UNI-T UT501A Insulation Resistance Tester User Manual
March 2, 2022
Overview
The UT501A Insulation Resistance Tester is designed with a brand-new design and a combination of massive integrated and digital circuits. It can measure insulation resistance, AC voltage, etc. The tester offers high accuracy, stable performance, easy operation, and reliability. It is used for insulation resistance measurement for insulation materials and various kinds of electric equipment such as transformers, electric machines, cables, switches, and electrical appliances. It is an ideal tool for electric equipment maintenance, testing, and inspection.
Technical Specification
Accuracy | ±(a% reading + digits); calibration per year. | ||||
Ambient temperature | 23(±5)°C | ||||
Environmental humidity | 45% to 75% | ||||
Rated Voltage | 100V | 250V | 500V | 1000V | |
Opened Voltage | DC100V±10% | DC 250V±10% | DC 500V±10% | DC 1000V±10% | |
Rated Test Current | When load is 100KΩ, the rated testing current is 0.9mA~1.1 mA. | When load is 250KΩ, the rated testing current is 0.9mA-1.1 mA. | When load is 500KΩ, the rated testing current is 0.9mA-1.1 mA. | When load is 1MΩ, the rated testing current is 0.9mA-1.1 mA. | |
Shorted Current | About less than 1.8mA. | ||||
Accuracy | 0.00MΩ -99MΩ: ±(3%+5digits); 100MΩ-5.5 GΩ :(5%+5digits) |
Voltage Measurement
- Test Range: 30V~750V(50Hz/60 Hz)
- Resolution: 1V
- Accuracy: ±(2%+3digits)
- Display: LCD. 1999 count.
- Low Battery Indication: "?"
- Overload Indication: "> 5.5GΩ" for insulation resistance measurement; "OL V" for voltage measurement.
- Autoranging.
- Discharge voltage automatically.
- Backlight, suitable in dark site.
- Red warning light (warning light is on when high voltage outputs).
- Working conditions: 0°C ~35°C; relative humidity is 75% or less; altitude: 2000m.
- Storage conditions: -20°C~ 60°C/ relative humidity is 80% or less.
- Dimensions (LxWxD): 150mm x 100mm x 71 mm.
- Power supply: alkaline batteries. 1.5V (5#) X6.
- Weight: 0.5kg (with battery).
- Accessories: test leads, instruction manual, carrying case, gallus.
Tester's Structure (See Diagram 1)
Diagram 1 shows the structure of the tester. The components are labeled as follows:
- 1. EARTH: Insulation resistance input jack.
- 2. G: Negative voltage input jack.
- 3. V: Positive voltage input jack.
- 4. LINE: Insulation resistance input jack (high voltage output).
- 5. LCD screen.
- 6. Backlight button.
- 7. Data-hold button.
- 8. Insulation resistance test button.
- 9. Functional knob.
Use
Voltage Measurement (See Diagram 2)
To measure AC voltage, follow these steps:
- Insert the red test lead into the "V" input port and the black test lead into the "G" input port.
- Place the function knob in the ACV function position to test AC voltage.
Caution:
- Do not input AC voltage over 750Vrms. It is possible to display a higher voltage, but it may cause damage to the instrument or electric shock.
- After all testing operations, disconnect the test leads and the circuit under test, and remove the test leads from the instrument input jack.
Insulation Resistance Measurement (See Diagram 3)
When measuring insulation resistance, please strictly place the two test probes separately. Do not mix them up. Neither short circuit the two test probes under high voltage output state nor measure insulation resistance after high voltage outputs.
- Before testing insulation resistance, the circuit under test must be completely discharged and completely isolated from the power supply circuit.
- Insert the red test wire into the "LINE" input port and the black test wire into the "EARTH" input port.
- Connect the red and black alligator clips to the circuit under test. The voltage is output from the LINE port.
Continuous Measurement
After the function knob is set to one of the test voltages (100V / 250V / 500V / 1000V), press the TEST key. The instrument will be self-locked to measure continuously. The test voltage will be output, and the TEST button will light up. With the measurement finished, press the TEST button to unlock and stop the measurement.
Caution:
- Make sure the tested circuit is de-energized before measurement. Do not measure the insulation of any energized equipment or wire.
- After the measurement is completed, do not touch the circuit by your hand. The capacitance stored in the circuit can cause electric shock.
- Do not touch test wires when they are disconnected from the tested circuit; wait until the test voltage is completely discharged.
Battery Replacement (See Diagram 4)
Please follow these steps to replace batteries:
- In order to avoid the risk of electric shock, first turn off the power source before replacing the battery (i.e., the function knob points at OFF) and remove the test wires.
- Unscrew the screws on the cover of the battery compartment and remove the battery compartment. Replace six batteries, minding the polarity when inserting.
