1- Warnings

2- Installation

D141H232 Ed.0 en
Installation instructions
AKO-D14120 AKO-D14123 AKO-D14012 AKO-D14023 AKO-D14023-C AKO-D14024 AKO-D14124 AKO-D14125

-Using the equipment without following the manufacturer's instructions may affect the device's safety requirements. To ensure that the device operates correctly, only probes supplied by AKO should be used. -The unit must be installed in a location protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed that shown in the technical data. -To ensure a correct reading, the probe must be situated in a location without any external heat influences except for the temperature which is being measured or controlled. -The power supply circuit must be provided with a main switch rated at at least 2A, 230V, located close to the equipment.The cables will enter through the back and should be type H05VV-F or H05V-K. -The gauge will depend on local regulations, but should in no case be less than 1 mm2. -Connecting wires for the relay contacts should be sized 2.5 mm2. -Between -40 ºC and +20 ºC, if the probe NTC is prolonged till 1.000 m with a mínimum of cable 0,5 mm², the maximum deviation will be of 0,25 ºC (extension cable for probe ref. AKO-15586) NOTE: Equipment not compatible with AKO-14917 (external communication module) and AKO-14918 (programming key).

71mm

3- Wiring
The probe and its cable should NEVER be installed in the same conduit as power, control or supply cables.

AKO-D14123, AKO-D14124, AKO-D14125

Mode: HEAT (P0=1)

16 A

I max.: 16 A LN

Mode: COLD (P0=0)

16 A

123456

123456

230 V~ 50/60 Hz

Probe 1 RES.

5203/600VH~z

Probe 1 COOL

I max.: 16 A LN

Mode: HEAT (P0=1)

16 A

AKO-D14120

I max.: 16 A LN

Mode: COLD (P0=0)

16 A

123456

123456

120 V~ 50/60 Hz

Probe 1 RES.

120 V~ 50/60 Hz

Probe 1 COOL

I max.: 16 A LN

AKO-D14023, AKO-D14024

AKO-D14012

Modbus
12 13 14 15

AKO-D14023-C

123456

5203/600VH~z

Probe 1

4- Operation
3 key equipment
Program Mode

Display COOL relay ON (P0=0)

123456
12 V ~_
Probe 1
24 V ~_ 1 key equipment
Program Mode

Display

1234

5 6 7 8 9 10 11

90-240 V~ Probe 1 50/60 Hz

5.1- Access to set point and programming

3 key equipment

5 sec.

10 sec.

t

SET Keyboard

Standby mode

RES relay active (P0=1)

SET key
Press for 5 seconds to modify the set point (SP). Press for 10 seconds to go to the programming menu. In the programming menu, go to the level displayed or accept the new value while setting a parameter.
Up key N / H
Pressing for 5 seconds starts/stops defrosting. In programming menu, allows you to scroll through the various levels or, during the setting of a parameter, to change the value.
Down key Q / m
Pressing for 5 seconds activates Standby mode, pressing for 2 seconds returns the equipment to normal mode. In Standby mode, the equipment performs no actions and only the m indicator is displayed on the screen. In programming menu, allows you to scroll through the various levels or, during the setting of a parameter, to change the value.

SET

SET key / m

Standby mode

SET key / m
Pressing for 5 seconds activates Standby mode, pressing for 2 seconds returns the equipment to normal mode. In Standby mode, the equipment performs no actions and only the m indicator is displayed on the screen. Pressing for 10 seconds goes to the programming menu. Pressing for 5 seconds in the programming menu goes to the level displayed on the screen or, during the setting of a parameter, accepts the new value. In the programming menu, a short press allows you to scroll through the various levels or, during the setting of a parameter, to increment the value. When upper limit is reached, it will start again from the lower limit.
5- Start-up

(Only 3 key models)

On power-up, the equipment will start up in Wizard mode (P3 / 1 flashing), press N or Q to select the most appropriate application and press SET.

1: Multipurpose 4: Fresh fish 7: AC

2: Frozen

3: Fruits and vegetables

5: Soft Drinks 6: Bottle racks

8: Heat / Incubators

The wizard will configure the parameters of the equipment for the chosen application (see table "Default settings by application").

35D141232 REV.04 2024

www.ako.com ako@ako.com

Av. Roquetes, 30-38 08812 Sant Pere de Ribes Barcelona (España)

Tel. (34) 938 142 700 Fax (34) 938 934 054

Temperature Indication

Release SET to access
the set point

Release SET to access
programming

1 key equipment

5 sec.

