XTP/XTC601 SIL Safety Manual

Michell Instruments

XTP/XTC 601 SIL Safety Manual

Manuals - Dew-Point, Humidity and Oxygen Specialists - Michell Instruments

Binary Gas Analyzer for Hydrogen Monitoring - Michell XTC601


File Info : application/pdf, 18 Pages, 990.94KB

PDF preview unavailable. Download the PDF instead.

Michell Instruments XTP-XTC601 SIL2 Manual v1-2
XTP/XTC 601 SIL Safety Manual
Note: Supplement to instruction manual
97587 Issue 1.2 September 2022

For Michell Instruments' contact information please go to www.michell.com
© 2022 Michell Instruments This document is the property of Michell Instruments Ltd and may not be copied or otherwise reproduced, communicated in any way to third parties, nor stored in any Data Processing System without the express written authorization of Michell Instruments Ltd.
The contents of this safety manual shall not become part of or modify any prior or existing agreement, commitment or legal relationship. All obligations on the part of Michell Instruments are contained in the respective sales contract which also contains the complete and solely applicable warranty conditions. Any statements contained herein do not create new warranties or modify the existing warranty.

XTP & XTC SIL Safety Manual

Contents

Safety Guidelines ................................................................................................................... iv
Qualified Personnel ................................................................................................................ iv Abbreviations ........................................................................................................................ v

1

INTRODUCTION ......................................................................................................... 1

1.1 General ........................................................................................................... 1

1.2 Required documentation ................................................................................... 1

2

SAFETY INSTRUCTION ................................................................................................ 2

2.1 Safety Integrity Level (SIL) ............................................................................... 2

3

DEVICE-SPECIFIC SAFETY INSTRUCTIONS ................................................................... 3

3.1 Applications ..................................................................................................... 3

3.2 Safety Function ................................................................................................ 3

3.3 Settings .......................................................................................................... 4

3.4 In case of faults ............................................................................................... 4

3.5 Maintenance/Calibration ................................................................................... 5

3.6 Safety Characteristics ....................................................................................... 6

APPENDIX A A.1 SIL Declaration of Conformity ................................................................. 7 A.2 Engineering Safety Consultants Limited. London, UK Test Report extract ... 9

Michell Instruments

iii

XTP & XTC SIL Safety Manual
NOTE: This product must not be modified or altered in any way. Unauthorised change is not permitted and to do so would cause the Functional Safety, as confirmed by the IEC61508 assessment, to be null-and-void. This products design is strictly controlled and to do so would invalidate all approvals, certification and warranties this product holds. Please consultant Michell Instruments Ltd directly for any functionality or service quries you may have.
Safety Guidelines
This manual relates only to the SIL aspects of this product.
For all other operation, installation & maintenance information refer to the product manual. The user must not use this equipment for any other purpose than that stated. Do not apply values greater than the maximum value stated.
This manual contains information relating to the SIL aspects of operating this product. Use competent personnel using good engineering practice for all procedures in this manual.
Qualified Personnel This product should only be set up and used in conjunction with this documentation. Commissioning and operation of this product should only be performed by qualified personnel.

iv

97587 Issue 1.2, September 2022

XTP & XTC SIL Safety Manual

Abbreviations

The following abbreviations are used in this manual:

 D DD DU s /hr ADC DAC DC E/E/PE EMF ESC EUC FIT FMEDA FMR FS FSM HFT MDT MTTR NPRD O2 O/C PFD PFH PLC PTI QA RBD S/C SFF SIF SIL SR Tp

Failure Rate Dangerous Failure Rate Dangerous Detected Failure Rate Dangerous Undetected Failure Rate Safe Failure Rate Per Hour Analogue-To-Digital Converter Digital-To-Analogue Converter Diagnostic Coverage Electrical/Electronic/Programmable Electronic Electromotive Force Engineering Safety Consultants Equipment Under Control Failure in time Failure Mode Effect and Diagnostics Analysis Failure Mode Ratio Functional Safety Functional Safety Management Hardware Fault Tolerance Mean Down Time Mean Time To Restoration Non-Electronic Parts Reliability Data Oxygen Open Circuit Probability of Failure on Demand Average Frequency of a Dangerous Failure per Hour Programmable Logic Controller Proof Test Interval Quality Assurance Reliability Block Diagram Short Circuit Safe Failure Fraction Safety Instrumented Function Safety Integrity Level Safety Related Proof Test Interval

