[PDF] Emergency lighting units EM powerLED

Product description. Fixed output LED driver for mains operation. Emergency lighting LED driver with manual test function.


File Info : application/pdf, 15 Pages, 1.11MB

PDF preview unavailable. Download the PDF instead.

EM powerLED BASIC FX lp 75 W 28856
Emergency lighting units EM powerLED
EM powerLED BASIC FX lp 75 W Combined emergency lighting LED driver

Product description _ Fixed output LED driver for mains operation _ Emergency lighting LED driver with manual test function _ For self-contained emergency lighting _ For LED modules with a forward voltage of 50 ­ 220 V _ For luminaire installation _ Low profile cross-section (21 x 30 mm) _ EM = Emergency _ 5 years guarantee (conditions at
https://www.tridonic.com/manufacturer-guarantee-conditions)
Properties _ 6 ­ 75 W output power _ Constant current LED operation _ Adjustable output current between 100 and 400 mA via
ready2mains Programmer or I-SELECT 2 plugs _ Integrated emergency lighting unit _ 1 or 3 h rated duration _ Automatic shutdown of output if LED load is out of range _ Green charge status display LED _ Electronic charge system _ Polarity reversal protection for battery _ Deep discharge protection _ Short-circuit-proof battery connection
Batteries _ High-temperature cells _ NiCd or NiMH batteries _ D, Cs or LAL cells _ 4 year design life _ 2 years guarantee (conditions at
https://www.tridonic.com/manufacturer-guarantee-conditions) _ For battery compatibility refer to data sheet, battery selection
Website http://www.tridonic.com/89800598

Spotlights Downlights

Linear

ADrattiacleshineefotr0m4a/t2io5-nE0M40/8253-15 SSuubbjjeecctt ttoo cchhaannggee wwiitthhoouutt nnoottiiccee..

Area

Floor | Wall Free-standing

Street

Decorative

High bay

www.tridonic.com

1

Emergency lighting units EM powerLED
EM powerLED BASIC FX lp 75 W Combined emergency lighting LED driver

21

5

6
side fixing feature 350
tc 110
360

Ø4,1

4,1

15 30

Ordering data
Type EM powerLED BASIC FX 213 lp 75W 220V EM powerLED BASIC FX 214 lp 75W 220V EM powerLED BASIC FX 215 lp 75W 220V EM powerLED BASIC FX 233 lp 75W 220V EM powerLED BASIC FX 234 lp 75W 220V EM powerLED BASIC FX 235 lp 75W 220V

Article number 89800598 89800599 89800600 89800601 89800602 89800603

Rated duration 1h 1h 1h 3h 3h 3h

Number of cells 3 4 5 3 4 5

Technical data

Rated supply voltage AC

220 ­ 240 V

AC voltage range

198 ­ 264 V

Mains frequency Typ. rated current (at 230 V, 50 Hz, full load) 1 Leakage current (at 230 V, 50 Hz, full load) 1

50 / 60 Hz 380 mA < 250 µA

Max. input power

85 W

Typ.  (at 230 V, 50 Hz, normal operation)

0.98

Overvoltage protection

320 V (for 48 h)

Battery charging time

< 24 h

U-OUT (including open- / short-circuit and double load) 280 V

Typ. input current in no-load operation 1 hr (charging) 16 mA

Typ. input current in no-load operation 3 hr (charging) 18 mA

Typ. input power in no-load operation 1 hr (charging) 2 W

Typ. input power in no-load operation 3 hr (charging) 2.4 W

In-rush current (peak / duration) THD (at 230 V, 50 Hz, full load) 1

26 A / 280 µs < 10 %

Starting time

< 0.5 s from detection of emergency event

Starting time (mains off)

< 1.3 s

Starting time (stand-by)

< 250 ms

Turn off time (at 230 V, 50 Hz, full load)

< 50 ms

Output LF current ripple (< 120 Hz)

<5%

Output current tolerance

5%

Ambient temperature ta

-5 ... +50 °C

Max. casing temperature tc

75 °C

Mains surge capability (between L - N)

1 kV

Mains surge capability (between L/N - PE)

2 kV

Surge voltage at output side (against PE)

2 kV

Dimensions L x W x H

360 x 30 x 21 mm

Mains voltage changeover threshold

According to EN 60598-2-22

Type of protection

IP20

Lifetime

up to 50,000 h

Guarantee (conditions at www.tridonic.com)

5 Year(s)

Approval marks

Packaging, carton 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

Packaging, pallet 600 pc(s). 600 pc(s). 600 pc(s). 600 pc(s). 600 pc(s). 600 pc(s).

