SmartLine RMA801 HART/DE Remote Indicator Assembly
Quick Start Installation Guide
Document Number: 34-ST-25-63, Revision 7, February 2022
Introduction
This document provides descriptions and procedures for the quick installation of Honeywell's SmartLine Remote Indicator. The SmartLine Remote Indicator is a configurable intelligent field device that functions as an output and status indicator for any HART and DE devices.
For complete details, refer to the manuals listed for protocols, user interface (HMI) operation, installation, configuration, calibration, maintenance, parts, safety, approvals, and options.
Documentation Access
To access complete documentation, including language variants, scan the QR code below using your smartphone/device or QR code scanner. You can also access the online SmartLine HUB page via the provided URL, which contains direct links to open SmartLine product documentation.
Features and Options
The RMA801 Remote Indicator provides a means of remote-mounting an indicator (display) associated with a Honeywell Smartline Transmitter or any transmitter operating in a 4-20 mA current loop. The RMA801 is a DE/Analog Remote Indicator that can be connected anywhere along the current loop.
For analog PV, the RMA801 measures the loop current and displays the equivalent PV value. The RMA801 will auto-configure when connected to Honeywell DE transmitters (except SMV800/3000) when a database upload is performed.
This document provides information for a quick setup. For detailed information, please refer to the RMA801 user manual (34-ST-25-62).
Figure 1: Electronics Housing Components shows the standard cover, display module choices, communication modules, and the DE/ANALOG terminal block.
Installation and Setup
Site Evaluation
Evaluate the selected site for the Remote Indicator installation with respect to the process system design specifications and Honeywell's published performance characteristics for your particular model. Refer to the RMA801 user manual (#34-ST-25-62) for site evaluation parameters.
Installation Precautions
Temperature extremes can affect display quality. The display may go blank if the temperature is below -20°C or above +70°C, but this is a temporary condition, and the display will become readable again when temperatures return to operable limits.
CAUTION: The device shall be operated by a trained professional. It is the user/installer's responsibility to install the indicator in accordance with national and local code requirements. Conduit entry plugs and adapters must be suitable for the environment, certified for the hazardous location when required, and acceptable to the authority having jurisdiction for the plant.
The RMA device is always connected in series with the transmitter. The current loop will be broken if the RMA801 device is removed from the loop.
Explosion-Proof Conduit Seal
WARNING: When installed as explosion-proof in a Division 1 Hazardous Location, keep covers tight while the Remote Indicator is energized. Disconnect power to the Remote Indicator in the non-hazardous area prior to removing end caps for service.
When installed as non-incendive equipment in a Division 2 hazardous location, disconnect power to the Remote Indicator in the non-hazardous area, or determine that the location is non-hazardous before disconnecting or connecting the Remote Indicator wires.
Mounting Remote Indicator
SmartLine Remote Indicator models can be attached to a two-inch (50.8 mm) vertical or horizontal pipe using Honeywell's optional pipe mounting bracket. Honeywell's optional wall mounting bracket is also available.
Mounting Dimensions
Refer to Honeywell drawing numbers for detailed dimensions: 51455045 (electronic housing), 32306827 (pipe mounting), 50124813 (pipe angle mounting), and 32306828 (wall mounting). The transmitter enclosure can be rotated a total of 90° from the standard mounting position.
Bracket Mounting
Pipe Mount Option: Align the two mounting holes at the bottom of the Remote Indicator with the two slots in the mounting bracket and assemble the provided M8 hex cap screws, lock washers, and flat washers. Rotate the assembly to the desired position and torque the M8 hex cap screws to a maximum of 27.0 Nm (20.0 Lb-ft). Position the bracket on a 2-inch (50.8 mm) horizontal or vertical pipe and install a "U" bolt around the pipe through the bracket holes. Secure the bracket with the provided M10 hex nuts, flat washers, and lock washers. (See Figure 2, 3, and 4).
