connected lighting control system
typical radial topology

 Overview

 Typical components : number of devices / mA load

One benefit of the connected lighting control system is that the 2 wire DALI subnet may be wired with a free topology, this means that any wiring configuration may be used so long as everything is connected, and it does not exceed the maximum subnet length of 300 m1 or the maximum load capacity of each DALI subnet at 64 x inputs + 64 outputs per channel or 200 mA
We recommended design levels are 180 mA (10 % spare capacity) and 50 devices (typically a maximum of 12 control devices) per DALI subnet
Each wired manager features 4 DALI channels and typically controls up to 64 inputs + 64 outputs per channel according to the current consumption of the devices used

Luminaires DALI luminaire (single driver) 1 x device, 2 mA DALI emergency module (additional) 1 x device, 2 mA
Please note some luminaires may contain more than one driver
Control devices EBDMR-DALI 2... mid range PIR with photocell : 1 x device, 8 mA EBDSPIR-DALI2... PIR with photocell : 1 x device, 8 mA DP-SR-S4-WCU-DALI2... 4 button scene plate : 1 x device, 2 mA DALI-COUPLER-PB-G... (switch interface) 1 x device, 5 mA DP-SR-RM-DALI2... DALI switching actuator : 1 x device, 3mA

Please refer to latest copy of application drawings that indicate which lighting circuits have been allocated to specific wired manager Any deviation from these drawings may result in the wired manager's maximum loadings being exceeded and could lead to additional wiring and equipment
Please discuss any changes with us to ensure no overload For further information contact technical support on +44 (0) 0333 900 0671
1 : 300 m max. applies to a radial topology Star field network is acceptable : yotal cable used must not exceed 300 m

DALI cable type Recommended field network cable : 1.5 mm2 twisted pair 600-1000 V rated LSOH : flex or equivalent (mains rated cable) Maximum length 300 m : singles must not be used. For further information or to discuss these options, contact technical support on +44 (0) 0333 900 0671
When DALI and mains cable share containment, DALI cable to be rated at same potential voltage as mains (although the DALI cable operates at ELV potential it is not classified as SELV). All wiring and connections are the responsibility of the customer
Ethernet cable
1 x RJ45 10/100 Mbps, Cat 5e up to 100 m (audio MDI/MDI-X crossover). All equipment, wiring and connections are the responsibility of the customer

 Typical radial topology

This illustration shows how each component is easily integrated into the Encelium Energy Management System DALI is a daisy chain communication topology that enables data in and out to the system components Each light fixture, sensor, and wall controller is daisy-chained back to the wired manager

Note : sensors and wall controllers are powered from the DALI bus

Cat. No. EN-M-DALI-X

Wired manager

IN Ethernet OUT

ECN

LINK SPEED

LINK SPEED

ONLINE

DALI MANUAL

1

2

3

+-+ -+

ERROR
4 -+-

SELECT

Power ON/OFF/DIM

Wired Manager -- DALI

EN-M-DALI-X

Product Code: 56377

flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2

10 to 12 mm Made in Canada

ta = 40°C maximum 24V; 0.9A
-+

230 V
Power supply

230 V power supply
Light fitting
PIR sensor (Cat. No. EBDSPIRDALI2)
Switch input (DALI push button coupler)

24 V
A B C D

Cat. No. PS-30

Recommended field network cable : 1.5 mm2 twisted pair 600-1000 V rated LSOH : flex or equivalent (mains rated cable) Maximum length 300 m : singles must not be used, please contact us to discuss these options1

Wired manager ­ DALI is powered from 24 V DALI power supply (Cat. No. PS-30 sold separately) Connect -/+24 V from DALI power supply to wired manager Do not connect DALI lines to mains or any mains referred voltage Wired manager and power supply will need to be installed in approriate DIN rail enclosure to ensure terminal connections are not accessible For further information contact technical support on +44 (0) 0333 900 0671
Note : wired manager needs to be installed in dry, indoor locations ONLY

1 : For further information contact technical support on +44 (0) 0333 900 0671
2

For more information on product specifications and design tools visit www.legrand.co.uk/en/brands/cp-electronics or contact your local Account Manager
All dimensions (mm) are nominal

connected lighting control system
typical networked system

 Typical networked system
Each wired manager, typically controlling individual floors / groups of inputs and outputs and can be linked via an Ethernet network, when data analytics / Polaris software is required. Internet or LAN connection allows control software to be operated anywhere on the network
Note: if the customer's Ethernet network is not dedicated to the connected lighting control system then static IP addresses will need to be issued to Technical Support prior to the commissioning of the control's installation Static IP addresses will be required for each wired manager, each PC and 1 additional IP address should an SSU (system support unit Cat. No. EN-SSU-X) be installed Please liaise with the Commissioning Department for confirmation of the number of static IP addresses required
To upper floors

