Installation Guide for AIMS POWER models including: PICOGLF50KW384V240VS, Off Grid Inverter Charger, PICOGLF50KW384V240VS Off Grid Inverter Charger, Inverter Charger, Charger

逆变电源系统说明书

2

ok

Off Grid Inverter Charger - AIMS Power

However, this manual is subject to change without prior notice. AIMS Power™ reserves the right to continuously improve the product. In addition, the illustrations in this manual are only meant to help explain system configuration concepts and installation instructions. Your system or application may be different than the examples used in this ...

AIMS Power 30kw Power Inverter Charger

AIMS Power cannot monitor the compliance to this manual, nor the conditions and methods of installation, operation, usage and maintenance of the solar ...


File Info : application/pdf, 24 Pages, 1.88MB

PDF preview unavailable. Download the PDF instead.

AIMS300V DC 41201
Off Grid Inverter Charger
User and Installation Manual
PICOGLF50KW384V240VS PICOGLF50KW384V2083P PICOGLF30KW300V240VS PICOGLF30KW300V2083P PICOGLF30KW300V4803P
1

Read the manual carefully. Follow all warning and operating instructions contained in the manual before operating the inverter. Keep the manual for future reference. The information included in this manual is based on the product at the time of publication. However, this manual is subject to change without prior notice. AIMS PowerTM reserves the right to continuously improve the product. In addition, the illustrations in this manual are only meant to help explain system configuration concepts and installation instructions. Your system or application may be different than the examples used in this manual.
Exclusion of Liability
AIMS Power cannot monitor the compliance to this manual, nor the conditions and methods of installation, operation, usage and maintenance of the solar controller. Improper installation may result in damage to property and, as a result, to bodily injury. We assume no responsibility or liability for loss, damage or costs which result from, or are in any way related to, incorrect installation, improper operation, or incorrect use and maintenance. AIMS Power reserves the right to make changes to the product, technical data or assembly and operating instructions without prior notice.
2

Contents
_Toc25567765 Safety Instructions................................................................................................................................5 1. Product Introduction .........................................................................................................................6 2. Technical Information........................................................................................................................8 3. Unpacking the Inverter .....................................................................................................................8 4. Installation ........................................................................................................................................9 5. Electrical Connection......................................................................................................................10 6. LCD Display Layout........................................................................................................................12 7.LCD Panel Operating Instructions ...................................................................................................14 9. Malfunction and Troubleshooting....................................................................................................19 10. Maintenance.................................................................................................................................20 11. Warranty Conditions .....................................................................................................................21 12. Specifications ...............................................................................................................................22
3

SYMBOLS
SYMBOL

DESCRIPTION Grounding point
Refer to instructions
Properly dispose
Beware of dangerous electrical voltage. The inverter operates at high voltages! CE mark The inverter complies with the requirements of the applicable CE guidelines. SAA mark The inverter complies with the requirements of the applicable Australia guidelines. UL mark The inverter complies with the standard of UL1741.
CSA mark The inverter complies with the standard of CSA22.2.