Wall Mount Option: Position the bracket on the mounting surface at the desired location and secure it using appropriate hardware (wall mounting hardware to be determined and supplied by the end user). (See Figure 5).
Wiring a Remote Indicator
Overview
The Remote Indicator operates in normal 4-20mA analog mode with HART enabled transmitters across Smartline Devices and DE transmitters (except SMV800/3000). For improved noise performance, it is recommended to provide earth ground for both the transmitter and RMA housing.
Terminal Block
The RMA801 has 3 terminals: Terminal 5 (Loop +ve), Terminal 6 (Loop -ve), and Terminal 9 (DE COMM). Three screw terminals are suitable for wiring up to 16 AWG.
Shielded, twisted-pair cable (e.g., Belden 9318 or equivalent) must be used for all signal/power wiring. The cable shield must be connected at only one end of the cable, preferably at the power supply side, leaving the shield insulated at the transmitter and RMA sides.
Note: If solid core wire is used, strip insulation 1/4 in (6 mm). If multi-stranded wire is used, a ferrule should be used. Loop Terminals 5 & 6 must be connected in series with the 4-20 mA loop for both analog and DE modes. Terminal 9 is required for DE communication in DE mode only.
Loop wiring for analog and DE mode is shown in the figures. After wiring, torque the screws to 1.1 Nm (10 lb-in).
Figure 6: DE/ANALOG Terminal Block and Figure 7: RMA801 Terminal Block illustrate the terminal connections.
Figure 8, 9, and 10 show the wiring options for connecting the Remote Indicator to the loop.
Wiring Connections and Power Up
Ensure the following power supply constraint is met: Vs,Min = 2.3V + VTxer,Min + (Rloop * Imax/1000), where Vs. Min is minimum supply voltage, VTxer,Min is Transmitter Minimum supply voltage at terminals, Rloop is loop resistance in ohms, and Imax is High failSafe/Burnout current in mA.
ATTENTION: For all wiring options, ensure the RMA chassis ground terminal is connected to earth ground. Connect the Loop Power shield to earth ground at the power supply end, not at the RMA end. The shield must be continuous from the transmitter through the RMA to the power supply.
Note: The resistor "R" indicates the loop resistor needed for HART and DE communication, typically provided by the user or control system.
Device Configuration
Once the loop is powered, the RMA will turn on with a scrolling message "SmartLine" on the display. For DE devices, the RMA is auto-configured. For any DE configuration change in the transmitter, a database upload must be performed to reflect the changes in the RMA.
To configure the device, open the front cover and use the 'Menu' and 'Enter' key buttons on the display. The following parameters can be configured:
SNO | MENU | Parameters | Description |
---|---|---|---|
1 | SEL PV | Select Process Variable | (temperature, pressure, flow, Level, loop out, % out) |
2 | UNIT | Select Engineering Unit | Units are visible as per PV selection |
3 | C UNIT | Enter required customized unit | (String) |
4 | ENTLRV | Enter Lower Range Value | (Numeric Value) |
5 | ENTURV | Enter Upper Range Value | (Numeric Value) |
6 | CAL Lo | Input Calibration Low Point | (Applicable in Analog Mode only) |
7 | CAL Hi | Input Calibration High Point | (Applicable in Analog Mode only) |
8 | B UNIT | Select Engineering Base Unit of Transmitter | Base Units visible as per PV selection (Applicable in Analog Mode only) |
9 | CNTRST | Set LCD Contrast | |
10 | RMA DG | RMA Diagnostic Messages | See manual for details of diagnostic messages |
11 | SQRT | Select Square Root | (Disable, Enable) |
12 | SCLLO | Enter Scaling Low Value | (Numeric Value) |
13 | SCLHI | Enter Scaling High Value | (Numeric Value) |
14 | RBoot | Reboot the Remote Indicator Assembly | |
15 | TAG | Displays Tag | (Read only) |
16 | FW VER | Firmware Version | |
EXIT | EXIT Menu |
Engineering Units include various options for Temperature (°C, °F, °R, K, mV, Ohm), Pressure (inH2O, mH2O, cmH2O, Torr, mmH2O, ftH2O, atm, Pa, kPa, MPa, gf/cm2, kgf/cm2, psi, mbar, bar, inHg, mmHg), Flow (CFS, GPM, GPH, LPM, LPH, M3/s, M3/hr, Lb/s, Lb/min, Lb/hr, Kg/s, Kg/hr, SCFM, SCFH, SCFD, MSCFH, NM3/hr, MMSCFD, MMSCFH), and Level (m, cm, mm, in, ft).
