Instruction Manual for SIEMENS models including: RDB160BNU Fan Coil Unit Room Thermostat with BACnet MS TP Communication, RDB160BNU, Fan Coil Unit Room Thermostat with BACnet MS TP Communication, BACnet MS TP Communication
RDB160BNU - alpscontrols.com
Fan Coil Unit Room Thermostat with BACnet MS/TP Communication
File Info : application/pdf, 18 Pages, 415.78KB
DocumentDocumentFan Coil Unit Room Thermostat with BACnet MS/TP Communication RDB160BNU The RDB160BNU controls fan coil units with the following features: HVAC applications: 2-pipe, 2-pipe with electric heater, and 4-pipe Communication: BACnet MS/TP Operating voltage: AC 24 V Fan: 1, 2, 3-speed or DC 0...10 V (automatic or manual) Valve actuators: On/off, 3-position or DC...10 V Electric heater: On/off Built-in temperature sensor Three configurable inputs for external room/return air temperature, supply air temperature limitation, heating/cooling changeover, window contact, and occupancy sensor. Operating modes: Comfort, Standby (Economy), OFF, and mold protection Room temperature control: Based on built-in temperature sensor or room/return air temperature Heating/cooling changeover: manual, or automatic via water temperature sensor or digital input Supply air temperature limitation Automatic valve exercise Backlit LCD A6V12045445_en--_a 2022-04-26 Smart Infrastructure Use Functions The RDB160BNU is suitable for commercial applications where communication to a building management system is required, such as offices, healthcare, education, retail, shopping malls or other commercial facilities. Temperature control Built-in temperature sensor or External room/return air temperature Operating modes Comfort Standby (Economy) OFF mode Mold protection (optional in OFF mode) Additional functions Heating/cooling changeover Manual: via thermostat (P02) or BACnet object Automatic: via water temperature sensor or digital input Supply air temperature limitation function Security functions Lock buttons Lock parameter menu access Block device during fire alarms Valve exercising feature Energy efficiency functions Setpoint limitation Window state Occupancy Fan operation Automatic and manual modes Fan operation in dead zone (fan kick) Fan over-run for electric heater Fan blocking functions Block fan speed control in Auto mode Block fan speed control in Manual mode BACnet MS/TP communication BACnet MS/TP MAC address: set from 0 to 127. Factory setting is 127. BACnet MS/TP device instance number: set from 0 to 4194302. Factory setting is 0. Baud rate: selectable between 9600, 19200, 38400 and 76800 (default setting) bps. 2 Smart Infrastructure A6V12045445_en--_a 2022-04-26 Applications HVAC applications The RDB160BNU can control fan coil units of the following types: 2-pipe system 2-pipe system with electric heater 4-pipe system The applications can be configured using the local parameter menu or via BACnet objects: HVAC applications 2-pipe fan coil (P01 = 2) 2-pipe fan coil with electric heater (P01 = 4) 4-pipe fan coil (P01 = 3) B2 T YHC T (B1) M1 T (B1) YE B2 T YHC T (B1) M1 T (B1) YC YH T (B1) M1 T (B1) YHC Heating/cooling valve actuator M1 YH Heating valve actuator B1 YC Cooling valve actuator B2 YE Electric heater Fan Return air temperature sensor or external room temperature sensor (optional) Changeover sensor (optional) Smart Infrastructure 3 A6V12045445_en--_a 2022-04-26 Control applications The RDB160BNU can control 29 different FCU control applications with up to 2 DC 0...10 V control outputs i.e., the control of a DC fan, DC cooling valve, and DC heating valve is not possible. 