HumiTherm-i Pro

abc

HumiTherm-i Pro Operation Manual

Operation Manual This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application;

Operator Manual

Digital Humidity Indicator | Temperature Humidity Indicator - PPI


File Info : application/pdf, 2 Pages, 505.41KB

PDF preview unavailable. Download the PDF instead.

Product-148-OM
HumiTherm-i Pro
Enhanced `Temperature + Humidity' Indicator (with Dry/Wet RTD Input Selection)

PAGE-10 : TEMPERATURE - ALARM PARAMETERS

Parameters

Settings (Default Value)

Temperature Alarm Type

None

Process Low

Temperature Alarm Setpoint Temperature Alarm Hysteresis

Process High (Default : None)
-50.0 to 150.0°C or -58.0 to 302.0°F (Default :
For Process Low : -50.0 For Process High : 150.0)
0.1 to 25.0 °C or °F (Default : 0.2)

Temperature Alarm Logic Temperature Alarm Inhibit

Direct Reverse (Default : Direct)
No Yes (Default : Yes)

PAGE-11 : RELATIVE HUMIDITY - ALARM PARAMETERS

Parameters

Settings (Default Value)

%RH Alarm Type

None

Process Low

%RH Alarm Setpoint %RH Alarm Hysteresis

Process High
(Default : None)
0.0 to 100.0% (Default :
For Process Low : 0.0 For Process High : 100.0)
0.1 to 25.0% (Default : 0.2)

%RH Alarm Logic

Direct

%RH Alarm Inhibit

Reverse (Default : Direct)
No
Yes (Default : Yes)

Operation Manual
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

PAGE-12 : INPUT CHANNEL CONFIGURATION PARAMETERS

Parameters

Settings (Default Value)

Input Type For Temp Sensor

Refer Table 1 (Default : RTD)

Signal Low For Temp Sensor Signal High For Temp Sensor Temperature Range Low

Input Type 0 to 20 mA 4 to 20 mA 0 to 1.25 V
0 to 5 V 0 to 10 V 1 to 5 V

Settings 0.00 to Signal High 4.00 to Signal High 0.000 to Signal High 0.000 to Signal High 0.00 to Signal High 1.000 to Signal High

Default 0.00 4.00 0.000 0.000 0.00 1.000

Input Type 0 to 20 mA 4 to 20 mA
0 to 1.25 V 0 to 5 V 0 to 10 V 1 to 5 V

Settings Signal Low to 20.00 Signal Low to 20.00
Signal Low to 1.250 Signal Low to 5.000 Signal Low to 10.00 Signal Low to 5.000

Default 20.00 20.00
1.250 5.000 10.00 5.000

-199.9 to 999.9 (Default : 0.0)

Temperature Range High Zero Offset For Temp Value

-199.9 to 999.9 (Default : 100.0)
-25.0 to 25.0 (Default : 0.0)

Input Type For Humidity Sensor Signal Low For Humidity Sensor
Signal High For Humidity Sensor
%RH Range Low %RH Range High

Refer Table 1 (Default : 0 to 5 V)

Input Type 0 to 20 mA 4 to 20 mA 0 to 1.25 V
0 to 5 V 0 to 10 V 1 to 5 V

Settings 0.00 to Signal High 4.00 to Signal High 0.000 to Signal High 0.000 to Signal High 0.00 to Signal High 1.000 to Signal High

Default 0.00 4.00 0.000 0.000 0.00 1.000

Input Type 0 to 20 mA 4 to 20 mA
0 to 1.25 V 0 to 5 V 0 to 10 V 1 to 5 V

Settings Signal Low to 20.00 Signal Low to 20.00
Signal Low to 1.250 Signal Low to 5.000 Signal Low to 10.00 Signal Low to 5.000

Default 20.00 20.00
1.250 5.000 10.00 5.000

-199.9 to 999.9 (Default : 0.0)

-199.9 to 999.9 (Default : 100.0)

Parameters Wet-bulb Temperature Zero Offset
%RH Zero Offset

Settings (Default Value)
-25.0 to 25.0 (Default : 0.0)
-99.0 to 99.0 (Default : 0.0)

PAGE-13 : SUPERVISORY PARAMETERS

Parameters

Settings (Default Value)

