Instructions for legrand models including: EBDMR-DALI 2, EBDMR-DALI 2 Connected Lighting Control System, Connected Lighting Control System, Lighting Control System, Control System
File Info : application/pdf, 7 Pages, 1.94MB
DocumentDocumentENCELIUM CONNECTED LIGHTING CONTROL SYSTEM POWERED BY SPECIALISTS WIRING GUIDE connected lighting control system typical radial topology Overview Typical components : number of devices / mA load One benefit of the connected lighting control system is that the 2 wire DALI subnet may be wired with a free topology, this means that any wiring configuration may be used so long as everything is connected, and it does not exceed the maximum subnet length of 300 m1 or the maximum load capacity of each DALI subnet at 64 x inputs + 64 outputs per channel or 200 mA We recommended design levels are 180 mA (10 % spare capacity) and 50 devices (typically a maximum of 12 control devices) per DALI subnet Each wired manager features 4 DALI channels and typically controls up to 64 inputs + 64 outputs per channel according to the current consumption of the devices used Luminaires DALI luminaire (single driver) 1 x device, 2 mA DALI emergency module (additional) 1 x device, 2 mA Please note some luminaires may contain more than one driver Control devices EBDMR-DALI 2... mid range PIR with photocell : 1 x device, 8 mA EBDSPIR-DALI2... PIR with photocell : 1 x device, 8 mA DP-SR-S4-WCU-DALI2... 4 button scene plate : 1 x device, 2 mA DALI-COUPLER-PB-G... (switch interface) 1 x device, 5 mA DP-SR-RM-DALI2... DALI switching actuator : 1 x device, 3mA Please refer to latest copy of application drawings that indicate which lighting circuits have been allocated to specific wired manager Any deviation from these drawings may result in the wired manager's maximum loadings being exceeded and could lead to additional wiring and equipment Please discuss any changes with us to ensure no overload For further information contact technical support on +44 (0) 0333 900 0671 1 : 300 m max. applies to a radial topology Star field network is acceptable : yotal cable used must not exceed 300 m DALI cable type Recommended field network cable : 1.5 mm2 twisted pair 600-1000 V rated LSOH : flex or equivalent (mains rated cable) Maximum length 300 m : singles must not be used. For further information or to discuss these options, contact technical support on +44 (0) 0333 900 0671 When DALI and mains cable share containment, DALI cable to be rated at same potential voltage as mains (although the DALI cable operates at ELV potential it is not classified as SELV). All wiring and connections are the responsibility of the customer Ethernet cable 1 x RJ45 10/100 Mbps, Cat 5e up to 100 m (audio MDI/MDI-X crossover). All equipment, wiring and connections are the responsibility of the customer Typical radial topology This illustration shows how each component is easily integrated into the Encelium Energy Management System DALI is a daisy chain communication topology that enables data in and out to the system components Each light fixture, sensor, and wall controller is daisy-chained back to the wired manager Note : sensors and wall controllers are powered from the DALI bus Cat. No. EN-M-DALI-X Wired manager IN Ethernet OUT ECN LINK SPEED LINK SPEED ONLINE DALI MANUAL 1 2 3 +-+ -+ ERROR 4 -+- SELECT Power ON/OFF/DIM Wired Manager -- DALI EN-M-DALI-X Product Code: 56377 flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2 10 to 12 mm Made in Canada ta = 40°C maximum 24V; 0.9A -+ 230 V Power supply 230 V power supply Light fitting PIR sensor (Cat. No. EBDSPIRDALI2) Switch input (DALI push button coupler) 24 V A B C D Cat. No. PS-30 Recommended field network cable : 1.5 mm2 twisted pair 600-1000 V rated LSOH : flex or equivalent (mains rated cable) Maximum length 300 m : singles must not be used, please contact us to discuss these options1 Wired manager DALI is powered from 24 V DALI power supply (Cat. No. PS-30 sold separately) Connect -/+24 V from DALI power supply to wired manager Do not connect DALI lines to mains or any mains referred voltage Wired manager and power supply will need to be installed in approriate DIN rail enclosure to ensure terminal connections are not accessible For further information contact technical support on +44 (0) 0333 900 0671 Note : wired manager needs to be installed in dry, indoor locations ONLY 1 : For further information contact