2-pipe Fan 1/2/3-speed DC 0...10 V Output #1 On/Off, PWM, 3-position, DC 0...10 V Output #2 N/A 2-pipe with electric heater 4-pipe 1/2/3-speed DC 0...10 V 1/2/3-speed DC 0...10 V On/Off, PWM, DC 0...10 V On/Off On/Off, PWM, DC 0...10 V On/Off, DC 0...10 V PWM On/Off, PWM 4 Smart Infrastructure A6V12045445_en--_a 2022-04-26 Mechanical design The RDB160BNU consists of 3 parts: Mounting plate with screw terminals Plastic housing with electronics, buttons, display, and room temperature sensor Frame Buttons 1 On/Off 2 Up/down 3 Fan 1 2 3 Display 12 3 12 11 10 9 8 7 1 AUTO/MAN: Automatic or manual mode indication for the fan 4 2 Current fan speed (Low, Medium, High) 5 3 Up/Down buttons to adjust setpoints and parameters 4 Occupancy indication 6 5 Current room temperature or setpoint in °F or °C (one decimal point) 6 Open window 7 COOL/HEAT: Shows the current control mode 8 STANDBY: Economy mode indication SERVICE: Commissioning mode (setting parameters) 9 OFF: OFF mode 10 Indoor / outdoor temperature 11 Setpoint temperature 12 Fan status Smart Infrastructure 5 A6V12045445_en--_a 2022-04-26 Type summary Type Order number RDB160BNU S55770-T437 Designation RDB160BNU BACnet FCU Room Thermostat Equipment combinations The thermostat can be combined with sensors and actuators with compatible signal types as listed in chapter 'Technical data'. Product documentation Topic Installation instructions Commissioning instructions Document ID: A6V12045441 A6V12045450 The Installation instructions document is available in English, Spanish, and French. It is included with the thermostat in the same packaging box. Related documents such as environmental declarations, CE declarations, etc., can also be downloaded at the following Internet address: www.siemens.com/bt/download The BTL listing can be found at https://www.bacnetinternational.net/btl/. 6 Smart Infrastructure A6V12045445_en--_a 2022-04-26 Notes Safety CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. Observe national provisions and comply with the appropriate safety regulations. Mounting The thermostat is suitable for mounting directly on the wall or on a 4" x 4" conduit box (using the ARG70 adapter plate). Recommended height: 1.5 m above the floor. Do not mount the devices in recesses, shelves, behind curtains or doors, or above or near heat sources. Avoid direct solar radiation and drafts. Seal the conduit box or the installation tube if any, as air currents can affect sensor readings. Adhere to allowed ambient conditions. Smart Infrastructure 7 A6V12045445_en--_a 2022-04-26 Installation WARNING No internal line protection for supply lines to external consumers Risk of fire and injury due to short-circuits The AC 24 V mains supply line must have an external circuit breaker with a rated current of no more than 10 A. Adapt the supply line cable diameters as per local regulations to the rated value of the installed over-current protection device. Disconnect the thermostat from the power supply before removing it from the mounting plate. WARNING Relay outputs (DO1, DO2, DO3, DO4 or UO1) connected to mains voltage Injuries caused by electric shock when touching the device Adapt the relay cable diameters as per local regulations to the rated value of the installed over-current protection device. Use only valve actuators rated for AC 24 V. Commissioning The RDB160BNU thermostat is delivered with pre-programmed control sequences. The relevant application and its parameters can be selected using the buttons on the thermostat. This can be done through: Setup Wizard: Only appears the first time the thermostat is powered on. It enables rapid system configuration of the most important parameters. For a list of these parameters, please refer to the installation instructions. See chapter 'Product documentation [ 6]'. Parameter Menu: Available anytime. Used to access and change the complete parameter set. For a list of these parameters, please refer to the