Weight per pc. 0.245 kg 0.245 kg 0.245 kg 0.245 kg 0.245 kg 0.245 kg

ADrattiacleshineefotr0m4a/t2io5-nE0M40/8253-15

SSuubbjjeecctt ttoo cchhaannggee wwiitthhoouutt nnoottiiccee..

www.tridonic.com

2

Emergency lighting units EM powerLED
Standards EN 61347-1, EN 61347-2-13, EN 61347-2-7, EN 62384, EN 55015, EN 61547, EN 61000-3-2, EN 60068-2-29, EN 60068-2-30, EN 60068-2-64, according to EN 50172, according to EN 60598-2-22

ADrattiacleshineefotr0m4a/t2io5-nE0M40/8253-15

SSuubbjjeecctt ttoo cchhaannggee wwiitthhoouutt nnoottiiccee..

www.tridonic.com

3

Emergency lighting units EM powerLED
Specific technical data

Type Number of battery cells Output current23 Min. output voltage4 Max. output voltage4 Output power Typ. power consumptio n (at 230 V, 50 Hz, full load) Typ. current consumptio n (at 230 V, 50 Hz, full load)  (at 230 V, 50 Hz, full load) I-SELECT resistor value5

Normal operation

EM powerLED BASIC FX 213 lp 75W 220V EM powerLED BASIC FX 213 lp 75W 220V EM powerLED BASIC FX 213 lp 75W 220V EM powerLED BASIC FX 213 lp 75W 220V EM powerLED BASIC FX 213 lp 75W 220V EM powerLED BASIC FX 213 lp 75W 220V EM powerLED BASIC FX 213 lp 75W 220V EM powerLED BASIC FX 213 lp 75W 220V

­

80 mA

75 V 220 V 20.0 W

20 W

100 mA

­

100 mA 50 V 220 V 33.0 W

27 W

135 mA

­

150 mA 50 V 220 V 33.0 W

37 W

170 mA

­

200 mA 50 V 220 V 44.0 W

49 W

220 mA

­

250 mA 50 V 220 V 55.0 W

60 W

270 mA

­

300 mA 50 V 220 V 66.0 W

71 W

320 mA

­

350 mA 50 V 214 V 75.0 W

82 W

360 mA

­

400 mA 50 V 188 V 75.0 W

82 W

370 mA

0.85C 0.90C 0.95 0.95 0.97 0.97 0.98 0.98

­ 50.00 k 33.33 k 25.00 k 20.00 k 16.67 k 14.29 k 0.00 k

EM powerLED BASIC FX 214 lp 75W 220V EM powerLED BASIC FX 214 lp 75W 220V EM powerLED BASIC FX 214 lp 75W 220V EM powerLED BASIC FX 214 lp 75W 220V EM powerLED BASIC FX 214 lp 75W 220V EM powerLED BASIC FX 214 lp 75W 220V EM powerLED BASIC FX 214 lp 75W 220V EM powerLED BASIC FX 214 lp 75W 220V

­

80 mA

75 V 220 V 20.0 W

20 W

100 mA

­

100 mA 50 V 220 V 33.0 W

27 W

135 mA

­

150 mA 50 V 220 V 33.0 W

37 W

170 mA

­

200 mA 50 V 220 V 44.0 W

49 W

220 mA

­

250 mA 50 V 220 V 55.0 W

60 W

270 mA

­

300 mA 50 V 220 V 66.0 W

71 W

320 mA

­

350 mA 50 V 214 V 75.0 W

82 W

360 mA

­

400 mA 50 V 188 V 75.0 W

82 W

370 mA

0.85C 0.90C 0.95 0.95 0.97 0.97 0.98 0.98

­ 50.00 k 33.33 k 25.00 k 20.00 k 16.67 k 14.29 k 0.00 k

EM powerLED BASIC FX 215 lp 75W 220V EM powerLED BASIC FX 215 lp 75W 220V EM powerLED BASIC FX 215 lp 75W 220V EM powerLED BASIC FX 215 lp 75W 220V EM powerLED BASIC FX 215 lp 75W 220V EM powerLED BASIC FX 215 lp 75W 220V EM powerLED BASIC FX 215 lp 75W 220V EM powerLED BASIC FX 215 lp 75W 220V

­

80 mA

75 V 220 V 20.0 W

20 W

100 mA

­

100 mA 50 V 220 V 33.0 W

27 W

135 mA

­

150 mA 50 V 220 V 33.0 W

37 W

170 mA

­

200 mA 50 V 220 V 44.0 W

49 W

220 mA

­

250 mA 50 V 220 V 55.0 W

60 W

270 mA

­

300 mA 50 V 220 V 66.0 W

71 W

320 mA

­

350 mA 50 V 214 V 75.0 W

82 W

360 mA

­

400 mA 50 V 188 V 75.0 W

82 W

370 mA

0.85C 0.90C 0.95 0.95 0.97 0.97 0.98 0.98

­ 50.00 k 33.33 k 25.00 k 20.00 k 16.67 k 14.29 k 0.00 k

EM powerLED BASIC FX 233 lp 75W 220V EM powerLED BASIC FX 233 lp 75W 220V EM powerLED BASIC FX 233 lp 75W 220V EM powerLED BASIC FX 233 lp 75W 220V EM powerLED BASIC FX 233 lp 75W 220V EM powerLED BASIC FX 233 lp 75W 220V EM powerLED BASIC FX 233 lp 75W 220V EM powerLED BASIC FX 233 lp 75W 220V