Unit Selection for Temperature

°C
°F (Default : °C)

Dry-Bulb Temperature and % RH Min / Max

No

Monitoring

Yes

(Default : No)

Password For Resetting PV High - Low

0 to 250 (Default : 0)

Slave Id Baud Rate Parity Communication Write Enable

1 to 127 (Default : 1)
4800 9600 19200 (Default : 9600)
None Even Odd (Default : Even)
No Yes (Default : Yes)

101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar - 401 210. Sales : 8208199048 / 8208141446 Support : 07498799226 / 08767395333 E: sales@ppiindia.net, support@ppiindia.net

PAGE-14 : DE-HUMIDIFIER CONTROL PARAMETERS

Parameters

Settings (Default Value)

De-humidifier Control

Disable

De-humidifier Setpoint

Enable (Default : Disable)
0.0 to 100.0 (Default : 0)

De-humidifier Hysteresis

0.1 to 99.9 (Default : 2.0)

PAGE - 0 : OPERATOR PAGE AND PARAMETERS

Parameters

Settings (Default Value)

Maximum Dry Bulb Temperature Value

View Only

Minimum Dry - Bulb Temperature Value

View Only

Maximum %RH Value Minimum Peak of RH Reset Command
Reset Pass - Code

View Only
View Only
No Yes (Default : No) 0 to 250 (Default : 0)

Jan 2022

Table 1

FRONT PANEL LAYOUT

Option

What it means 3-wire, RTD Pt100

Range (Min. to Max.)

Resolution

-199.9 to +600.0 °C / -199.9 to 999.9 °F 0.1 °C / °F

0 to 20mA DC current 4 to 20mA DC current

Reserved (Don't Select)
0 to 1.25V DC voltage 0 to 5.0V DC voltage 0 to 10.0V DC voltage 1 to 5.0V DC voltage

-199.9 to 999.9 units

0.1 units

ELECTRICAL CONNECTIONS

Upper Readout

Temperature Alarm

Indicator

°CA

%RH Alarm Indicator
RHA

HumiTherm-i Pro
DHO L2

De-Humidifier Output Indicator

L1

L3

Serial Comm. Indicator

COM

L4

PAGE Key DOWN Key

Symbol

Key PAGE

Keys Operation
Function Press to enter or exit set-up mode.

Lower Readout ENTER Key
UP Key

DOWN

Press to decrease the parameter value. Pressing once decreases the value by one count; keeping pressed speeds up the change.

Press to increase the parameter value. Pressing

UP

once increases the value by one count; keeping

pressed speeds up the change.

ENTER

Press to store the set parameter value and to scroll to the next parameter on the PAGE.

TEMP. ALARM
RLY NC C NO
SSR SSR NC C NO
RLY
RH ALARM

TEMP INPUT
+-
mA/V RTD

RH INPUT
+-
mA/V RTD

RS485
B+ B-

+

17 16 15 14 13 12 11 10

18

9+

19

8-

20

7

21

6

1

2

3

4

5

L

N

85~264

VAC

NO

C

+

Relay EXC

DE-HUM 5/12/24V

PV Error Indications for Dry Bulb Temperature

Message

Error Type
Over-range Dry Bulb Temp. above Max. Range

Under-range Dry Bulb Temp. below Min. Range
Sensor Open Dry Bulb Sensor (RTD) Broken / Open

Message

PV Error Indications for Relative Humidity (RH)

Error Type

Cause

Over-range

Wet Bulb Temperature above Max. Range

Under-range

Wet Bulb Temperature below Min. Range

Sensor Open

Wet Bulb Sensor (RTD) Broken / Open

RH Error

This error is indicated in the following cases : · Dry Bulb Temperature above 102.0°C. · Dry Bulb Temperature below -20.0°C. · Wet Bulb depression beyond:
50.0°C for Dry Bulb Temperature above 0°C 5.6°C for Dry Bulb Temperature below 0°C

Display Freezes To 100.0%
Display Freezes To 0.0%

This error is indicated in the following cases : · Wet-Bulb Temperature exceeds Dry-Bulb Temperature. · Computed % RH above 100.0%.
Computed % RH is below 0.0%.