4

Off Grid Inverter
Safety Instructions
Warning: The warnings, cautions, and instructions discussed in this instruction manual cannot cover all possible conditions and situations that may occur. It must be understood by the operator that common sense and caution are factors which cannot be built into this product and must be supplied by operator.to prevent electric shock.
1. To avoid risk of fire and electronic shock, make sure existing wiring is in good electrical condition and the wire is not undersized.
2. This equipment contains components which may produce arcs and/or sparks. To prevent fire and/or explosion, do not install in compartments containing batteries or flammable materials including any space containing gasoline-powered machinery, fuel tanks, joints, fittings, or areas that contain fuel.
3. To reduce the risk of electrical shock, disconnect both AC and DC power from the inverter before attempting any maintenance or cleaning. Simply turning off the controls will not reduce this risk.
4. Never smoke or allow sparks or flames close to the inverter or solar system. 5. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with this product. 6. Do not operate if under the influence of alcohol or drugs. Read warning labels on prescriptions to determine if your
judgement or reflexes are impaired while taking drugs. If there is any doubt, do not operate the box. 7. People with pacemakers should consult their physician(s) before using this product. Electromagnetic fields near a
pacemaker could cause interference to or failure of the pacemaker. 8. Keep inverter away from children. Don't install the inverter where it is accessible to children. 9. Properly maintain all equipment. Check all wiring, batteries, inverters and charge controllers. 10. Ensure someone is within close range when working with any type of electrical equipment. 11. Do not expose the inverter to rain, snow, spray, damp area, bilge or dust. 12. Do not cover or obstruct the ventilation openings. Install in a well-ventilated area. Do not install the inverter in a
zero-clearance compartment. Overheating may result. Allow at least 12" of clearance around the inverter for air flow. Make sure that the air can circulate freely around the unit. A minimum air flow of 145CFM is required. 13. See Warranty Instructions for servicing the inverter. Only a professional electrician should service the inverter.
WARNING INSTALLATION & MAINTENANCE SHOULD BE PERFORMED BY A PROFESSIONAL ELECTRICIAN/TECHNICIAN. ALL ELECTRICAL INSTALLATION SHOULD FOLLOW LOCAL CODES.
NOTE CAREFULLY INSPECT ALL PARTS AND MAKE SURE THERE IS NO DAMAGE. NOTIFY MANUFACTURER OF ANY DAMAGES BEFORE ACCEPTING DELIVERY AND INSTALLING THE INVERTER.
NOTE Do not close any breakers until all equipment is completely connected and inspected.
Warning Use proper grounding, using appropriate cable and fuse size.
Danger Before performing checks or maintenance, open (off) AC breaker, turn off start switch, then open (off) DC breaker. Wait 5 minutes for energy to dissipate. Measure DC and AC voltages with a multimeter and ensure there is no voltage between DC side and AC side. The display will slowly dim and disappear as the voltage drops.
Danger Don't make any connections or open door when the inverter is powered on. Shock may occur. 5

1. Product Introduction
Summary

Off Grid Inverter

Our PICOGLF series off grid inverter is one of the largest DC to AC inverters in the world. The Global LF Series Pure Sine Wave Inverter is a combination of an inverter, trickle battery charger and an AC auto-transfer switch into one complete system, with a peak conversion efficiency of 94%.

It is packed with unique features and it is one of the most advanced inverters on the market today. It features power factor correction, customizable AC and DC operation and a pure sine wave output with unprecedentedly high surge capability to meet demanding power needs of inductive loads without damaging the equipment.

When utility AC power cuts off (or falls out of acceptable range), the transfer relay is de-energized, and the load is automatically transferred to Inverter mode. Once the qualified AC power is restored the relay is reenergized and the load is automatically reconnected to AC bypass mode. The priority is programmable.

Features

Advanced short circuit, over load, over temperature protections ensure a service life up to 15 years or more. Two types of startup modes: Soft Start and Variable Frequency Start. User can select mode according to the type of load. Adjustable output frequency. Adjustable AC output voltage. Output voltage can be set between -40 % to +20 % of rated voltage. Adjustable DC voltage range. Over-voltage point, under-voltage point, over-voltage recovery point and under-voltage recovery point can be set via the LCD panel. Powerful data display and fault instruction function. The LCD can display DC input voltage, output frequency, phase voltage, phase current, AC bypass input voltage, power generated, time and date, temperature, fault code display. Pure sine wave output with quick transfer less than 50ms, minimal waveform distortion and stable output voltage.
Low frequency transformer with isolated DC and AC busbars to eliminate interference.
Wide input voltage range, customizable to customer's requirement. Input voltage range of 100300V or 200-600V or 400-800V, suitable for solar/wind system without using backup batteries and charge controller. it can save many cost and maximization use the solar/wind energy. Using SVPWM space vector algorithms, high conversion efficiency, high instantaneous power and low losses conversion efficiency up to 94%.
Output AC power compatible for all types of home electric equipment, sensitive electronics, and electric motors, etc.
European CE (EMC & LVD) certified and UL1741 & CSA22.2 listed.

6

Physical Layout
2. Lock & Handle 1.LCD
Model number nomenclature
Example: PICOGLF50KW384V240

Off Grid Inverter
4. Start Switch 5. Breakers 6. Connection Terminals 3. Cable Gland
7. Name Plate

No. Name

VS Description

LCD Display Screen

Displays inverter's operating status. Some functions are settable using the LCD display. Battery voltage, AC output voltage, AC current, frequency, work mode and faults.

Lock & Handle Cable Gland 4 Start Switch Breakers

Inverter lock and handle for main door. The input and output wire throughputs. Start switch to charge capacitors for starting the inverter. DC input and AC output breaker.

Connection Terminals DC input terminal & AC output terminal.

Name Plate

Basic inverter specifications listed on the nameplate including serial number.