­

80 mA

75 V 220 V 20.0 W

20 W

100 mA

­

100 mA 50 V 220 V 33.0 W

27 W

135 mA

­

150 mA 50 V 220 V 33.0 W

37 W

170 mA

­

200 mA 50 V 220 V 44.0 W

49 W

220 mA

­

250 mA 50 V 220 V 55.0 W

60 W

270 mA

­

300 mA 50 V 220 V 66.0 W

71 W

320 mA

­

350 mA 50 V 214 V 75.0 W

82 W

360 mA

­

400 mA 50 V 188 V 75.0 W

82 W

370 mA

0.85C 0.90C 0.95 0.95 0.97 0.97 0.98 0.98

­ 50.00 k 33.33 k 25.00 k 20.00 k 16.67 k 14.29 k 0.00 k

EM powerLED BASIC FX 234 lp 75W 220V EM powerLED BASIC FX 234 lp 75W 220V EM powerLED BASIC FX 234 lp 75W 220V EM powerLED BASIC FX 234 lp 75W 220V EM powerLED BASIC FX 234 lp 75W 220V EM powerLED BASIC FX 234 lp 75W 220V EM powerLED BASIC FX 234 lp 75W 220V EM powerLED BASIC FX 234 lp 75W 220V

­

80 mA

75 V 220 V 20.0 W

20 W

100 mA

­

100 mA 50 V 220 V 33.0 W

27 W

135 mA

­

150 mA 50 V 220 V 33.0 W

37 W

170 mA

­

200 mA 50 V 220 V 44.0 W

49 W

220 mA

­

250 mA 50 V 220 V 55.0 W

60 W

270 mA

­

300 mA 50 V 220 V 66.0 W

71 W

320 mA

­

350 mA 50 V 214 V 75.0 W

82 W

360 mA

­

400 mA 50 V 188 V 75.0 W

82 W

370 mA

0.85C 0.90C 0.95 0.95 0.97 0.97 0.98 0.98

­ 50.00 k 33.33 k 25.00 k 20.00 k 16.67 k 14.29 k 0.00 k

EM powerLED BASIC FX 235 lp 75W 220V EM powerLED BASIC FX 235 lp 75W 220V EM powerLED BASIC FX 235 lp 75W 220V EM powerLED BASIC FX 235 lp 75W 220V EM powerLED BASIC FX 235 lp 75W 220V EM powerLED BASIC FX 235 lp 75W 220V EM powerLED BASIC FX 235 lp 75W 220V EM powerLED BASIC FX 235 lp 75W 220V

­

80 mA

75 V 220 V 20.0 W

20 W

100 mA

­

100 mA 50 V 220 V 33.0 W

27 W

135 mA

­

150 mA 50 V 220 V 33.0 W

37 W

170 mA

­

200 mA 50 V 220 V 44.0 W

49 W

220 mA

­

250 mA 50 V 220 V 55.0 W

60 W

270 mA

­

300 mA 50 V 220 V 66.0 W

71 W

320 mA

­

350 mA 50 V 214 V 75.0 W

82 W

360 mA

­

400 mA 50 V 188 V 75.0 W

82 W

370 mA

0.85C 0.90C 0.95 0.95 0.97 0.97 0.98 0.98

­ 50.00 k 33.33 k 25.00 k 20.00 k 16.67 k 14.29 k 0.00 k

Emergency operation

EM powerLED BASIC FX 213 lp 75W 220V

3

­

50 V 220 V

2.5 W

­

­

­

­

EM powerLED BASIC FX 214 lp 75W 220V

4

­

50 V 220 V

3.5 W

­

­

­

­

EM powerLED BASIC FX 215 lp 75W 220V

5

­

50 V 220 V

4.5 W

­

­

­

­

EM powerLED BASIC FX 233 lp 75W 220V

3

­

50 V 220 V

2.5 W

­

­

­

­

EM powerLED BASIC FX 234 lp 75W 220V

4

­

50 V 220 V

3.5 W

­

­

­

­

EM powerLED BASIC FX 235 lp 75W 220V

5

­

50 V 220 V

4.5 W

­

­

­

­

1 Depending on the selected output current. 2 The table only lists a number of possible operating points but does not cover each single point. The output current can be set within the total value range in 1-mA-steps. Output current is mean value. 3 Output current is mean value. 4 Output voltage range defined in normal operation. 5 Not compatible with I-SELECT (generation 1). Calculated resistor value.