commissioning instructions. See chapter 'Product documentation [ 6]'. Disposal The symbol with the crossed-out waste container means that electrical and electronic products and batteries may not be disposed of in normal household waste. They must be placed in separate collection and recycling containers according to the applicable laws. Please also refer to any applicable national labelling requirements. Proper disposal helps save valuable resources and prevents potentially harmful effects to people and the environment. Spent batteries and accumulators that can be removed from old devices for disposal, must be removed and placed in the indicated disposal channels. You are responsible for deleting any personal data from old devices for disposal. The registered manufacturers or distributors of electrical and electronic devices have established a common system for returning old devices. Suppliers of electrical devices must accept the returned devices at no charge. You can return old devices to the original sales location or to recycling or collection centers for old electrical devices. Please contact your regional or municipal offices/authorities for information on recycling centers or collection centers for old electrical devices. 8 Smart Infrastructure A6V12045445_en--_a 2022-04-26 Warranty Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used. Smart Infrastructure 9 A6V12045445_en--_a 2022-04-26 Technical data General Operating voltage AC 18...30 V Frequency 50...60 Hz Power consumption 2.5 VA No internal fuse! External preliminary protection with max. C 10 circuit breaker required in all cases. Ambient conditions, environmental conditions Ambient temperature 32...122 °F (0...50 °C) Storage temperature -4...+158 °F (-20...+70 °C) Ambient humidity Max. 90% Communication Communication Communication speed BACnet MS/TP 9600, 19200, 38400 or 76800 bps Inputs Analog input (AI1) PT1000-sensor, 32...122 °F (0...50 °C) Universal input (UI1) Analog input: PT1000 sensor, 32...212 °F (0...100 °C) Digital input: potential-free contact Digital input (DI1) Potential free contact Common ('C') power output (for UI1 and DI1 DC 24 V, max. 10 mA, short circuit-protected only) Outputs Digital outputs (Dox) AC 24 V, max. 0.5 A Do NOT connect fans in parallel. Connect one fan directly. For additional fans, install one relay for each speed. Universal outputs (UOx) Digital output (DO): AC 24 V, max. 2.0 A Analog output (AO): DC 0...10 V, max. 5 mA 10 Smart Infrastructure A6V12045445_en--_a 2022-04-26 Operational data Built-in temperature sensor Technology Measuring range Accuracy Setpoint range NTC linearized 15 k 32...122 °F (0...50 °C) ±0.9 °F (±0.5 °C) at 59...86 °F (15...30 °C) 41...95 °F (5...35 °C) Standards and directives UL certificates UL916 *) BACnet BTL Listing BACnet Application Specific Controller (B-ASC) EU conformity (CE) See EU declaration of conformity *) UK conformity (UKCA) See UK declaration of conformity *) The product environmental declaration See product environmental declaration *) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal) General Mounting Terminal blocks Display Casing material Color Safety class Net weight Indoor, wall (directly, or on a 4" x 4" conduit box using the ARG70 adapter plate). Lift type for max. cable cross-section: 2.1 mm2 Backlit LCD Polycarbonate, PC Signal white RAL 9003 IP20 3.88 ounces (110 g) *) The documents can be downloaded at http://siemens.com/bt/download Smart Infrastructure 11 A6V12045445_en--_a 2022-04-26 Connection terminals No. Label 10 G 11 G0 12 DO1 13 DO2 14 DO3 Description Supply voltage (AC 24 V~) Supply voltage (AC 24 V) Digital Output 1 (AC 24 V, max. 0.5 A): Fan speed low Digital Output 2 (AC 24 V, max. 0.5 A): Fan speed medium Digital Output 3 (AC 24 V, max. 