Michell Instruments

v

XTP & XTC SIL Safety Manual

This page has been left blank intentionally.

vi

97587 Issue 1.2, September 2022

XTP & XTC SIL Safety Manual

1

INTRODUCTION

1.1 General

This manual refers only to:
XTP601 Oxygen Transmitter. XTP601 Oxygen Analyzer. XTC601 Binary Gas Analyzer. XTC601 Binary Gas Transmitter.
There are derivatives of each model as shown in the below table:

Analyzer Name Type
XTP601-GP1 General purpose analyzer with display XTP601-GP2 General purpose analyzer with flame arrestors XTP601-EX1 Hazardous area analyzer with display

XTC601-GP1 XTC601-GP2 XTC601-EX1

General purpose analyzer with display General purpose analyzer with flame arrestors Hazardous area analyzer with display

1.2 Required documentation This document only applies in conjunction with the following documentation:

Analyzer Name Type

Document No.

XTP601 XTC601

Process Oxygen Analyzer User's Manual (UK) Binary Gas Analyzer User's Manual (UK)

97313 97400

NOTE: For each type, there are manuals with the same content translated into other languages.

This document contains SIL-related data that will be required when using the XTP601 & XTC601 products in safety-instrumented systems.
It is aimed at system planners, constructors, service and maintenance engineers and personnel who will commission the device.

Michell Instruments

1

XTP & XTC SIL Safety Manual

2

SAFETY INSTRUCTIONS

These products are intended for use in safety applications.
All safety instructions relate exclusively to the analogue output signal (4­20mA). The products are certified to SIL2 (IEC 61508). The products software is certified SIL2 (IEC61508). The use of these products integrated in to safety-related systems is therefore possible.

Definition: Safety-instrumented system A safety-instrumented system executes the safety functions that are required to achieve
or maintain a safe status in a system. It consists of a sensor, logic unit/control system
and final controlling element.

A Safety Instrumented System (SIS) could be made of an analyzer (e.g. XTP 02 Concentration), a Safety rated logic Solver (e.g. safety relay or safety rated PLC) and a final element (e.g. valve, or alarm with defined response).

Definition: Safety function Defined function executed by a safety-instrumented system with the objective of achieving or maintaining a safe system considering a defined dangerous occurrence.

Example: XTP O2 concentration above or below a defined threshold.

2.1 Safety Integrity Level (SIL)
The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from SIL 1 to SIL 4. Each level corresponds to the probability range for the failure in a safety function. The higher the SIL of the safety-instrumented system, the higher the probability that the required safety function will work.
The achievable SIL is determined by the following safety characteristics:
· Average probability of dangerous failure of a safety function in case of demand (PFDAvG)
· Hardware fault tolerance (HFT) · Safe failure fraction (SFF)

Description:
The following table shows the dependency of the SIL on the average probability
of dangerous failures of a safety function of the entire safety-instrumented system
(PFDAvG). The table deals with "Low demand mode", i.e. the safety function is required a maximum of once per year on average.

SIL level SIL 4 SIL 3 SIL 2 SIL 1
Table 1

PFDavg 10­4 > PFDavg  10­5 10­3 > PFDavg  10­4 10­2 > PFDavg  10­3 10­1 > PFDavg  10­2
Safety Integrity Level

2

97587 Issue 1.2, September 2022

XTP & XTC SIL Safety Manual

The "average probability of dangerous failures of the entire safety-instrumented system" (PFDAvG) is normally spilt between the entire SIL system.

Sensor/Analyzer

  Control System or Logic Unit

Final controlling Element:

e.g. XTP601 or XTC601

e.g. Valve

e.g. PLC

The following table shows the achievable Safety Integrity Level (SIL) for the entire safety-
instrumented system for type B systems depending on the proportion of safe failures
(SFF) and the hardware fault tolerance (HFT). XTP and XTC units are considered Type B due to their complexity. Type B systems also include sensors and positioners actuators
with complex components, e.g. microprocessors (see also IEC 61508, Section 2).

SFF

HFT

0

1

2

<60%

Not allowed

SIL1

SIL2

60 to 90%

SIL1

SIL2

SIL3

90 to 99%

SIL2

SIL3

SIL4

>99%

SIL3

SIL4

SIL4

Table 2

Safety Integrity Level

3

DEVICE-SPECIFIC SAFETY INSTRUCTIONS

3.1 Applications

The Hardware assessment of the XTP601 & XTC601 shall provide the safety instrumentation engineer with the required failure data as per IEC 61508.