ADrattiacleshineefotr0m4a/t2io5-nE0M40/8253-15

SSuubbjjeecctt ttoo cchhaannggee wwiitthhoouutt nnoottiiccee..

www.tridonic.com

4

Emergency lighting units EM powerLED
Test switch EM2

Accessory

Product description _ For connection to the emergency lighting unit _ For checking the device function _ Dielectric strength: 1,500 V AC for 60 seconds

Website http://www.tridonic.com/89805277

Ordering data
Type Test switch EM 2

Article number 89805277

Packaging, bag 25 pc(s).

Packaging, carton 600 pc(s).

Weight per pc. 0.009 kg

Approval marks

Accessory

Status indication green LED EM

Product description
_ A green LED indicates that charging current is flowing into the battery

Ordering data
Type LED EM green LED EM green, ultra high brightness
Approval marks

Website http://www.tridonic.com/89899605

Article number 89899605 89899756

Packaging, bag 25 pc(s). 25 pc(s).

Packaging, carton 200 pc(s). 200 pc(s).

Weight per pc. 0.011 kg 0.012 kg

ADrattiacleshineefotr0m4a/t2io5-nE0M40/8253-15

SSuubbjjeecctt ttoo cchhaannggee wwiitthhoouutt nnoottiiccee..

www.tridonic.com

5

Emergency lighting units EM powerLED
I-SELECT 2 PLUG PRE / EXC

5,5

4,5

Accessory

Product description _ Ready-for-use resistor to set output current value _ Compatible with LED driver featuring I-select 2 interface; not
compatible with I-SELECT (generation 1) _ Resistor is base insulated _ Resistor power 0.25 W _ Current tolerance ± 2 % additional to output current tolerance _ Compatible with LED driver series PRE and EXC
Example of calculation _ R [k] = 5 V / I_out [mA] x 1000 _ E96 resistor value used _ Resistor value tolerance  1 %; resistor power  0.1 W; base
insulation necessary _ When using a resistor value beyond the specified range, the
output current will automatically be set to the minimum value (resistor value too big), respectively to the maximum value (resistor value too small)
Website http://www.tridonic.com/28001101

xxxx xxxx 7,5

9 13,5

Ordering data
Type I-SELECT 2 PLUG 125MA BL I-SELECT 2 PLUG 150MA BL I-SELECT 2 PLUG 200MA BL I-SELECT 2 PLUG 225MA BL I-SELECT 2 PLUG 250MA BL I-SELECT 2 PLUG 275MA BL I-SELECT 2 PLUG 300MA BL I-SELECT 2 PLUG 325MA BL I-SELECT 2 PLUG 350MA BL I-SELECT 2 PLUG 375MA BL I-SELECT 2 PLUG 400MA BL I-SELECT 2 PLUG MAX BL

3,5

Article number 28001101 28001102 28001104 28001105 28001106 28001107 28001108 28001109 28001110 28001111 28001112 28001099

Colour Blue Blue Blue Blue Blue Blue Blue Blue Blue Blue Blue Blue

Marking 0125 mA 0150 mA 0200 mA 0225 mA 0250 mA 0275 mA 0300 mA 0325 mA 0350 mA 0375 mA 0400 mA
MAX

Current 125 mA 150 mA 200 mA 225 mA 250 mA 275 mA 300 mA 325 mA 350 mA 375 mA 400 mA MAX

Resistor value 40.20 k 33.20 k 24.90 k 22.10 k 20.00 k 18.20 k 16.50 k 15.40 k 14.30 k 13.30 k 12.40 k 0.00 k

Packaging, bag 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s). 10 pc(s).

Weight per pc. 0.001 kg 0.001 kg 0.001 kg 0.001 kg 0.001 kg 0.001 kg 0.001 kg 0.001 kg 0.001 kg 0.001 kg 0.001 kg 0.001 kg

ADrattiacleshineefotr0m4a/t2io5-nE0M40/8253-15

SSuubbjjeecctt ttoo cchhaannggee wwiitthhoouutt nnoottiiccee..

www.tridonic.com

6

Emergency lighting units EM powerLED

Emergency lighting units EM powerLED

1. Standards
· EN 61347-1 · EN 61347-2-13 · EN 61347-2-7 · EN 62384 · EN 55015 · EN 61547 · EN 61000-3-2 · EN 60068-2-29 · EN 60068-2-30 · EN 60068-2-64 · according to EN 50172 · according to EN 60598-2-22

2. Thermal data

2.1 Expected Lifetime

Average lifetime 50,000 hours under rated conditions with a failure rate of less than 10 %. Average failure rate of 0.2 % per 1000 operating hours.

Expected lifetime Type
EM powerLED BASIC FX 2xx lp 75W 220V

Output power < 40 W
40 ­ 60 W > 60 ­ 75 W

ta tc Lifetime tc Lifetime tc Lifetime

40 °C 56 °C > 100,000 h 60 °C > 100,000 h 65 °C > 100,000 h

50 °C 66 °C 70,000 h 70 °C 60,000 h 75 °C 50,000 h

55 °C 71 °C 50,000 h
­ ­ ­ ­

The EM powerLED is designed for a lifetime stated above under reference conditions and with a failure probability of less than 10 %.

