Installation Guide for Danfoss models including: WND-WR-MB Opt 38K, EP, WND-WR-MB Opt 38K, WattNode Modbus, WND-WR-MB Opt 38K WattNode Modbus, Modbus

WattNode Modbus, type WND-WR-MB Opt 38K, EP

PDF preview unavailable. Download the PDF instead.

AN430921567693en-000101
Danfoss 80G8406

Installation Guide
WattNode Modbus Type WND-WR-MB Opt 38K, EP

­40 ­ +80 °C (­40 ­ 176 °F) Operating Humidity: non-condensing, 5 ­ 90% relative humidity (RH) up to 40 °C, decreasing linearly to 50% RH at 55 °C.
L × W × H: 155 mm × 85 mm × 38 mm (6.1" × 3.35" × 1.5")
Mounting holes: center-to center 136.6 mm (5.375 in)

EIA-485

Monitoring Device
A-, D0, RxD-/TxDB+, D1, RxD+/TxD+
Common

White Black White Black White Black

Continental Control Systems LLC !
A- WN® M

Modbus

B+

WND-WR-MB Opt EP, 38K

C Com

X

VN

CT1

PCT1

VA

CT2

PCT2

VB

CT3

PCT3

VC

1 0

Source Faces

CT: 0,333 V AC at rated current

Current Transformers

Ground
Phase A Phase B Phase C Neutral

LINE LOAD

Code 080Z2129

Electrical Service Type (Load type) Single Phase 2-wire with neutral
Single Phase 3-wire with neutral Three Phase 4-wire wye (star) with neutral

Line-to-Neutral (V AC) 96 ­ 347
96 ­ 347 96 ­ 347

Line-to-Line (V AC) 120 ­ 600
120 ­ 600 120 ­ 600

Meter Powered by Line to Neutral or Line to Line
Line to Neutral or Line to Line Line to Neutral or Line to Line

Single Phase 2-wire with neutral

Single Phase 3-wire with neutral

Three Phase 4-wire Wye (star) with neutral

WN®
CT3 CT2 CT1 VC VB VA VN

Earth Neutral L1

WN®
CT3 CT2 CT1 VC VB VA VN

Earth Neutral L1 L2

WN®
CT3 CT2 CT1 VC VB VA VN

Earth Neutral L1 L2 L3

Modbus address

DIP Switch Up (1) Value Address 1 1+2+4 = 7 4+16 = 20 1+2+16+32 = 51

1 1
Up Up Down Up

2 2
Down Up
Down Up

3

4

4

8

Examples

Down Down

Up

Down

Up

Down

Down Down

5 16
Down Down
Up Up

6 32
Down Down Down
Up

Danfoss 80G8407 Danfoss 80G8408 Danfoss 80G8409

© Danfoss | Climate Solutions | 2022.10

AN430921567693en-000101 | 1

Modbus integration with the AK-SM 800A
Step 1: Set the Modbus address Step 2: Perform a network scan from the AK-SM 800A* *For more information about data communication see document RC8AC and the AK-SM 800A manual. Pay special attention to the AK-SM 800A manual if devices with a different baud rate than 38.400 baud are connected to the AK-SM 800A, e.g. the variable speed compressor type SLV.

Phase Status LED

All/ Single phase All
All
All
All
Single Single Single
Single

LED Indication Description

Red, Yellow, Green for 3 x 1 second Red / Green continuous flashing OFF
Red for 3 seconds or more
Green
OFF Red continuous flashing
Flashing Green

Power up sequence
Overvoltage warning. Line voltage too high. DISCONNECT power immediately!
WattNode not operating. Check that the wiring and voltages are correct
WattNode Error. If you see this happen repeatedly, replace the meter No power but line voltage is present on this phase No voltage on this phase Negative power on this phase (Reversed CT's, swapped CT wires or CT not matching line voltage phase) Positive power on this phase

Modbus Com LED
LED Indication Green flash Yellow flash Red for 1 second Red / Yellow continuous flashing Red

Description Valid packet for this device Valid packets for different device Invalid packet (bad baud rate, noise, ...) Possible address conflict (two devices with same address) Address set to 0 (zero)

Precautions
1.1 Only qualified personnel or licensed electricians should install the WattNode meter. The mains voltages can be lethal! 1.2 Follow all applicable local and national electrical and safety codes. 1.3 The terminal block screws are not insulated. Do not contact metal tools to the screw terminals if the circuit is live! 1.4 Verify that circuit voltages and currents are within the proper range for the meter model. 1.5 Use only UL listed or UL recognized current transformers (CTs) with built-in burden resistors, that generate 0.333 Vac (333
millivolts AC) at rated current. Do not use current output (ratio) CTs such as 1 amp or 5 amp output CTs: they will destroy the meter and may create a shock hazard. 1.6 Protect the line voltage phase conductors, typically #14 or #12 AWG with 3 pole 15 A or 20 A breaker. Depending on location, breaker may provide disconnect means. 1.7 Equipment must be disconnected from the HAZARDOUS LIVE voltages before access. 1.8 If the meter is not installed correctly, the safety protections may be impaired.

2 | AN430921567693en-000101

© Danfoss | Climate Solutions | 2022.10