technical support on +44 (0) 0333 900 0671 2 For more information on product specifications and design tools visit www.legrand.co.uk/en/brands/cp-electronics or contact your local Account Manager All dimensions (mm) are nominal connected lighting control system typical networked system Typical networked system Each wired manager, typically controlling individual floors / groups of inputs and outputs and can be linked via an Ethernet network, when data analytics / Polaris software is required. Internet or LAN connection allows control software to be operated anywhere on the network Note: if the customer's Ethernet network is not dedicated to the connected lighting control system then static IP addresses will need to be issued to Technical Support prior to the commissioning of the control's installation Static IP addresses will be required for each wired manager, each PC and 1 additional IP address should an SSU (system support unit Cat. No. EN-SSU-X) be installed Please liaise with the Commissioning Department for confirmation of the number of static IP addresses required To upper floors Ethernet network to upper floors *Customer supplied Network switch* 1 2 3 4 5 6 7 8 Power supply from local source 230 V Ethernet network First floor Legrand supplied products Wired manager - DALI Cat. No. EN-M-DALI-X IN Ethernet OUT ECN LINK SPEED LINK SPEED ONLINE DALI MANUAL 1 2 3 +-+ -+ ERROR 4 -+- SELECT Power ON/OFF/DIM Wired Manager -- DALI EN-M-DALI-X Product Code: 56377 flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2 10 to 12 mm Made in Canada ta = 40°C maximum 24V; 0.9A -+ DALI Power Supply DALI subnet D DALI subnet C DALI subnet B DALI subnet A 24 V (Cat. No. PS-30) Power supply from local source 230 V 100 m max. Network switch* 1 2 3 4 5 6 7 8 Power supply from local source 230 V Any cable connected to a switch 100 m max. Network switch* 1 2 3 4 5 6 7 8 Ethernet network Power supply from local source 230 V Ground floor Wired manager - DALI Cat. No. EN-M-DALI-X IN Ethernet OUT ECN LINK SPEED LINK SPEED ONLINE DALI MANUAL 1 2 3 +-+ -+ ERROR 4 -+- SELECT Power ON/OFF/DIM Wired Manager -- DALI EN-M-DALI-X Product Code: 56377 flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2 10 to 12 mm Made in Canada ta = 40°C maximum 24V; 0.9A -+ DALI Power Supply DALI subnet D DALI subnet C DALI subnet B 24 V (Cat. No. PS-30) Power supply from local source 230 V DALI subnet A Wired manager - DALI Cat. No. EN-M-DALI-X IN Ethernet OUT ECN LINK SPEED LINK SPEED ONLINE DALI MANUAL 1 2 3 +-+ -+ ERROR 4 -+- SELECT Power ON/OFF/DIM Wired Manager -- DALI EN-M-DALI-X Product Code: 56377 flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2 10 to 12 mm Made in Canada ta = 40°C maximum 24V; 0.9A -+ DALI Power Supply DALI subnet D DALI subnet C DALI subnet B DALI subnet A 24 V (Cat. No. PS-30) Power supply from local source 230 V System support unit (SSU - Cat. No. EN-SSU-X) Option to connect to customer network Customer to supply devices, i.e. Network switches for connection to Legrand products Customer supplied : DALI cable : 2 core mains rated, 1.5 mm radial Maximum length = 300 m Power supply from local source 230 V Customer supplied: Ethernet cable: 1 x RJ45 10/100 Mbps up to 100 m All dimensions (mm) are nominal 3 connected lighting control system typical connected topology and simple network Typical connected topology Connected solution using BVITM6 230 V Wired manager - DALI Cat. No. EN-M-DALI-X IN Ethernet OUT ECN LINK SPEED LINK SPEED ONLINE DALI MANUAL 1 2 3 +-+ -+ ERROR 4 -+- SELECT Power ON/OFF/DIM Wired Manager -- DALI EN-M-DALI-X Product Code: 56377 flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2 10 to 12 mm Made in Canada ta = 40°C maximum 24V; 0.9A -+ Power supply 24 V (Cat. No. PS-30) D C B A 230 V Subnet loading should be checked Each subnet 64 devices / 200 mA / 300 m max. Recommended field network cable : 1.5 mm2 twisted pair 600-1000 V rated LSOH : flex or equivalent (mains rated cable) Maximum length 300 m : singles must not be used, please contact us to discuss these options1 230 V power supply Light fitting PIR sensor (Cat. No. EBDSPIRDALI2) Switch input (Dali push button coupler) Next device BVITM6-S 230 V BVITM6-S BVITM6-E 1 : For further information contact technical support on +44 (0) 0333 900 0671 Simple network Where communication is required between wired managers, upto 4 x wired managers can be directly connected, this