The relation of tc to ta temperature depends also on the luminaire design. If the measured tc temperature is approx. 5 K below tc max., ta temperature should be checked and eventually critical components (e.g. ELCAP) measured. Detailed information on request.

3. Installation / Wiring
3.1 Wiring diagrams
Wiring diagram EM powerLED BASIC FX without sensor
220­240 V 50/60 Hz L N

L N

EM powerLED BASIC

LED

+ ­

S/L

I-sel 2-1 I-sel 2-2

Test switch

Indication LED

Orange Pink

+ ­



Battery

­ +

The connected LED module will be used for mains and emergency operation.
The mains power must be removed before changing the LED load.
Secondary switching of LEDs is not allowed and may cause damage to the LEDs. The hot plug-in of LEDs during normal operation may result in high current peaks.

DDaatatashsehete1e0t/203-4EM/2058-3E-1M5 083-15 SSuubbjejcetctot cthoancgheawnitgheouwt nitohtioceu. Itnfnoormtiactieo.n provided without guarantee.

wwww.twrwid.tornidico.cnoicm.com

67

Emergency lighting units EM powerLED

Emergency lighting units EM powerLED

3.2 Wiring type and cross section

4. Mechanical data

Solid wire with a cross section of 0.5 ­ 1.5 mm². Strip 8 ­ 9 mm of insulation from the cables to ensure perfect operation of terminals.
LED module/LED Driver/supply
wire preparation: 0.5 ­ 1.5 mm²

4.1 Housing properties
· Low-profile metal casing with white cover · Type of protection IP 20
4.2 Mechanichal data accessories

8 ­ 9 mm
3.3 Loose wiring

LED status indicator · Green · Mounting hole 6.5 mm diameter, 1 ­ 1.6 mm thickness · Lead length 0.8 m · Insulation rating: 90 °C
Test switch · Mounting hole 7.0 mm diameter · Lead length 0.55 m

Loosen wire through twisting and pulling or using a Ø 1 mm release tool

Maximum lead length

LED

3 m

status indication LED

1 m

batteries

1 m

3.4 Wiring guidelines

Battery leads · Quantity: 1 red and 1 black · Length: 1.3 m · Wire type: 0.5 mm2 solid conductor · Insulation rating: 90 °C
Battery end termination Push on 4.8 mm receptacle to suit battery spade fitted with insulating cover or plug connection.
Module end termination 8.0 mm stripped insulation
Two-piece batteries are supplied with a 200 mm lead with 4.8 mm receptacle at each end and insulating covers to connect the separate sticks together.

· The output to the LED is DC but has high frequency content, which should be considered for good EMC compliance.
· LED leads should be separated from the mains connections and wiring for good EMC performance.
· Maximum lead length on the LED terminals is 3 m. For a good EMC performance keep the LED wiring as short as possible.
· The secondary wires (LED module) should be routed in parallel to ensure good EMC performance.
· Maximum lead length for the Test switch and Indicator LED connection is 1 m. The test switch and Indicator LED wiring should be separated from the LED leads to prevent noise coupling.
· Battery leads are specified with 0.5 mm cross section and a length of 1.3 m. · To avoid the damage of the control gear, the wiring must be protected against
short circuits to earth (sharp edged metal parts, metal cable clips, louver, etc.).

To ensure that a luminaire containing LED emergency units complies with EN 55015 for radio frequency conducted interference in both normal and emergency mode it is essential to follow good practice in the wiring layout.

Within the luminaire the switched and unswitched 50 Hz supply wiring must be routed as short as possible and be kept as far away as possible from the LED leads.Through wiring may affect the emc performance of the luminaire.

The length of LED leads must not be exceeded.

The output current depends on the forward voltage and the tolerance of the LED modules.

DDaatatashsehete1e0t/203-4EM/2058-3E-1M5 083-15 SSuubbjejcetctot cthoancgheawnitgheouwt nitohtioceu. Itnfnoormtiactieo.n provided without guarantee.

wwww.twrwid.tornidico.cnoicm.com

78

Emergency lighting units EM powerLED

Emergency lighting units EM powerLED

5. Electrical values

5.1 Maximum loading of automatic circuit breakers

Automatic circuit breaker type Installation Ø EM powerLED BASIC FX 2xx lp 75W 220V

C10 1.5 mm2
12

C13 1.5 mm2
18

C16 2.5 mm2
24

C20 2.5 mm2
28

Calculation uses typical values from ABB series S200 as a reference. Actual values may differ due to used circuit breaker types and installation environment.