Ethernet network to upper floors

*Customer supplied Network switch*

1

2

3

4

5

6

7

8

Power supply from local source 230 V
Ethernet network

First floor

Legrand supplied products
Wired manager - DALI Cat. No. EN-M-DALI-X

IN Ethernet OUT

ECN

LINK SPEED

LINK SPEED

ONLINE

DALI MANUAL

1

2

3

+-+ -+

ERROR
4 -+-

SELECT

Power ON/OFF/DIM

Wired Manager -- DALI

EN-M-DALI-X

Product Code: 56377

flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2

10 to 12 mm Made in Canada

ta = 40°C maximum 24V; 0.9A
-+

DALI Power Supply

DALI subnet D DALI subnet C DALI subnet B DALI subnet A

24 V (Cat. No. PS-30)
Power supply from local source
230 V

100 m max.

Network switch*

1

2

3

4

5

6

7

8

Power supply from local source 230 V

Any cable connected to a switch 100 m max.

Network switch*

1

2

3

4

5

6

7

8

Ethernet network

Power supply from local source
230 V

Ground floor

Wired manager - DALI Cat. No. EN-M-DALI-X

IN Ethernet OUT

ECN

LINK SPEED

LINK SPEED

ONLINE

DALI MANUAL

1

2

3

+-+ -+

ERROR
4 -+-

SELECT

Power ON/OFF/DIM

Wired Manager -- DALI

EN-M-DALI-X

Product Code: 56377

flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2

10 to 12 mm Made in Canada

ta = 40°C maximum 24V; 0.9A
-+

DALI Power Supply

DALI subnet D DALI subnet C DALI subnet B

24 V (Cat. No. PS-30)
Power supply from local source
230 V

DALI subnet A

Wired manager - DALI Cat. No. EN-M-DALI-X

IN Ethernet OUT

ECN

LINK SPEED

LINK SPEED

ONLINE

DALI MANUAL

1

2

3

+-+ -+

ERROR
4 -+-

SELECT

Power ON/OFF/DIM

Wired Manager -- DALI

EN-M-DALI-X

Product Code: 56377

flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2

10 to 12 mm Made in Canada

ta = 40°C maximum 24V; 0.9A
-+

DALI Power Supply

DALI subnet D DALI subnet C DALI subnet B DALI subnet A

24 V (Cat. No. PS-30)
Power supply from local source
230 V

System support unit (SSU - Cat. No. EN-SSU-X)

Option to connect to customer network
Customer to supply devices, i.e. Network switches for connection to Legrand products Customer supplied : DALI cable : 2 core mains rated, 1.5 mm radial Maximum length = 300 m

Power supply from local source
230 V

Customer supplied: Ethernet cable: 1 x RJ45 10/100 Mbps up to 100 m

All dimensions (mm) are nominal
3

connected lighting control system
typical connected topology and simple network

 Typical connected topology Connected solution using BVITM6
230 V

Wired manager - DALI Cat. No. EN-M-DALI-X

IN Ethernet OUT

ECN

LINK SPEED

LINK SPEED

ONLINE

DALI MANUAL

1

2

3

+-+ -+

ERROR
4 -+-

SELECT

Power ON/OFF/DIM

Wired Manager -- DALI

EN-M-DALI-X

Product Code: 56377

flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2

10 to 12 mm Made in Canada

ta = 40°C maximum 24V; 0.9A
-+

Power supply

24 V (Cat. No. PS-30)
D
C B A
230 V

Subnet loading should be checked Each subnet 64 devices / 200 mA / 300 m max.

Recommended field network cable : 1.5 mm2 twisted pair 600-1000 V rated LSOH : flex or equivalent (mains rated cable) Maximum length 300 m : singles must not be used, please contact us to discuss these options1

230 V power supply Light fitting PIR sensor (Cat. No. EBDSPIRDALI2)
Switch input (Dali push button coupler)
Next device

BVITM6-S

230 V

BVITM6-S

BVITM6-E

1 : For further information contact technical support on +44 (0) 0333 900 0671
 Simple network Where communication is required between wired managers, upto 4 x wired managers can be directly connected, this enables wired managers to communicate directly, alternatively network switches, by others, can be employed. Enabling more than 4 x wired managers to be employed for a given project or allow for system scaling

Up to 4 x wired manager max.