enables wired managers to communicate directly, alternatively network switches, by others, can be employed. Enabling more than 4 x wired managers to be employed for a given project or allow for system scaling Up to 4 x wired manager max. 230 V Wired manager - DALI Cat. No. EN-M-DALI-X IN Ethernet OUT ECN LINK SPEED LINK SPEED ONLINE DALI MANUAL 1 2 3 +-+ -+ ERROR 4 -+- SELECT Power ON/OFF/DIM Wired Manager -- DALI EN-M-DALI-X Product Code: 56377 flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2 10 to 12 mm Made in Canada ta = 40°C maximum 24V; 0.9A -+ Power supply 24 V (Cat. No. PS-30) A B C D 230 V Ethernet cable RJ45 10 / 100 Mbps upto 100 m (customer supplied) Wired manager Cat. No. EN-M-DALI-X Power supply Cat. No. PS-30 Wired manager - DALI Cat. No. EN-M-DALI-X IN Ethernet OUT ECN LINK SPEED LINK SPEED ONLINE DALI MANUAL 1 2 3 +-+ -+ ERROR 4 -+- SELECT Power ON/OFF/DIM Wired Manager -- DALI EN-M-DALI-X Product Code: 56377 flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2 10 to 12 mm Made in Canada ta = 40°C maximum 24V; 0.9A -+ Power supply 24 V (Cat. No. PS-30) A B C D 4 All dimensions (mm) are nominal connected lighting control system wiring diagram Mounting option Ethernet From Ethernet switch To additional wired managers Line Neutral Wired manager - DALI Cat. No. EN-M-DALI-X IN Ethernet OUT ECN LINK SPEED LINK SPEED ONLINE DALI MANUAL 1 2 3 +-+ -+ ERROR 4 -+- SELECT Power ON/OFF/DIM Wired Manager -- DALI EN-M-DALI-X Product Code: 56377 flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2 10 to 12 mm Made in Canada ta = 40°C maximum 24V; 0.9A -+ DALI Power Supply Attach ferrite over DALI wires, as close as possible to wired manager connection 24 VDC +24 VDC Ferrite KX4 touch screen LCD touch screen display panel Cat. No. RTI-KX4 1234 DALI Wired manager DALI (Cat. No. EN-M-DALI-X) (Cat. No. PS-30) Cable wire Stranded Solid Wired manager - SSU - DALI System support unit Sensor Sensor Polaris. monitor KX4 touch screen Wire Key Ethernet DALI PoE KX4 touch screen Cat. No. RTI-KX4 Flush mounting LCD touch screen display that provides the ability to recall multiple lighting scenes for a given zone. It's ideal for large multi-purpose spaces where lighting requirements vary throughout the day, such as an auditorium or conference room KX4 touch screen DALI wiring diagram To additional wired managers (as needed) Ethernet cable 91.4 m max. (typical) To secure LAN port for PC lighting control (requires static IP address) Wired manager- DALI KX4 Power supply Power supply 100 to 240 VAC, 50/60 Hz, 1.3 A 230 VAC, 50 Hz, 300 W SSU emergency circuit (preferred) non-emergency circuit (acceptable) External PoE switch 230 VAC, 50 Hz, 10 W (non-emergency circuit) Note: A PoE switch can be used. This will eliminate the need for individual PoE injectors Ethernet cable with PoE 91.4 m max. (typical) Note: The maximum run from the network switch to any end device is 91.4 m. The PoE injector does not extend the length limitation 5 connected lighting control system System Support Unit System Support Unit Cat. No. EN-SSU-X The System Support Unit (SSU) is a key component in the connected lighting control system. It hosts the Polaris software giving Facility Managers and Building Operators the ability to monitor and maintain their system. It enables them to change or modify light settings, schedules and other system settings. A typical building or campus requires one SSU per site Cat. No. EN-SSU-X DALI wiring To wired or wireless managers System network SSU 448 mm SSU Power plug Ethernet switch 700 mm Technical data Dimensions Weight Housing colour Housing material Mounting options 42.9 mm 700 x 448 x 42.9 mm (H x W x D) 14.3 kg Black Steel Rack mount Wall mount 4U wall mounted rack (optional and sold separately) All dimensions (mm) are nominal Contact details United Kingdom For further information contact the CP Electronics office: Brent Crescent London NW10 7XR Email: info@cpelectronics.co.uk Quotations and Technical Support: Tel: +44 (0) 333 900 0671 In accordance with its policy of continuous improvement, the Company reserves the right to change specifications and designs without notice. All illustrations, descriptions, dimensions and weights in this catalogue are for guidance and cannot be held binding on the Company. All contents and design presentation included in this publication are © Legrand Electric Limited. All rights reserved. 2024.