instructions document is available in English, Spanish, and French. It is included with the thermostat in the same packaging box. Related documents such as environmental declarations, CE declarations, etc., can also be downloaded at the following Internet address: www.siemens.com/bt/download The BTL listing can be found at https://www.bacnetinternational.net/btl/.

6 Smart Infrastructure

A6V12045445_en--_a 2022-04-26

Notes Safety

CAUTION
National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage.  Observe national provisions and comply with the appropriate safety regulations.

Mounting

 The thermostat is suitable for mounting directly on the wall or on a 4" x 4" conduit box (using the ARG70 adapter plate).
 Recommended height: 1.5 m above the floor.  Do not mount the devices in recesses, shelves, behind curtains or doors, or above or
near heat sources.
 Avoid direct solar radiation and drafts.  Seal the conduit box or the installation tube if any, as air currents can affect sensor
readings.
 Adhere to allowed ambient conditions.

Smart Infrastructure

7 A6V12045445_en--_a
2022-04-26

Installation

WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
 The AC 24 V mains supply line must have an external circuit breaker with a rated current of no more than 10 A.
 Adapt the supply line cable diameters as per local regulations to the rated value of the installed over-current protection device.
 Disconnect the thermostat from the power supply before removing it from the mounting plate.

WARNING
Relay outputs (DO1, DO2, DO3, DO4 or UO1) connected to mains voltage Injuries caused by electric shock when touching the device  Adapt the relay cable diameters as per local regulations to the rated value of the
installed over-current protection device.  Use only valve actuators rated for AC 24 V.

Commissioning

The RDB160BNU thermostat is delivered with pre-programmed control sequences. The relevant application and its parameters can be selected using the buttons on the thermostat. This can be done through:

 Setup Wizard: Only appears the first time the thermostat is powered on. It enables rapid system configuration of the most important parameters. For a list of these parameters, please refer to the installation instructions. See chapter 'Product documentation [ 6]'.
 Parameter Menu: Available anytime. Used to access and change the complete parameter set. For a list of these parameters, please refer to the commissioning instructions. See chapter 'Product documentation [ 6]'.

Disposal

The symbol with the crossed-out waste container means that electrical and electronic products and batteries may not be disposed of in normal household waste. They must be placed in separate collection and recycling containers according to the applicable laws. Please also refer to any applicable national labelling requirements. Proper disposal helps save valuable resources and prevents potentially harmful effects to people and the environment. Spent batteries and accumulators that can be removed from old devices for disposal, must be removed and placed in the indicated disposal channels. You are responsible for deleting any personal data from old devices for disposal. The registered manufacturers or distributors of electrical and electronic devices have established a common system for returning old devices. Suppliers of electrical devices must accept the returned devices at no charge. You can return old devices to the original sales location or to recycling or collection centers for old electrical devices. Please contact your regional or municipal offices/authorities for information on recycling centers or collection centers for old electrical devices.

8 Smart Infrastructure

A6V12045445_en--_a 2022-04-26

Warranty

Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used.

Smart Infrastructure

9 A6V12045445_en--_a
2022-04-26

Technical data

General

Operating voltage

AC 18...30 V

Frequency

50...60 Hz

Power consumption

2.5 VA

No internal fuse! External preliminary protection with max. C 10 circuit breaker required in all cases.

Ambient conditions, environmental conditions

Ambient temperature

32...122 °F (0...50 °C)

Storage temperature

-4...+158 °F (-20...+70 °C)

Ambient humidity

Max. 90%

Communication Communication Communication speed

BACnet MS/TP 9600, 19200, 38400 or 76800 bps

Inputs

Analog input (AI1)

PT1000-sensor, 32...122 °F (0...50 °C)

Universal input (UI1)

 Analog input: PT1000 sensor, 32...212 °F (0...100 °C)
 Digital input: potential-free contact

Digital input (DI1)

Potential free contact

Common ('C') power output (for UI1 and DI1 DC 24 V, max. 10 mA, short circuit-protected only)

Outputs

Digital outputs (Dox)

AC 24 V, max. 0.5 A

Do NOT connect fans in parallel. Connect one fan directly. For additional fans, install one relay for each speed.

Universal outputs (UOx)

 Digital output (DO): AC 24 V, max. 2.0 A
 Analog output (AO): DC 0...10 V, max. 5 mA

10 Smart Infrastructure

A6V12045445_en--_a 2022-04-26

Operational data Built-in temperature sensor Technology Measuring range Accuracy Setpoint range

NTC linearized 15 k 32...122 °F (0...50 °C) ±0.9 °F (±0.5 °C) at 59...86 °F (15...30 °C) 41...95 °F (5...35 °C)

Standards and directives

UL certificates

UL916 *)

BACnet BTL Listing

BACnet Application Specific Controller (B-ASC)

EU conformity (CE)

See EU declaration of conformity *)

UK conformity (UKCA)

See UK declaration of conformity *)

The product environmental declaration

See product environmental declaration *)

contains data on environmentally compatible

product design and assessments (RoHS

compliance, materials composition,

packaging, environmental benefit, disposal)

General Mounting
Terminal blocks
Display Casing material Color Safety class Net weight

Indoor, wall (directly, or on a 4" x 4" conduit box using the ARG70 adapter plate).
Lift type for max. cable cross-section: 2.1 mm2
Backlit LCD
Polycarbonate, PC
Signal white RAL 9003
IP20
3.88 ounces (110 g)