7

Off Grid Inverter
2. Technical Information
Derating Reducing the output power is a way to prevent inverter overload or damage. When the operating environment temperature and altitude are too high, both can cause a decrease in the inverter's output power.
Inverter temperature derating curve =Pout/Pnomx100 T = environment temperature Pout is the off grid inverter's actual maximum output power Pnom is the off grid inverter's allowed max. output power
3. Unpacking the Inverter
The product has been tested, thoroughly inspected and packaged to withstand transportation. It is important to check the package and inverter before installing. Be sure to inspect for any damage or incorrect quantities BEFORE signing for the product. If you accept the product, make sure to have the carrier NOTE the damage before signing.
8

Off Grid Inverter
The nameplate shows the inverter's model and other important information. Confirm you
ordered and that you received the correct inverter.

NO.

Description

1

AIMS Power Logo and product name.

2

Inverter model and parameter information.

3

Serial number.

4

Certifications and safety symbols.

5

Company info.

Note Photos are for reference only, check nameplate on the inverter.

4. Installation
Location
 The inverter must be installed in a cool dry area. Water, dirt and dust will damage the inverter.
 A 1ft clearance around the inverter is recommended.  Installation must comply with local standards and codes.  Do not install the inverter in a flammable or explosive area or a place where flammable or explosive
materials are stored.  Do not install the inverter in areas where the inverter is vulnerable to lightning strikes.  Do not install the inverter in a high salt, humid environment.  Inverter has a rating of IP20. Install indoors and out of direct sunlight.  Place inverter on a solid, sturdy, flat surface that can handle the inverter's weight.  The ideal temperature should be maintained within -13 to 122°F and
humidity not exceeding 95%.  The inverter should be installed vertically.  Do not allow the inverter to tilt forwards.
9

Off Grid Inverter
 Never install the inverter horizontally.  Install the inverter so the LCD is easy to access and read.  The inverter should have plenty of air flow all around the inverter for
proper cooling fan operation.  Don't install the inverter where passersby or children can tamper or
access the unit.
5. Electrical Connection
As mentioned several times in this manual, installation should be done by a licensed professional. The
electrical connections should be tested immediately after the installation is completed.
Prechecks
All electrical connections must meet local electrical codes.
Incorrect wiring and/or installation may damage the inverter and may cause bodily harm. Before making any connections or performing maintenance to the inverter, make sure all power is off and no voltage present on the AC and DC sides. Test for correct grounding, using proper cable and fuse sizes. Use a fuse or breaker 12 inches off the battery bank. Confirm the front panel breakers are in the "OFF" position and confirm all connections are properly wired. Check that the DC input breakers are in the "OFF" position. The cable between the battery and inverter should be as short as possible to avoid voltage drop. Never turn off DC input breaker with the inverter on or under a load, damage to the breaker or the inverter will occur. Ensure all air vents are free from obstructions and clear of dust and debris. Don't connect ground wire (PE) of cabinet and neutral wire (N) together.
NOTE: Do not over shut DC breaker off during operation. To shut AC off, use AC breaker first, then disengage AC start switch. To shut down inverter completely, follow above steps first then turn off DC breaker. Shutting off DC breaker during operation and under a load will damage the breaker and cause arcing.

Terminals
L1, L2 L1, L2, N PE

Description DC positive input terminals DC negative input terminals AC input terminals, connect with AC grid or generator AC output terminals, connect with AC load panel Earth ground

10

Terminal Block

Off Grid Inverter

Warning
Do not reverse the polarity when connecting to DC input terminals. Confirm your wires are connected properly. Use the proper size cable and use bigger cable to handle voltage drop for long distance runs. REVERSE POLARITY IS NOT COVERED UNDER WARRANTY. Source ground to case ground must be isolated and wire length should be as short as possible. After all wire connections have been made, check all voltages to ensure the voltages are within inverter's specification. Never operate any inductive motor larger than 30% of the inverters output due to high startup surge. When turning on the DC input breakers, the breaker may trip or pop the first time. This is normal as the large capacitors are rapidly charging. If this happens, simply reset the DC breakers. When powering on the inverter, we recommend turning on the output circuit breaker first, then turn on start switch allowing a soft start of AC loads to avoid any damage by large inrush current to inverter. Before performing checks or maintenance, open (off) AC breaker, turn off start switch, then open (off) DC breaker. Wait 5 minutes for energy to dissipate. Measure DC and AC voltages with a multimeter and ensure there is no voltage between DC side and AC side. The display will slowly dim and disappear as the voltage drops. Inverter may still be live and have voltage present in the off position due to the large capacitors. Never touch any connection prior to testing with a multimeter. When the inverter is operating normally, it is typical to see a rise in temperature. The cooling fans will start when the temperature reaches @ 113°F. Do not open inverter's door or touch any wire while in operation.
NOTE
When the inverter is running, it is normal for the inverter to get warm. To avoid injury, only touch the LCD display and start/stop switch. DO NOT TOUCH ANY BREAKERS WHILE INVERTER IS OPERATING. THIS M AY CAUSE BODILY HARM AND RUIN THE INVERTER.
After all connections are made and voltages are verified with a multimeter, proceed to the startup procedure
in section 6.
11