B10 1.5 mm2
6

B13 1.5 mm2
9

B16 2.5 mm2
12

B20 2.5 mm2
14

Inrush current

I
max
25.8 A

time 280 µs

5.2 Insulation matrix

Mains

Mains

­

Switched Live

·

Battery, LED, Test · ·
switch, Indicator LED

I-SELECT 2

·

· Represents basic insulation · · Represents double or reinforced insulation

Switched Live · ­ · · ·

Battery, LED, Test switch, Indicator LED
· · · · ­ · ·

I-SELECT 2 · · · · ­

Insulate the battery, LED, test switch and indicator LED in the luminaire according to the U-OUT rating of the LED Driver.

DDaatatashsehete1e0t/203-4EM/2058-3E-1M5 083-15 SSuubbjejcetctot cthoancgheawnitgheouwt nitohtioceu. Itnfnoormtiactieo.n provided without guarantee.

wwww.twrwid.tornidico.cnoicm.com

89

Emergency lighting units EM powerLED

Emergency lighting units EM powerLED

5.3 Typ. LED current/voltage characteristics

The LED current in emergency mode is automatically adjusted by the EM powerLED module based on the total forward voltage of the LED modules connected and the associated battery. The start of the LED in emergency mode does not result in a current peak.

EM powerLED BASIC FX 213 / 233 lp 75W 220V Article number: 89800598 / 89800601 3.6 V battery voltage 850 ­ 960 mA battery discharge current (tolerance)
60

EM powerLED BASIC FX 214 / 234 lp 75W 220V Article number: 89800599 / 89800602 4.8 V battery voltage 850 ­ 960 mA battery discharge current (tolerance)
80

70 50
60
40 50

LED current [mA]

LED current [mA]

30

40

30 20
20
10 10

LED current [mA]

0 50 70 90 110 130 150 170 190 210
V [V] LED
EM powerLED BASIC FX 215 / 235 lp 75W 220V Article number: 89800600 / 89800603 6.0 V battery voltage 850 ­ 960 mA battery discharge current (tolerance)
100 90
80 70
60
50
40 30
20
10
0 50 70 90 110 130 150 170 190 210
V [V] LED

0 50 70 90 110 130 150 170 190 210
V [V] LED
LED current at nominal battery voltage and min. battery discharge current LED current at nominal battery voltage and max. battery discharge current

DDaatatashsehete1e0t/203-4EM/2058-3E-1M5 083-15 SSuubbjejcetctot cthoancgheawnitgheouwt nitohtioceu. Itnfnoormtiactieo.n provided without guarantee.

wwww.twrwid.tornidico.cnoicm.com

910

Emergency lighting units EM powerLED

Emergency lighting units EM powerLED

5.4 Operating window 250

5.5 Efficiency vs load 100

Output voltage [V]

200

90

Efficiency [%]

80 150
70
100 60

50

50

0 0 50 100 150 200 250 300 350 400 450 Output current [mA]

40 20 30 40 50 60 70 80 90 100 Load [%]

Operating window 100 %
Make sure that the LED Driver is operated within the given window under all operating conditions. Coming below the specified minimum output voltage of the LED Driver may cause the device to shut-down.

THD []

5.6 Power factor vs load

Power factor

1,0
0,9
0,8
0,7
0,6
0,5
0,4 20 30 40 50 60 70 80 Load [%]
5.7 THD vs load
THD without harmonic < 5 mA or 0.6 % of the input current:
        
       Load []

90 100  

100 mA 250 mA 400 mA
100 % load corresponds to the max. output power (full load) according to the table on page 2.

DDaatatashsehete1e0t/203-4EM/2058-3E-1M5 083-15 SSuubbjejcetctot cthoancgheawnitgheouwt nitohtioceu. Itnfnoormtiactieo.n provided without guarantee.

wwww.twrwid.tornidico.cnoicm.com

1011

Emergency lighting units EM powerLED

Emergency lighting units EM powerLED

6. Emergency output factor EOFi

EM powerLED BASIC

Type

EM powerLED BASIC FX 213/233 lp 75W 220V

EM powerLED BASIC FX 214/234 lp 75W 220V

EM powerLED BASIC FX 215/235 lp 75W 220V

Article no.

89800598 / 89800601

Cells

3 cells

Output current
 mA  mA  mA  mA  mA  mA  mA  mA

Min. LED load
               

Max. LED load
               

89800599 / 89800602 4 cells

Min. LED load Max. LED load

               

               

89800600 / 89800603 5 cells

Min. LED load
               

Max. LED load
               

7. Functions

7.1 Function: adjustable current

7.4 Overload protection

The output current of the EM powerLED can be adjusted in a certain range. For adjustment there are two options available.
Option 1: I-select 2 By inserting a suitable resistor or third party resistor into the I-select 2 interface, the current value can be adjusted. The relationship between output current and resistor value can be found in the chapter "Accessories I-SELECT 2 Plugs".
Please note that the resistor values for I-select 2 are not compatible with I-select (generation 1). Installation of an incorrect resistor may cause irreparable damage to the LED module(s).