10 sec.

t

SET

Temperature Indication

Release SET to go to Stand-by

Release SET to access
programming

AKO ELECTROMECÀNICA, S.A. We reserve the right to supply materials which may be slightly different from those described in our Data Sheets. Updated information on our web site: www.ako.com

5.2- Setting parameters

Programming Menu (parameters) After 20 seconds with no key being pressed, the equipment will return to the previous level. If you are on level 3, the changes will not be saved

3 KEY EQUIPMENT

1 KEY EQUIPMENT

OUT OF PROGRAMMING

PROGRAMMING 20 sec.

20 sec.

20 sec.

OUT OF PROGRAMMING

PROGRAMMING 20 sec.

20 sec.

20 sec.

10 sec.
SET
Temperature Indication
OK
SET

Change Menu OK
SET
Level 1 Menu
OK
SET

Change param. OK
SET
Level 2 Parameters

Level 3 Values

Change value OK
SET

10 sec.
SET
Temperature Indication OK
SET
> 5sec.

Change Menu OK

Change param. OK

Level 1 Menu

SET

SET

< 5sec. > 5sec.

SET
Level 2 < 5sec. Parameters

SET
> 5sec.

OK

SET
Key pressed several times

SET
> 5sec.

SET
Key pressed several times

Change set point (only equipment with three keys)

5 sec.

Change value

SET
Temperature Indication

Current Value

New Value

Accept value and Esc.
SET
Temperature Indication

Change value OK

Level 3 Values

SET

SET

< 5sec. > 5sec.

6- Table of parameters and messages
Def. column shows factory-set default parameters. Those marked with * are variable parameters depending on the application chosen in the wizard or the P3 parameter (see table "Default parameters by application"). Unless otherwise stated, temperatures are expressed in °C. (Equivalent velues in °F)

AKO-D14023-C

AKO-D14012, AKO-D14023, AKO-D14024

AKO-D14120, AKO-D14123, AKO-D14124, AKO-D14125

Level1

Menus and description

rE Level 2

Control

Level 3 Description

Values

SP

Temperature Adjustment (Set Point) (limits depending on probe type)

With NTC (ºC/ºF)
With PTC

C0 Calibrating probe 1 (Offset) C1 Probe 1 differential (Histeresis)

(ºC/ºF) (ºC/ºF)

C2

Upper blocking of the set point (cannot be set above this value)

With NTC (ºC/ºF)
With PTC

Min. Def. Max.

-50

99 (210ºF)

·

(-58ºF)

-

150 (302ºF)

·

-20.0 0.0 20.0 · · ·

0.1 2.0 20.0 ·

C3

99 (210ºF)

99 (210ºF)

·

-

150 (302ºF)

·

C3 Lower blocking of the set point (cannot be set below this value)

(ºC/ºF)

-50 -50 (-58ºF) (-58ºF)

C2

·

Type of delay for protection of the compressor: C4 0=OFF/ON (since the last disconnection);1=ON (since start-up/reset);
2=OFF-ON/ON-OFF (since the last shut-down /start-up)

0 0 2·

C5 Protection delay time (value of the option selected in parameter C4) Status of COOL relay with probe fault
C6 0=OFF;1=ON;2=Average based on last 24 hours prior to probe fault; 3=ON-OFF as prog. C7 and C8

(min.) 0 0 120 · 0 0 3·

C7

Time relay ON in case of faulty probe (If C7=0 and C8¹0, the relay will always be OFF deenergised)

(min.) 0 10 120 ·

C8

Time relay OFF in case of fault of probe 1 (If C8=0 and C7¹0, the relay will always be ON energised)

EP Exit to Level 1

dEF Level 2

DEFROST Control (if P0=0 Direct, Cold)

Level 3 Description

d0

Defrost frequency (Time between two starts)

(min.) 0 5 120 · ···

Values Min. Def. Max.

(h.)

0

96 ·

d1 Maximum defrost duration (0=defrost deactivated)

(min.) 0

255 ·

Type of message during defrost: d2 0=Current temperature;1=Temperature at start of defrost;
2=Display dEF message

0 2 2·

d3

Maximum duration of message (time added at the end of the defrost)

(min.) 0 5 255 ·

d8

Calculated time between defrost periods: 0=Total actual time; 1 =Sum of times the compressor is on

EP Exit to Level 1

CnF Level 2

General status

Level 3 Description

P0 Type of operation 0=Direct,Cold;1=Inverted,Heat

P1 Delay of all functions on receiving electrical power

P2

Access code (password) functions 0=Inactive; 1=Block access to parameters; 2=Keyboard lock

0 0 1· ·

Values (min.)