230 V

Wired manager - DALI Cat. No. EN-M-DALI-X

IN Ethernet OUT

ECN

LINK SPEED

LINK SPEED

ONLINE

DALI MANUAL

1

2

3

+-+ -+

ERROR
4 -+-

SELECT

Power ON/OFF/DIM

Wired Manager -- DALI

EN-M-DALI-X

Product Code: 56377

flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2

10 to 12 mm Made in Canada

ta = 40°C maximum 24V; 0.9A
-+

Power supply

24 V (Cat. No. PS-30)

A B C D
230 V

Ethernet cable RJ45 10 / 100 Mbps upto 100 m (customer supplied)

Wired manager ­ Cat. No. EN-M-DALI-X Power supply ­ Cat. No. PS-30

Wired manager - DALI Cat. No. EN-M-DALI-X

IN Ethernet OUT

ECN

LINK SPEED

LINK SPEED

ONLINE

DALI MANUAL

1

2

3

+-+ -+

ERROR
4 -+-

SELECT

Power ON/OFF/DIM

Wired Manager -- DALI

EN-M-DALI-X

Product Code: 56377

flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2

10 to 12 mm Made in Canada

ta = 40°C maximum 24V; 0.9A
-+

Power supply

24 V

(Cat. No. PS-30)

A B C D

4

All dimensions (mm) are nominal

connected lighting control system
wiring diagram

 Mounting option

Ethernet

From Ethernet switch

To additional wired managers

Line Neutral

Wired manager - DALI Cat. No. EN-M-DALI-X

IN Ethernet OUT

ECN

LINK SPEED

LINK SPEED

ONLINE

DALI MANUAL

1

2

3

+-+ -+

ERROR
4
-+-

SELECT

Power ON/OFF/DIM

Wired Manager -- DALI

EN-M-DALI-X

Product Code: 56377

flexible: Ø0.5 to 1.5 mm2 solid: Ø0.5 to 2.5 mm2

10 to 12 mm Made in Canada

ta = 40°C maximum 24V; 0.9A
-+

DALI Power Supply

Attach ferrite over DALI wires, as close as possible to wired manager connection

­24 VDC

+24 VDC

Ferrite

 KX4 touch screen ­ LCD touch screen display
panel Cat. No. RTI-KX4

1234
DALI Wired manager ­ DALI (Cat. No. EN-M-DALI-X)

(Cat. No. PS-30)

Cable wire

Stranded

Solid

Wired manager -

SSU -

DALI

System support unit

Sensor

Sensor

Polaris. monitor

KX4 touch screen

Wire Key
Ethernet DALI PoE

KX4 touch screen ­ Cat. No. RTI-KX4
Flush mounting LCD touch screen display that provides the ability to recall multiple lighting scenes for a given zone. It's ideal for large multi-purpose spaces where lighting requirements vary throughout the day, such as an auditorium or conference room

KX4 touch screen DALI wiring diagram
To additional wired managers (as needed)

Ethernet cable 91.4 m max. (typical)

To secure LAN port for PC lighting
control (requires static
IP address)

Wired manager- DALI

KX4
Power supply Power supply 100 to 240 VAC, 50/60 Hz, 1.3 A

230 VAC, 50 Hz, 300 W

SSU

emergency circuit (preferred)

non-emergency circuit (acceptable)

External PoE switch 230 VAC, 50 Hz, 10 W (non-emergency circuit)
Note: A PoE switch can be used. This will eliminate the need for individual PoE injectors

Ethernet cable with PoE 91.4 m max. (typical)
Note: The maximum run from the network switch to any end device is 91.4 m. The PoE injector does not extend the length limitation

5

connected lighting control system
System Support Unit
 System Support Unit ­ Cat. No. EN-SSU-X The System Support Unit (SSU) is a key component in the connected lighting control system. It hosts the Polaris software giving Facility Managers and Building Operators the ability to monitor and maintain their system. It enables them to change or modify light settings, schedules and other system settings. A typical building or campus requires one SSU per site

Cat. No. EN-SSU-X
 DALI wiring
To wired or wireless managers

System network

SSU

448 mm

SSU Power plug
Ethernet switch

700 mm

Technical data Dimensions Weight Housing colour Housing material
Mounting options

42.9 mm
700 x 448 x 42.9 mm (H x W x D) 14.3 kg Black Steel Rack mount Wall mount 4U wall mounted rack (optional and sold separately)

All dimensions (mm) are nominal

Contact details
United Kingdom For further information contact the CP Electronics office: Brent Crescent London NW10 7XR Email: info@cpelectronics.co.uk Quotations and Technical Support: Tel: +44 (0) 333 900 0671
In accordance with its policy of continuous improvement, the Company reserves the right to change specifications and designs without notice. All illustrations, descriptions, dimensions and weights in this catalogue are for guidance and cannot be held binding on the Company. All contents and design presentation included in this publication are © Legrand Electric Limited. All rights reserved. 2024.



References

Adobe PDF Library 17.0 Adobe InDesign 19.0 (Macintosh)