- After the batteries are replaced, ensure to fasten the screws.
Caution:
- Please do not mix old and new batteries.
- In case the battery cover is opened, do not conduct any test.
Maintenance
Clean the case:
- Clean the surface with a damp soft cloth or sponge with clean water.
- To avoid any damage to the instrument, do not submerge it into water.
- When the instrument is wet, please dry it before storing or using.
- When there is a need to calibrate or repair the instrument, please have it serviced by professional personnel or a designated service center.
Safety Information
The UT501A is designed and manufactured in compliance with: IEC61010-1 CATIII 600V, Double Insulation, and Pollution Degree 2 standards. Operate as specified in the manual; otherwise, the protection offered by the tester would be impaired.
Compliance Standards: EN61010-1:2010; EN61010-2-030:2010; EN61557-1:2007; EN61557-2:2007; EN61326-1:2013; EN61326-2-2:2013. Warning: Please follow the safety instructions below in order to avoid hazard to the user, electric shock, or damage to the unit.
- Do not measure any AC circuit with voltages above 750V.
- Do not measure in flammable places. Spark may cause explosion.
- In case that the surface of the instrument is wet or the operator's hands are wet, please do not operate this instrument.
- Do not touch the electric conduction parts of test leads when testing.
- Do not open the battery cover when testing.
- When insulation resistance is measured, do not touch the electric wire under test.
- Stop using the instrument if it works abnormally. For example: the equipment is damaged or metal parts are exposed.
- Operator must be careful when voltage exceeds 33Vrms, 46.7Vacrms, or 70V DC. These kinds of voltage may cause electric shock.
- Do not replace the battery in wet conditions.
- Ensure that all test wires are connected to the test ports of the tester securely.
- When opening the battery cover, make sure that the instrument is turned off.
- Please read carefully and understand the manual before using the instrument.
- Use the instrument as specified in the manual at any time and store the manual for further reference.
- When the instrument is testing, misoperation may lead to an accident and damage of equipment.
- Before testing insulation resistance, the circuit under test must be completely discharged and completely isolated with other power circuits.
- In case that the test pen is damaged and needs to be replaced, use only the test leads with the same model or identical electrical specifications.
- When the battery indicator indicates that the power runs out, do not use the instrument. Remove the battery if the instrument is not in use for a long time.
- Do not store or use this instrument in heat, humid, flammable, explosive, and strong electromagnetic field environments.
File Info : application/pdf, 5 Pages, 276.46KB
DocumentDocumentReferences
Related Documents
![]() |
UT501A Insulation Resistance Tester Manual User manual for the UT501A Insulation Resistance Tester, providing detailed instructions for operation, safety, and maintenance. Learn how to measure insulation resistance and AC voltage with this reliable UNI-T instrument. |
![]() |
UNI-T UT513A Insulation Resistance Tester Operating Manual Comprehensive operating manual for the UNI-T UT513A Insulation Resistance Tester, detailing its features, safety precautions, measurement procedures for voltage and insulation resistance, maintenance, specifications, and troubleshooting. |
![]() |
UNI-T UT502A Insulation Resistance Tester Operating Manual Operating manual for the UNI-T UT502A Insulation Resistance Tester, covering safety information, technical specifications, tester structure, operation, and maintenance. |
![]() |
UNI-T UT503PV Photovoltaic Insulation Resistance Tester User Manual Comprehensive user manual for the UNI-T UT503PV Photovoltaic Insulation Resistance Tester, detailing its features, operation, safety guidelines, and technical specifications for accurate insulation resistance measurements in photovoltaic and conventional electrical systems. |
![]() |
UNI-T UT513B/UT513C Insulation Resistance Tester User Manual Comprehensive user manual for the UNI-T UT513B and UT513C digital high-voltage insulation resistance testers. Details features, specifications, safety, and testing procedures for electrical applications. |
![]() |
UNI-T UT593/UT595 Multifunction Safety Tester Operating Manual This operating manual provides detailed instructions for using the UNI-T UT593 and UT595 multifunction digital safety testing instruments. It covers safety precautions, technical specifications, and step-by-step procedures for various electrical tests including RCD, loop impedance, continuity, insulation resistance, voltage, frequency, and phase sequence. |
![]() |
UNI-T UT501E Fast Insulation Resistance Tester User Manual Comprehensive user manual for the UNI-T UT501E Fast Insulation Resistance Tester, detailing its functions, technical specifications, safety guidelines, operation procedures, and maintenance instructions. |
![]() |
UNI-T UT658 Series USB Testers: User Manual Comprehensive guide to the UNI-T UT658A, UT658C, UT658DUAL, and UT658LOAD USB testers. Learn about their features, specifications, safety regulations, and operation for testing USB chargers, power sources, and data cables. |