Min. Def. Max.

0

1·

0 0 255 ·

0 0 2 ···

P5 Address (only systems with built-in communications)

P7 Temperature display mode

0= Integer °C 2=Integer °F

1=One decimal in ºC 3=One decimal in °F

1 1 255 · · · 0 1 3 ···

P9 Selection of probe type 0=NTC;1=PTC

EP Exit to Level 1

tid NLievveel l22

CAocncterossl AanccdeisnofoermInafotiromnaccoiónntrol

NLeivel 3

Descripctioón

L5 Access code (Password)

PU Program version (Information)

Pr Program revision (Information)

EP Exit to Level 1

EP Exit Programming

0 0 1 ··· ···

Valoueress Míin. Def. Máax.

0 - 99 · · ·

-

···

-

···

···

···

WARNING: The default parameters by type of application have been defined for the most common applications. Check that these parameters are suitable for your installation.

DEFAULT SETTINGS BY APPLICATION (P3)

1 Multipurpose

2 Frozen

3 Fruit and Vegetables

4 Fresh Fish

SP 2 (35,6ºF) -18 (-0,4ºF) 10 (50ºF)

0 (32ºF)

d0

4

4

4

4

d1

20

20

20

20

P0

0

0

0

0

5 Soft Drinks
3 (37,4ºF) 24 20 0

6 Bottle Racks
12 (53,6ºF) 24 20 0

7 AC
21 (69,8ºF) 96 0 0

8 Heat/ Incubators 37 (98,6ºF)
-
1

MESSAGES

L5 Access code (Password) request

dEF Indicates a defrost is underway.(Only if parameter d2=2)

E1

Probe 1 faulty (open circuit, crossover, NTC: temp. >110°C or <-55 °C PTC: temp. >150 °C or <58 °C) - (equivalent limits in °F)

D: Displays the message on the display S: Shows the message in the AKONet software (Only AKO-D14023-C)

D D-
DS

7- Technical specifications

Power supply AKO-D14023/D14024/D14123/D14124/D14125 . 230V~ ±10 % 50/60 Hz 3.5VA

AKO-D14120. . . . . . . . . . . . . . . . . . . . . . . . . . . . 120V~ +8 % - 12 % 50/60 Hz 4VA

AKO-D14023-C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90-240V ~ 50/60 Hz 6VA

AKO-D14012 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12/24V ~­ ±20% 2.5VA

MaximumVoltage SELV circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20V

Comunication (OnlyAKO-D14023-C). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modbus RTU RS485

Inputs (According to P4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 NTC/PTC

Relay COOL 16A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (EN60730-1: 12(9)A 250V~)

Number of relay operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN60730-1: 100.000 operations

Types of probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NTC AKO-149xx / PTC AKO-1558xx

Measurement range NTC. . . . . . . . . . . . . . . . . . . . . . . . . . . . -50,0 ºC to +99,9 ºC (-58,0 ºF to 211 ºF)

PTC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50,0 ºC to +150 ºC (-58,0 ºF to 302 ºF)

Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0,1 ºC

Working environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -10 to 50 ºC, humidity <90 %

Ambient storage humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 to 70 ºC, humidity <90 %

Class of protection - front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP65

Fixation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Panel-mounted with anchors

Panel cutout dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 x 29 mm

Front panel dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 x 38 mm

Depth

AKO-D14023-C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 mm

Other models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 mm

Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Screw terminals for cables up to 2.5 mm²

Rating of control device: built-in, automatic operation feature Type 1.B, for use in clean environments,

Class A software and continuous operation. Pollution classification 2 s/ UNE-EN 60730-1.

Double insulation between supply, secondary circuit and relay output.

Rated pulse voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2500V

Temperature during ball-pressure test Accessible parts . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC

Parts which position active elements . . . . . . . . . . . . 125 ºC

Voltage and current as per EMC tests

AKO-D14023/D14023-C/D14024/

AKO-D14123/D14124/D14125/ . . . . . . . . . 207V, 17 mA

AKO-D14120 . . . . . . . . . . . . . . . . . . . . . . . . 105V, 36 mA

AKO-D14012 . . . . . . . . . . . . . . . . . . . . . . . 9,6V, 181 mA

Current of radio jamming supression tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 mA