The hardware of XTP601 & XTC601 satisfies the requirements in terms of functional
safety to SIL 2 in accordance with IEC 61508. The XTP601 & XTC601 is usable in safety applications to monitor limits.

3.2 Safety Function
The XTP601 & XTC601 are mainly used for user-defined threshold monitoring. The XTP601 Process Oxygen Analyzer was assessed against the following safety function: · Ability to detect oxygen presence within another gas stream and generate
a 4­20mA output.
The XTC601 Binary Gas Analyzer was assessed against the following safety function: · Ability to detect target gas in another gas stream and generate a 4­20mA
output.

Michell Instruments

3

XTP & XTC SIL Safety Manual
Warning See the "Settings" and "Safety characteristics" sections for the binding settings and conditions. These conditions must be met to fulfil the safety function.
When the safety function has been executed, safety-instrumented systems with no selflocking function should be brought to a monitored or otherwise safe status within the Mean Time To Repair (MTTR). The MTTR is 168 hours.
For full product information refer to User Manuals 97313 & 97400.
3.3 Settings
After installation and commissioning (refer to User Manuals), the following parameter settings should be made for the safety function:
Safety parameters
Function Analog Output Select 4­20mA (NAMUR)
Protection against configuration changes After configuration, the menu access codes of XTP601 & XTC601 shall be changed so that the device is protected against unauthorized changes and operation.
Checking the safety function after installation After installation a safety function test must be carried out. Using reference gas, i.e. N2, 4mA must be measured at the analog output. For the test of the safety function it is fundamental to use a second reference gas with a defined proportion of oxygen. The results of the measurement must be within a range of ±5% (full span) of the expected result.
3.4 In case of faults
Fault The procedure in case of faults is described in the User Manuals.
Repair The defective product should be sent to a Michell Instruments Service Department with details of the fault and the cause. When ordering a replacement product, please specify the serial number of the original product. The serial number can be found on the nameplate.
Information regarding the location of Michell Instruments Service centres can be found at the following web address: www.michell.com

4

97587 Issue 1.2, September 2022

XTP & XTC SIL Safety Manual

3.5 Maintenance/Calibration

We recommend that the functioning of the XTP601 & XTC601 is checked at regular intervals of one year.

Check at least the following: Test the basic functionality of the XTP601 & XTC601 as described in the User Manual.

Checking safety
You should regularly check the safety function of the entire safety circuit in line with IEC 61508/61511.

The testing intervals are determined during the circulation of each individual safety circuit in a system. The recommended prove interval depends on the application but it should be at least once a year.

To detect dangerous undetected faults, the XTP601 & XTC601 analog output shall be checked with the following test:

To execute the safety proof test both tests (1 and 2) must be performed.

Proof test 1 consists of the steps described in the table below.

Step 1 2
3 4 5

Action
Bypass the safety PLC or take other appropriate action to avoid a false trip. Generate or simulate an alarm condition to force the product to go to the high alarm current output and verify that the analog current reaches that value.
Generate or simulate an alarm condition to force the product to go to the low alarm current output and verify that the analog current reaches that value.
Restore the loop to full operation.
Remove the bypass from the safety PLC or otherwise restore normal operation.

Proof test 2 consists of the steps described in the table below.

Step 1 2 3
4
5 6

Action
Bypass the safety PLC or take other appropriate action to avoid a false trip. Perform Proof Test 1.
Perform a 2-point calibration of the product. Perform a reference measuring with at least one measuring point between min and max concentration. You must use a calibration gas with a wellknown gas concentration. The expected result must have a tolerance of not more than 5%.
Restore the loop to full operation.
Remove the bypass from the safety PLC or otherwise restore normal operation.

This test will detect more than 90% of possible "du" failures in the product.

Should faults be detected, the product should not be used until completely rectified.

Michell Instruments

5

XTP & XTC SIL Safety Manual
3.6 Safety Characteristics
The safety characteristics necessary for use of the system are listed in the SIL declaration of conformity (see Appendix A.1). These values apply under the following conditions:
· The XTP601 & XTC601 are only used in safety-related systems with a low demand mode for the safety function.
· The safety-related parameters/settings (see "Settings" section) have been entered by local operation and checked before commencing safetyinstrumented operation.
· The XTP601 & XTC601 is blocked against unwanted and unauthorized changes/ operation.
· The maximum operating temperature is +40°C for the XTC601 and +55°C for the XTP601.
· All used materials are compatible with process conditions.
· The MTTR after a device fault is 168 hours. · The logic solver (PLC) must be configured to detect over range (>21mA)
and under range (<3.6mA) failure of the XTP601 & XTC601 (Fail High and Fail Low) and will recognize these as internal failures of the products and not cause a spurious trip.
Also see the Settings section of this manual and Appendix below.