6. LCD Display Layout

Off Grid Inverter

LED Indicators

There are 5 LED lights on the panel: Grid, Run, Fault, Auto, Manual.

Table7-1 LED Indicator Direction

LED Indicator Grid

Color Amber

Instructions AC bypass priority mode indicates the AC grid input condition.

Battery priority mode indicates the battery supply

Run

Green

condition. Inverter mode.

Fault

Red System fault.

Auto

Blue Inverter running, indicates the inverter is work

normally.

Manual

Illuminated Variable frequency mode, the inverter is working in variable frequency mode.

*When in inverter mode, the LED will be blue/green or blue/amber. This is normal.

Fault Code

DCU OVER DCU UNDER OVER LOAD MOD OUTErr

DC over-voltage DC under-voltage Current over-load Module error Output voltage unbalance (This error is only for 3 phase output, single phase output without this error display).

12

Off Grid Inverter
If any inverter parameters need to be made, follow instructions on page 15 LCD Panel Operating Instructions. All parameters must be set prior to engaging start switch DW. 13

LCD Display Interface Overview

Off Grid Inverter

7. LCD Panel Operating Instructions

Inverter power on, the first interface display parameter, press "down" key to display the following parameters:

DC IN

DC input voltage display

AC OUT AC output voltage display

AC OUT Output current display

Freq

Output frequency display

AC INPUT:

U

V

OUT W:

KWH

AC bypass input Bypass phase voltage Total generated amounts Generated amounts

14

Inv State:

Off Grid Inverter
Inverter working state:

DCU OVER

DC over-voltage

DCU UNDER DC under-voltage

OVER LOAD Over-load

MOD

Module error

Fault display"N" indicates no error, "Y" indicates error

OUTErr

Output voltage unbalanced

**This error is only for 3 phase output. (NA for 240V)  Fault alarm can be divided into automatic recovery and non-automatic recovery: When the LCD

screen display MOD error and overload you need to manually restart, turn off the DC circuit breaker

until the LCD screen is completely off and then turn on the DC circuit breaker; over-voltage, under-

voltage will automatically recover (the under-voltage recovery default setting is 10 minutes), and can

be set according to the customer application.

Keypad function

1. Running Info 2. Inv Start Mode 3. Work Modes 4. Parameter Set

Running state display Inverter Start mode Working Mode System parameter setting

15

Press " 2. Inv Start Mode " displays the following

1. Voltage
2. Frequency Y  YES

Constant frequency step-down voltage Starting mode Variable frequency starting mode
N NO

Press " 3. Work Modes " displays the following

1. Inv 2. Bypass

Battery priority mode AC bypass priority mode

Y  YES

N NO

Time:

Display current time and date

Tem:

Environmental temperature display

Press " 4. Parameter Set " you will need to enter password each time.
Note! If you want to adjust the parameter setting, please contact the manufacturer and ask for password

Note! When inverter is working, please don't adjust parameters setting. If you want to adjust parameter setting, please turn off start button and operation of inverter.
The following settings are to be set by a qualified professional. If you are not qualified to make these changes, damage will occur and not covered under warranty.
16

1. Freq Set 2. VIout Set 3. CT&Temp Set
4. Alarm Set

Frequency setting Output voltage setting Current ratio setting and temperature Protection setting DC over-voltage and under-voltage setting

5. UdcR Set voltage

Recovery setting of DC over-voltage and under-

6. Udc Under Delay

Default recovery time of under-voltage

is 10 minutes

7. Time Set

Date and time setting

8. Overload Set Overload times and overload time setting

Press " 1. Freq Set " output frequency setting display as following

Max Fre: HZ Recommend maximum output frequency setting between 30-100Hz
Min Fre: HZ The minimum frequency of output Starting can't less than 5Hz

Press " 2. Vout Set " output voltage and current setting display as following

Vout Set

Output voltage setting

Iout ­Max Set:

Output current setting

Note: Output Max Current default is the overload protection

current value and can be lowered, Output voltage should be

set to no more than 20% of the rated power. If the inverter is

damaged by incorrect settings it will not be covered under

warranty.