Appendix A. PRODUCT CERTIFICATIONS
A1 European Directive Information (CE Mark)
The RMA800 SmartLine Remote Indicator Series EU Declaration of Conformity (Document #32302406) can be downloaded.
A2. Hazardous Locations Certifications
This section details certifications for various hazardous locations, including Flame-proof, Dust, Intrinsically Safe, and Non-Incendive classifications across different regions and standards (e.g., CX, INMETRO, ATEX, IECEx, NEPSI, CCoE/PESO, SAEX, CCSAus).
Notes:
- 1. Operating Parameters: Input: 4-20 mA; 42 VDC max, 30 mA
- 2. Intrinsically Safe Entity Parameters: For details, see Control Drawing, 50089981.
A3 Conditions of Use for Ex Equipment
- Consult the manufacturer for dimensional information on flameproof joints for repair.
- Painted surfaces of the RMA 800 series may store electrostatic charge. Cleaning should only be done with a damp cloth.
- Ambient temperature range, maximum process temperature, and applicable temperature class: RMA801: T4 for -50°C < Ta < 85°C; RMA803: T4 for -20°C < Ta < 70°C.
- The RMA800 series enclosure contains aluminum and may present an ignition risk by impact or friction. Care must be taken during installation and use.
- If a charge-generating mechanism is present, implement precautions to prevent electrostatic charge buildup, e.g., earthing the metallic part.
- On installation, the RMA800 series must be provided with supply transient protection external to the apparatus such that the voltage at the supply terminals does not exceed 140% of the voltage rating of the equipment.
A4 Control Drawing
This section provides control drawing information for Analog, DE Communications, and Foundation Fieldbus, including intrinsically safe installation requirements, entity parameters, and system entity parameters. It details connections for hazardous and non-hazardous locations.
A.4 Marking ATEX Directive
- General: Provides information on manufacturer name, serial number, and year/week of manufacture.
- Apparatus Marked with Multiple Types of Protection: The user must determine and check the type of protection used on the equipment certification nameplate.
- WARNINGS and Cautions: Includes warnings for explosion hazards, substitution of components, and opening the device when an explosive gas atmosphere is present or when energized.
- General Requirements / Increased Safety (Zone 1): Warning to open circuit before removing the cover.
- All Protective Measures: Warning for connection in ambients above 60°C, use wire rated 105°C.
Sales and Service
For application assistance, current specifications, pricing, or the name of the nearest Authorized Distributor, contact one of the listed Honeywell offices for Asia Pacific, EMEA, and Americas.
Knowledge Base search engine: http://bit.ly/2N5Vldi
Warranty/Remedy
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the coverage period, Honeywell will repair or replace defective items without charge. This is the Buyer's sole remedy and is in lieu of all other warranties. Specifications may change without notice. Honeywell assumes no responsibility for the use of the information provided.
Contact Information
For more information about SmartLine Devices, visit https://process.honeywell.com or contact your Honeywell Account Manager.
Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042
Honeywell Control Systems Ltd
Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB
Shanghai City Centre
100 Jungi Road
Shanghai, China 20061
Document: 34-ST-25-63, Rev.7, February 2022
©2022 Honeywell International Inc.