6

97587 Issue 1.2, September 2022

XTP & XTC SIL Safety Manual
Appendix A A.1 SIL Declaration of Conformity

APPENDIX A

Random Hardware Reliability and Systematic Assessment Certificate
Functional Safety of Safety-Related Programmable Electronic Systems
The Michell Instruments UK Ltd, XTP601 Process Oxygen Analyser & XTC601 Binary Gas Analyser have been assessed and are considered capable for use in a low demand Safety Function up to (and including) SIL 2 capability with regards to systematic, random hardware failures and architectural constraints.
The assessment was based on the assumptions, data provided, and recommendations given in:
· Engineering Safety Consultants Ltd Report: H215_FM001 rev. 4.
The products were assessed against the following failure modes: · XTP601: Ability to detect oxygen presence within another gas stream and generate a 420mA output; · XTC601: Ability to detect target gas in another gas stream and generate a 4-20mA output.
The assessment was carried out to determine compliance with IEC 61508 (2010 Edition) with regards to:
· Random Hardware Failure (Predicted PFD as shown in Table below) with a Mean Down Time (MDT) of 168 hours, a Proof Test Interval (PTI) of one year (8760 hours), a Proof Test Coverage of 95% or 90% and an Overhaul Interval of 10 years (87600 hours);
· Random Hardware Failure with Achieved PFH: o XTP601 = 5.4E-08 o XTC601 = 3.9E-08
· Random Hardware Failure with Achieved DD: o XTP601 = 7.4E-07 o XTC601 = 7.0E-07
· Random Hardware Failure with Achieved DU: o XTP601 = 5.4E-08 o XTC601 = 3.9E-08
· Architectural Constraint (Type B, SFF >90%, <99%), HFT = 0; · Systematic SIL 2 capability against IEC 61508 (2010 Edition) Parts 1, 2 and 3.

Page 1 of 2

ENGINEERING SAFETY CONSULTANTS LTD 2nd Floor, Exchequer Court, 33 St. Mary Axe, London, EC3A 8AA UK Telephone/Fax: +44 (0)20 8542 2807 E-Mail: info@esc.uk.net Web: www.esc.uk.net
Registered in England and Wales: 7006868 Registered Office: 33 St. Mary Axe, London, EC3A 8AA

Michell Instruments

7

APPENDIX A

XTP & XTC SIL Safety Manual

Device XTP601 XTC601

Proof Test Coverage
(PTC)
95%
90%
95%
90%

PFD Target (20% of SIL
2 band)
2.0E-03
2.0E-03

PFD Achieved
4.1E-04 5.1E-04 3.1E-04 3.8E-04

Estimated Achieved
PFD
2
2
2
2

SFF 94% 96%

Type B B

Estimated Achieved SIL (Arch)
2
2
2
2

Estimated Overall SIL Capability
2
2
2
2

IMPORTANT: It should be noted that this assessment does not include confirmation of the response time of the device. For response times (along with any relevant assumptions) reference should be made to the Safety Manual of each device and the total SIF response time MUST be compared against the process safety time for the specific application.

Managing Director: Simon Burwood Member of IEC 61508 (MT61808-1-2) & IEC 61511 (MT61511) Maintenance Committees
Assessment Date: February 2020 Renewal Date: August 2022, valid to August 2024
Certificate: H215_CT001 rev. 3

Page 2 of 2

ENGINEERING SAFETY CONSULTANTS LTD 2nd Floor, Exchequer Court, 33 St. Mary Axe, London, EC3A 8AA UK Telephone/Fax: +44 (0)20 8542 2807 E-Mail: info@esc.uk.net Web: www.esc.uk.net
Registered in England and Wales: 7006868 Registered Office: 33 St. Mary Axe, London, EC3A 8AA

8

97587 Issue 1.2, September 2022

XTP & XTC SIL Safety Manual

APPENDIX A

A.2 Engineering Safety Consultants Limited. London, UK Test Report extract
2.1 General This report provides a Prior Use Assessment of the Michell Instruments UK Ltd, XTP601 Process Oxygen Analyzer and XTC601 Binary Gas Analyzer, as defined in the Prior Use requirements in IEC 61511 (2nd Edition) Clause 11.5.3 and 11.5.4 [2] including an estimation of Probability of Failure on Demand (PFD), Safe Failure Fraction (SFF) and a review of the systematic capability as supporting evidence for avoidance and minimisation of systematic failures.