If the output voltage range is exceeded the EM powerLED turns off the LED output. After restart of the EM powerLED the output will be activated again. The restart can be done via mains reset.
7.5 Overtemperature protection
The EM powerLED is protected against temporary thermal overheating. If the temperature limit is exceeded the output current of the LED module(s) is reduced. The temperature protection is activated approx. +5 °C above tc max (see page 2).
7.6 Forward voltage out of range

Resistors for the main output current values can be ordered from Tridonic (see accessories).

If the forward voltage is out of range the unit switches to shut down mode. After elimination of the short circuit a mains reset (SL off/on) is necessary.

Option 2: ready2mains Adjustment is done by the ready2mains Programmer and the corresponding configuration software (see ready2mains documentation).

Current adjustment can only be done five times over ready2mains. To program the EM powerLED a connected load is necessary that is within the operating window of the EM powerLED.

The priority for current adjustment methods is I-select 2 followed by ready2mains (lowest priority).

7.2 Short-circuit behaviour
In case of a short-circuit at the LED output the LED output is switched off. After restart of the EM powerLED the output will be activated again. The restart can either be done via mains reset or via interface ready2mains.
7.3 No-load operation
The EM powerLED will not be damaged in no-load operation. The output will be deactivated and is therefore free of voltage. If a LED load is connected the device has to be restarted before the output will be activated again.

DDaatatashsehete1e0t/203-4EM/2058-3E-1M5 083-15 SSuubbjejcetctot cthoancgheawnitgheouwt nitohtioceu. Itnfnoormtiactieo.n provided without guarantee.

wwww.twrwid.tornidico.cnoicm.com

1112

Emergency lighting units EM powerLED

Emergency lighting units EM powerLED

8. Battery data

8.1 Battery selection

Technology Design and capacity

stick

stick

stick

side by side

NiCd 4 Ah D cells

side by side stick + stick

stick + stick

remote box

remote box

remote box

stick

NiMH 2.2 Ah stick

Cs cells

stick

side by side

stick

NiMH 4 Ah stick

LA cells

stick + stick

stick + stick

EM powerLED BASIC, 1 / 3 h

Type

EM powerLED EM powerLED EM powerLED EM powerLED EM powerLED EM powerLED

BASIC FX

BASIC FX

BASIC FX

BASIC FX

BASIC FX

BASIC FX

213 lp 75W 220V 233 lp 75W 220V 214 lp 75W 220V 234 lp 75W 220V 215 lp 75W 220V 235 lp 75W 220V

Article no. 89800598

89800601

89800599

89800602

89800600

89800603

Cells

3 cells

3 cells

4 cells

4 cells

5 cells

5 cells

Duration

1 h

3 h

1 h

3 h

1 h

3 h

Number Type of cells

Article no.

Assignable batteries

1 x 3 Accu-NiCd 3A 55



·

1 x 4 Accu-NiCd 4A 55



·

1 x 5 Accu-NiCd 5A 55



·

3 x 1 Accu-NiCd 3B 55



·

4 x 1 Accu-NiCd 4B 55



·

2 + 2 Accu-NiCd 4C 55



·

3 + 2 Accu-NiCd 5C 55



·

1 x 3 Pack-NiCd 3D CON



·

1 x 4 Pack-NiCd 4D CON



·

1 x 5 Pack-NiCd 5D CON



·

1 x 3 Accu-NiMH 3A



·

1 x 4 Accu-NiMH 4A



·

1 x 5 Accu-NiMH 5A



·

5 x 1 Accu-NiMH 5B



·

1 x 3 Accu-NiMH 4Ah 3A CON 

·

1 x 4 Accu-NiMH 4Ah 4A CON 

·

2 + 2 Accu-NiMH 4Ah 4C CON 

·

2 + 3 Accu-NiMH 4Ah 5C CON 

·

8.2 Battery charge / discharge data

EM powerLED BASIC, 1 / 3 h
Type
Article no. Cells Duration Initial charge Battery charge Fast recharge time Trickle charge Initial charge Charging current Fast recharge Trickle charge Discharge current

EM powerLED BASIC FX 213 / 214 / 215 lp 75W 220V

EM powerLED BASIC FX 233 / 234 / 235 lp 75W 220V

89800598 / 89800596 / 89800600 3 / 4 / 5 cells 1 h

89800601 / 89800602 / 89800603 3 / 4 / 5 cells 3 h

24 h

24 h

continuously

105 mA

195 mA

105 mA

195 mA

70 mA

105 mA

850 ­ 960 mA

850 ­ 960 mA

DDaatatashsehete1e0t/203-4EM/2058-3E-1M5 083-15 SSuubbjejcetctot cthoancgheawnitgheouwt nitohtioceu. Itnfnoormtiactieo.n provided without guarantee.