*) The documents can be downloaded at http://siemens.com/bt/download

Smart Infrastructure

11 A6V12045445_en--_a
2022-04-26

Connection terminals

No. Label

10

G

11

G0

12

DO1

13

DO2

14

DO3

Description
Supply voltage (AC 24 V~) Supply voltage (AC 24 V) Digital Output 1 (AC 24 V, max. 0.5 A): Fan speed low Digital Output 2 (AC 24 V, max. 0.5 A): Fan speed medium Digital Output 3 (AC 24 V, max. 0.5 A): Fan speed high

20

CDO

21

MUO

22

DO4

23

UO1

24

UO2

Common (AC 24 V~) for Digital Outputs: for DOs or UO1 (when configured as DO)
Measuring ground for Universal Outputs (-DC 0...10 V): for UOs (when configured as AOs)
Digital Output 4 (AC 24 V, max. 0.5 A):  Electric heater (2-pipe FCU with electric heater)  Cooling valve (4-pipe FCU)
Universal Output 1 (AC 24 V, max. 2.0 A or +DC 0...10 V, max. 5 mA):  Heating or cooling valve (2-pipe FCU and 2-pipe FCU with
electric heater)  Heating valve (4-pipe FCU)
Universal Output 2 (+DC 0...10 V):  Fan (all applications with DC fan)  Cooling valve (4-pipe FCU with 3-speed fan)

30

AI1

31

UI1

32

DI1

33

M

Analog Input 1 (PT1000 sensor, 32...122 °F (0...50 °C)):  External room temperature sensor  Supply air temperature sensor
Universal Input 1 (PT1000 sensor, 32...212 °F (0...100 °C) or contact):  Change-over temperature sensor or contact  Window contact
Digital Input 1 (Contact):  Presence detector  Window contact
Measuring ground: for AI1 or UI1 (when configured as AI)

12 Smart Infrastructure

A6V12045445_en--_a 2022-04-26

40

C

41

REF

42

-

43

+

Common (DC 24 V): for DI1 and UI1 (when configured as DI) BACnet MS/TP Reference BACnet MS/TP BACnet MS/TP +

Connection diagrams Inputs

External room Supply air temperature temp limitaion

Change-over

BACnet MS/TP

REF 43 42 41
REF

Window Window Occupancy

Smart Infrastructure

13 A6V12045445_en--_a
2022-04-26

Outputs

DC 0...10 V fan G G0 MUO UO2
10 11 21 24

G

L

G0

N

HVAC application 2-pipe

Control application
Heating/cooling valve (V1): On/Off or PWM

Wiring

UO1 CDO

23

20

2-pipe 2-pipe

Heating/cooling valve (V1): 3-position  UO1 = Open  DO4 = Close

UO1 DO4 CDO 23 22 20

Open

Close

Heating/cooling valve (V1): DC 0...10 V

UO1 MUO

23

21

2-pipe with electric heater

Heating/cooling valve (V1): On/Off or PWM
Electric heater (V2): On/Off

UO1 DO4 CDO

23

22 20

V2

14 Smart Infrastructure

A6V12045445_en--_a 2022-04-26

2-pipe with electric heater

Heating/cooling valve (V1): DC 0...10 V
Electric heater (V2): On/Off

UO1 MUO DO4 CDO 23 21 22 20
V2

4-pipe

Heating valve (V1): On/Off or PWM
Cooling valve (V2): On/Off or PWM

UO1 DO4 CDO

23

22 20

V2

4-pipe

Heating valve (V1): DC 0...10 V
Cooling valve (V2): On/Off or PWM

UO1 MUO DO4 CDO 23 21 22 20
V2

Smart Infrastructure

15 A6V12045445_en--_a
2022-04-26

3-/2-1-speed fan G G0 DO1 DO2 DO3 CDO
10 11 12 13 14 20

G G0

HVAC application 2-pipe

Control application
Heating/cooling valve (V1): On/Off or PWM

Wiring

UO1 CDO

23

20

2-pipe 2-pipe

Heating/cooling valve (V1): 3-position  UO1 = Open  DO4 = Close

UO1 DO4 CDO 23 22 20

Open

Close

Heating/cooling valve (V1): DC 0...10 V

UO1 MUO

23

21

2-pipe with electric heater

Heating/cooling valve (V1): On/Off or PWM
Electric heater (V2): On/Off

UO1 DO4 CDO

23

22 20

V2

2-pipe with electric heater

Heating/cooling valve (V1): DC 0...10 V
Electric heater (V2): On/Off

UO1 MUO DO4 CDO 23 21 22 20
V2

16 Smart Infrastructure

A6V12045445_en--_a 2022-04-26

4-pipe 4-pipe 4-pipe 4-pipe

Heating valve (V1): On/Off or PWM
Cooling valve (V2): On/Off or PWM
Heating valve (V1): DC 0...10 V
Cooling valve (V2): On/Off or PWM
Heating valve (V1): On/Off or PWM
Cooling valve (V2): DC 0...10 V
Heating valve (V1): DC 0...10 V
Cooling valve (V2): DC 0...10 V

UO1 DO4 CDO

23

22 20

V2

UO1 MUO DO4 CDO 23 21 22 20
V2

UO1 CDO UO2 MUO 23 20 24 21

V1

V2

UO1 MUO UO2 23 21 24

V2

Smart Infrastructure

17 A6V12045445_en--_a
2022-04-26

Dimensions

95 mm (3.74")

95 mm (3.74")

10 11 12 13 14
UP

20 21 22 23 24
UP

30 31 32 33

40 41 42 43

60 mm (2.36") 68 mm (2.68")
All dimensions in mm

60 mm (2.36") 68 mm (2.68")

28 mm (1.10")

Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies

Document ID Edition

A6V12045445_en--_a 2022-04-26

© Siemens Switzerland Ltd, 2022 Technical specifications and availability subject to change without notice.