A Failure Mode Effects and Diagnostics Analysis (FMEDA) was conducted on the XTP601 & XTC601 to estimate the random hardware failure rate in order to assess suitability for use in a safety function with regards to the PFD and the architectural requirements in terms of Hardware Fault Tolerance (HFT) and SFF, using the approach detailed in Route 1H in IEC 61508-2 [1].
2.2 Hardware Reliability Verification These devices will form part of the sensor element sub-system of a Safety Instrumented Function (SIF) and thus an assessment was conducted to demonstrate its capabilities in terms of PFD. The remaining sensing, logic solver and final element sub-systems were excluded from the assessment, in order to allow for their PFD contributions, the devices were assessed against 20% of Safety Integrity Level (SIL) 2 PFD band (e.g. SIL 2 band modified to 2.0E-03).
The analysis was based on the assumption that repairs would be carried out with a Mean Down Time (MDT) of 168 hours, a Proof Test Interval (PTI) of one year (8760 hours) and capable of revealing 100% of undetected failures.
The XTP601 Process Oxygen Analyzer was assessed against the following safety function: · · Ability to detect oxygen presence within another gas stream and generate a 4­20mA output.

The XTC601 Binary Gas Analyzer was assessed against the following safety function: · · Ability to detect target gas in another gas stream and generate a 4­20mA output.
Table 3 shows a summary of the results of the XTP601 & XTC601 based on the data provided and the assumptions given in this report. The full set of results for the hardware reliability verification is presented in Table 4.

Device

PFD Target (20%

PFD

of SIL2 band)

achieved

XTP601 XTC601

2.0E-03 2.0E-03

3.6E-04 2.9E-04

Table 3

PFD achieved
(SIL)
2
2

SFF
94% 96%

Type
B B

Achieved SIL (Architecture
HFT =0)
2
2

SIL Results Summary

Overall achieved
SIL
2
2

Michell Instruments

9

APPENDIX A

XTP & XTC SIL Safety Manual

Device Reference Function Specification Software Configuration/Settings Software Version

Hardware Diagram version

Hardware Configuration/Settings

Failure Mode(s) Definition

Dangerous detected Dangerous undetected Safe

Estimated failure rate
Dangerous Undetected Failures (DU) Dangerous Detected Failures (DD) Safe Failures (S)

Probability of Failure on Demand (PFD) Safe Failure Fraction (SFF)

Hardware Fault Tolerance (HFT)

Classification (Type A or Type B)

Demand (Low demand or High Demand)

Proof Testing Procedures

Installation

Average lifetime of device (yrs)

Environmental Profile

Systematic/Proven in Use Safety Integrity Level

Assumptions

General Notes and applicable regulations

Testing requirements

XTP601 & XTC601 XTP601 Oxygen Transmitter XTC601 Binary Gas Analyzer
As per customer order
Firmware for XTP601: 36217 V1.09 Firmware for XTC601: 37701 V1.06
XTP601: 80895/C V2.0 XTC601: 81003/C V1.0 As per customer order
dangerous detected failure rate per hour
dangerous undetected failure rate per hour
safe (or spurious) failure rate per hour
XTP601 7.0E-07, XTC601 5.9E-07 XTP601 5.41E-08, XTC601 3.87E-08 (FIT/hr) XTP601 7.39E-07, XTC601 7.00E-07 (FIT/hr)
XTP601 & XTC601 1.57E-07 (FIT/hr) XTP601 3.6E-04, XTC601 2.9E-04
XTP601 94% XTC601 96% 0
B
Low See section 3.5
Refer to User Manual 97313 (XTP) & 97400 (XTC) 5
Max +50°C. 80%rh>31°C/50%>+50°C 2
Refer to User Manual
This product complies with applicable standards and clauses of EU ATEX, EMC, PED Directives. Refer to the EU Declaration supplied with each product for
full details of the latest versions.
See section 3.5

Table 4

Verification Results

10

97587 Issue 1.2, September 2022

XTP & XTC SIL Safety Manual NOTES