wwww.twrwid.tornidico.cnoicm.com

1213

Emergency lighting units EM powerLED

Emergency lighting units EM powerLED

8.3 Accu-NiCd
4.2 / 4.5 Ah International designation Battery voltage/cell Cell type Case temperature range to ensure 4 years design life Max. short term battery case temperature (shorter than 1 month over the battery lifetime) Max. number discharge cycles
Max. storage time
8.4 Accu-NiMH
2.2 Ah International designation Battery voltage/cell Cell type Case temperature range to ensure 4 years design life Max. short term battery case temperature (shorter than 1 month over the battery lifetime) Max. number discharge cycles
Max. storage time
4.0 Ah International designation Battery voltage/cell Cell type Case temperature range to ensure 4 years design life Max. short term battery case temperature (shorter than 1 month over the battery lifetime) Max. number discharge cycles
Max. storage time
8.5 Accupack-NiCd
4.5 Ah Battery voltage/cell Cell type Ambient temperature range to ensure 4 years design life tc point Max. short term battery case temperature (shorter than 1 month over the battery lifetime) Max. number discharge cycles
Max. storage time

8.6 Accupack-NiMH

KRMU 33/62 1.2 V D
+5 °C to +55 °C
70 °C 12 cycles per year plus 4 cycles during comissioning 12 months

2.2 Ah Battery voltage/cell Cell type Ambient temperature range to ensure 4 years design life tc point Max. short term battery case temperature (shorter than 1 month over the battery lifetime) Max. number discharge cycles
Max. storage time

1.2 V Cs
+5 °C to +35 °C +40 °C
70 °C 4 cycles per year plus 4 cycles during comissioning 12 months

HRMU 23/43 1.2 V Cs
+5 °C to +50 °C
70 °C 4 cycles per year plus 30 cycles during comissioning 12 months

4.0 Ah Battery voltage/cell Cell type Ambient temperature range to ensure 4 years design life tc point Max. short term battery case temperature (shorter than 1 month over the battery lifetime) Max. number discharge cycles
Max. storage time

1.2 V LAL
+5 °C to +35 °C +40 °C
70 °C 4 cycles per year plus 4 cycles during comissioning 12 months

For a higher battery temperature rating for NiMH 4 Ah refer to the EM converterLED xx MH/LiFePO4 product range.

HRMU 19/90 1.2 V LA
+5 °C to +45 °C
70 °C 4 cycles per year plus 30 cycles during comissioning 12 months

8.7 Batteries
Connection method: 4.8 x 0.5 mm spade tag welded to end of cell
For stick packs this connection is accessible after the battery caps have been fitted.
To inhibit inverter operation disconnect the batteries by removing the connector from the battery spade tag.
For further information refer to corresponding battery datasheet.

1.2 V D
+5 °C to +40 °C +45 °C
70 °C 4 cycles per year plus 4 cycles during comissioning 6 months

8.8 Storage, installation and commissioning
Relevant information about storage conditions, installation and commissioning are provided in the battery datasheets.

DDaatatashsehete1e0t/203-4EM/2058-3E-1M5 083-15 SSuubbjejcetctot cthoancgheawnitgheouwt nitohtioceu. Itnfnoormtiactieo.n provided without guarantee.

wwww.twrwid.tornidico.cnoicm.com

1314

Emergency lighting units EM powerLED

Emergency lighting units EM powerLED

9. Miscellaneous
9.1 Maximum number of switching cycles
All LED Drivers are tested with 50,000 switching cycles. The actually achieved number of switching cycles is significantly higher.
9.2 Insulation and electric strength testing of luminaires
Electronic devices can be damaged by high voltage. This has to be considered during the routine testing of the luminaires in production.
According to IEC 60598-1 Annex Q (informative only!) or ENEC 303-Annex A, each luminaire should be submitted to an insulation test with 500 V DC for one second. This test voltage should be connected between the interconnected phase and neutral terminals and the earth terminal. The insulation resistance must be at least 2 M.
As an alternative, IEC 60598-1 Annex Q describes a test of the electrical strength with 1500 V AC (or 1.414 x 1500 V DC). To avoid damage to the electronic devices this test must not be conducted.

9.3 Conditions of use and storage

Humidity:

5 % up to max. 85 %, not condensed (max. 56 days/year at 85 %)

Storage temperature:

-40 °C up to max. +80 °C

The devices have to be acclimatised to the specified temperature range (ta) before they can be operated.

9.4 Additional information Additional technical information at www.tridonic.com  Technical Data Guarantee conditions at www.tridonic.com  Services
Lifetime declarations are informative and represent no warranty claim. No warranty if device was opened.

DDaatatashsehete1e0t/203-4EM/2058-3E-1M5 083-15 SSuubbjejcetctot cthoancgheawnitgheouwt nitohtioceu. Itnfnoormtiactieo.n provided without guarantee.

wwww.twrwid.tornidico.cnoicm.com

1415



References

cairo 1.18.0 (https://cairographics.org) Mozilla Firefox 136.0.4