Press " 3. CT&Temp Set " Current and mutual inductance ratio and Protection temperature setting display as following

CT Set: Temp Set:

Current and mutual inductance ratio setting Protection temperature setting

17

Press " 4. Alarm Set " over-voltage and under-voltage setting display as following

Udc-over Set: Udc-under Set

DC over-voltage protection setting DC under-voltage protection setting

Press " 5. UdcR Set " DC over-voltage and under-voltage recovery setting display as following

Udc-over Set: Udc-under Set:

DC over-voltage recovery setting DC under-voltage recovery setting

Press " 6. Udc Under Delay " Under-voltage recovery time setting display as following
Udc Under Delay: Under-voltage recovery time setting

Min

Minute

Press " 7. Time Set " to display as following
Time: Display date and time setting

Press " 8. Over Load Set "
Recovery over Load Set: Overload times setting Overload surge time 18

8. Malfunction and Troubleshooting
If a malfunction or alarm sounds, the malfunction LED will light up, LCD will display current malfunction or stop condition, please refer to chart below for commons malfunction and troubleshooting steps.

Condition code State 01
State 02
State 03
State 04

Name DC input voltage low
DC input Over voltage
Output overload
IPM fault

Phenomena

Cause value

Troubleshooting

Inverter stopped working, No AC

Battery voltage out Check battery output

of inverter's DC range. DC input

voltage on the inverter,

output, inverter

voltage lower than ensure the output voltage

restarts automatically min input voltage of is within spec of

inverter

inverter.

Inverter stopped working, No AC output, inverter
restarts automatically

DC input voltage higher than maximum input voltage of inverter

Check battery output. voltage or PV array voltage and ensure the output voltage is within spec of inverter.

Inverter shut down, AC loads turn on and off

Load higher than rated output power of inverter.
Battery bank too small

Insure correct system design. This fault is usually caused by high surge devices that the inverter or battery bank can't support.

Inverter shut down, will no longer output AC power

Check for short circuit on AC output. If this fault appears frequently, please contact AIMS Power

Under fault of MOD, overload, output error and fault alarm, turn off the DC input breaker for 1 hour to restart the machine.

19

9. Maintenance

CAUTION

Before performing checks or maintenance, open (off) AC breaker, turn off start switch, then open (off) DC breaker. Wait 5 minutes for energy to dissipate. Measure DC and AC voltages with a multimeter and ensure there is no voltage between DC side and AC side. The display will slowly dim and disappear as the voltage drops. Inverter may still be live and have voltage present in the off position due to the large capacitors. Never touch any connection prior to testing with a multimeter.
Every 6 months
 Check all ventilation and fan airways. Blow air and clear all dust in the inverter and in the surrounding area. If high level of dust is accumulating, relocate inverter or find a way to keep dust at a minimum.
 Check the inverter cable connections. If loose, tighten according to the proper connection guidelines in this manual.
 Ensure the cables are not damaged, inspect for cracking, fraying, cut or over heated wiring.

Parts Input and output
terminals Input and output cable
Control board Bus capacitor Radiator Fan Inside of cabinet
Button cell

Check the contents
Loose
Condition of cable
Accumulation of dust and dirt
Discoloration or smell Not working
Accumulation of dust and dirt
LCD doesn't display Time

Solutions
Tighten
Replace poor quality cable
Using 392kPa-588kPa pressure dry compressed air to clean inverter Replace capacitor Replace fan
Using 392kPa-588kPa pressure dry compressed air to blow off
Replace the CR1220 Button Cell on the motherboard