0.5 A): Fan speed high 20 CDO 21 MUO 22 DO4 23 UO1 24 UO2 Common (AC 24 V~) for Digital Outputs: for DOs or UO1 (when configured as DO) Measuring ground for Universal Outputs (-DC 0...10 V): for UOs (when configured as AOs) Digital Output 4 (AC 24 V, max. 0.5 A): Electric heater (2-pipe FCU with electric heater) Cooling valve (4-pipe FCU) Universal Output 1 (AC 24 V, max. 2.0 A or +DC 0...10 V, max. 5 mA): Heating or cooling valve (2-pipe FCU and 2-pipe FCU with electric heater) Heating valve (4-pipe FCU) Universal Output 2 (+DC 0...10 V): Fan (all applications with DC fan) Cooling valve (4-pipe FCU with 3-speed fan) 30 AI1 31 UI1 32 DI1 33 M Analog Input 1 (PT1000 sensor, 32...122 °F (0...50 °C)): External room temperature sensor Supply air temperature sensor Universal Input 1 (PT1000 sensor, 32...212 °F (0...100 °C) or contact): Change-over temperature sensor or contact Window contact Digital Input 1 (Contact): Presence detector Window contact Measuring ground: for AI1 or UI1 (when configured as AI) 12 Smart Infrastructure A6V12045445_en--_a 2022-04-26 40 C 41 REF 42 - 43 + Common (DC 24 V): for DI1 and UI1 (when configured as DI) BACnet MS/TP Reference BACnet MS/TP BACnet MS/TP + Connection diagrams Inputs External room Supply air temperature temp limitaion Change-over BACnet MS/TP REF 43 42 41 REF Window Window Occupancy Smart Infrastructure 13 A6V12045445_en--_a 2022-04-26 Outputs DC 0...10 V fan G G0 MUO UO2 10 11 21 24 G L G0 N HVAC application 2-pipe Control application Heating/cooling valve (V1): On/Off or PWM Wiring UO1 CDO 23 20 2-pipe 2-pipe Heating/cooling valve (V1): 3-position UO1 = Open DO4 = Close UO1 DO4 CDO 23 22 20 Open Close Heating/cooling valve (V1): DC 0...10 V UO1 MUO 23 21 2-pipe with electric heater Heating/cooling valve (V1): On/Off or PWM Electric heater (V2): On/Off UO1 DO4 CDO 23 22 20 V2 14 Smart Infrastructure A6V12045445_en--_a 2022-04-26 2-pipe with electric heater Heating/cooling valve (V1): DC 0...10 V Electric heater (V2): On/Off UO1 MUO DO4 CDO 23 21 22 20 V2 4-pipe Heating valve (V1): On/Off or PWM Cooling valve (V2): On/Off or PWM UO1 DO4 CDO 23 22 20 V2 4-pipe Heating valve (V1): DC 0...10 V Cooling valve (V2): On/Off or PWM UO1 MUO DO4 CDO 23 21 22 20 V2 Smart Infrastructure 15 A6V12045445_en--_a 2022-04-26 3-/2-1-speed fan G G0 DO1 DO2 DO3 CDO 10 11 12 13 14 20 G G0 HVAC application 2-pipe Control application Heating/cooling valve (V1): On/Off or PWM Wiring UO1 CDO 23 20 2-pipe 2-pipe Heating/cooling valve (V1): 3-position UO1 = Open DO4 = Close UO1 DO4 CDO 23 22 20 Open Close Heating/cooling valve (V1): DC 0...10 V UO1 MUO 23 21 2-pipe with electric heater Heating/cooling valve (V1): On/Off or PWM Electric heater (V2): On/Off UO1 DO4 CDO 23 22 20 V2 2-pipe with electric heater Heating/cooling valve (V1): DC 0...10 V Electric heater (V2): On/Off UO1 MUO DO4 CDO 23 21 22 20 V2 16 Smart Infrastructure A6V12045445_en--_a 2022-04-26 4-pipe 4-pipe 4-pipe 4-pipe Heating valve (V1): On/Off or PWM Cooling valve (V2): On/Off or PWM Heating valve (V1): DC 0...10 V Cooling valve (V2): On/Off or PWM Heating valve (V1): On/Off or PWM Cooling valve (V2): DC 0...10 V Heating valve (V1): DC 0...10 V Cooling valve (V2): DC 0...10 V UO1 DO4 CDO 23 22 20 V2 UO1 MUO DO4 CDO 23 21 22 20 V2 UO1 CDO UO2 MUO 23 20 24 21 V1 V2 UO1 MUO UO2 23 21 24 V2 Smart Infrastructure 17 A6V12045445_en--_a 2022-04-26 Dimensions 95 mm (3.74") 95 mm (3.74") 10 11 12 13 14 UP 20 21 22 23 24 UP 30 31 32 33 40 41 42 43 60 mm (2.36") 68 mm (2.68") All dimensions in mm 60 mm (2.36") 68 mm (2.68") 28 mm (1.10") Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID Edition A6V12045445_en--_a 2022-04-26 © Siemens Switzerland Ltd, 2022 Technical specifications and availability subject to change without notice.