20

10. Warranty Conditions
All AIMS Power® products come with warranty coverage against defects as follows, from the date of purchase, unless otherwise indicated:
· 2-Year with optional extended warranties Within the warranty coverage period, AIMS Power® will either repair or replace, at its sole discretion, the defective product. A refund may be issued if a defective product is not repairable or a comparable replacement is available. ­ We will never issue a refund. We will always have a replacement if the unit is not repairable. Our distributors offer their own return policy. AIMS only covers warranty issues. Any shipping charges that occur as a result of a warranty return or exchange are NOT covered by the warranty and are the responsibility of the customer. The warranty does not cover the following:
· Products that AIMS Power® determine, in its sole discretion, to be free of any material or workmanship defects or flaws
· Products evidencing excessive wear, misuse or alteration · Products with missing or defaced labels, stickers, or other identifying information · Improper care or storage (e.g. water damage, exposure to extreme heat or cold temperatures) · Alterations or customization · Items that were purchased second hand, or from an unauthorized seller · Items outside of the covered warranty period AIMS Power 9550 Gateway Drive Reno, NV 89521 775-359-6703 www.aimscorp.net
21

Off Grid Inverter

11. Specifications

Model

Isolation mode

DC Input

Rated voltage (Vdc) Rated current(A)

DC operating range

Programmable range

Rated power (KW)

Rated voltage

AC Output

Output phases
Rated current (A)
Output frequency Output waveform
Voltage accuracy Waveform distortion
rate (THD) Dynamic Response Power Factor (PF) Inverter Efficiency Electrical insulation
properties Running mode Output voltage (Vac)
Phases

30KW Low Frequency Transformer 300V Operating: 270-430V DC Programming: 250-500V DC
100A 270-430V DC 250-500V DC
30KW 120/240V split 120/208V 3 phase 480 3 phase Split phase | 3 phase ­ depends on model
125A | 83.3A
(phase current)
60Hz Pure Sine Wave
Load balance1%, Unbalance load5%
Linear load2%, Nonlinear load3%
5%, 50ms( load 0 ~ 100%) 0.95 >94%
2000Vac, 1 Minute
Working continuously, can work 24h*7@50% load 110/120/220/230/240/380/400/415/440VAC can be customized
Single / Split/ Three phase optional ­ per order

Protection Function

Overload Ability
Protection
Display Communication port
Cooling method Short-circuit protection

120% - 35 seconds, 150% - 5 seconds
Input reverse polarity, under voltage, over voltage, output overcurrent, short circuit, overheating etc. LCD RS485(Optional) Fan-cooled
No automatic recovery, need to restart the machine

Working environment
& Mechanical dimension
Certifications 22

Degree of protection Working Altitude (m) Working temperature
Relative humidity
Noise (1 meter) Depth* Width * Height
Weight (Kg)

IP20(indoor)
2500m -15~+50 0~90%non-condensing
50dB 650x750x1100mm | 24" x 24.75" x 42.50"
260Kg | 568lb ­ 650lb European CE (EMC & LVD) UL, CSA

Off Grid Inverter

Model

Isolation mode

DC Input

Rated voltage (Vdc) Rated current(A)

DC operating range

Programmable range

AC Output

Rated power (KW) Rated voltage Output phases
Rated current (A)
Output frequency Output waveform
Voltage accuracy Waveform distortion
rate (THD) Dynamic Response Power Factor (PF) Inverter Efficiency Electrical insulation
properties Running mode Output voltage (Vac)
Phases

50KW Low Frequency Transformer
360V 139A 346-550V DC 320-600V DC
50KW 120/240V | 120/208V Split phase | 3 phase
208.3A |138.8A
(phase current)
50Hz or 60Hz Pure Sine Wave
Load balance1%, Unbalance load5%
Linear load2%, Nonlinear load3%
5%, 50ms (load 0 ~ 100%) 0.95 >94%
2000Vac, 1 Minute
Working continuously, can work 24h*7 110/120/220/230/240/380/400/415/440VAC can be customized
Single / Split/ Three phase optional ­ per order

Protection Function

Overload Ability
Protection
Display Communication port
Cooling method Short-circuit protection

120% - 35 seconds, 150% - 5 seconds
Input reverse polarity, under voltage, over voltage, output overcurrent, short circuit, overheating etc. LCD RS485(Optional) Fan-cooled
No automatic recovery, need to restart the machine

Working environment
& Mechanical dimension
Certification

Degree of protection Working Altitude (m) Working temperature
Relative humidity
Noise (1 meter) Depth* Width * Height
Weight (Kg)

IP20(indoor)
2500m -15~+50 0~90%non-condensing
50dB 710x750x1300mm| 31.5" x 31.5" x 49.5"
400Kg | 900lb -960lb European CE (EMC & LVD) UL, CSA

23

Electrical Diagram
24


Adobe PDF Library 20.6.74