User Guide for STUDER models including: xtender xth Inverter Charger Perma-Batteries, xtender xth, Inverter Charger Perma-Batteries, Perma-Batteries

| STUDER


File Info : application/pdf, 9 Pages, 539.00KB

PDF preview unavailable. Download the PDF instead.

quickguide-xtender-xth-def
quick guide xtender xth
swiss made power

designed and assembled by studer in Switzerland

Introduction
EN Congratulations ! You are about to install and use a high-end equipment that will play a central role in the energy management of your battery-based system. The xtender is an smart battery inverter/charger with advanced functions. This xtender has been designed, manufactured, assembled and tested in our factory in Switzerland. It has a 5-year warranty and is eligible for an extension 5+5.
FR Félicitations ! Vous vous préparez à installer et à utiliser un appareil haute-gamme qui jouera un rôle central dans la gestion d'énergie de votre système avec stockage. L'xtender est un onduleur / chargeur de batterie intelligent doté de fonctions avancées. Ce xtender a été conçu, fabriqué, assemblé et testé dans notre usine en Suisse. Il bénéficie d'une garantie de 5 ans et est éligible à une extension 5+5.
DE Herzlichen Glückwunsch ! Wir freuen uns, dass Sie sich für eines High-Tech-Gerät entschieden haben, welches bei der Energie-management Ihrer Anlage entscheidende Rolle spielen wird. Der xtender ist ein intelligenter Wechselrichter / Batterielader mit erweiterten Funktionen. Dieser xtender wurde in unserem Werk in der Schweiz entwickelt, hergestellt, montiert und getestet. Es hat eine 5-jährige Garantie und kann um 5+5 verlängert werden.
ES ¡Enhorabuena! Está a punto de instalar y de utilizar un equipo de alta gama que desempeñará una función esencial en la gestión de energía de su sistema con almacenamiento. El xtender es un inversor / cargador de batería inteligente con funciones avanzadas. Este xtender ha sido diseñado, fabricado, ensamblado y probado en nuestra fábrica en Suiza. Tiene una garantía de 5 años y es elegible para una extensión 5+5.
3

General Information
EN Exclusion of liability Studer disclaims all responsibility and liability for damage, costs or losses resulting from an installation that does not comply with the instructions, a faulty operation or inadequate maintenance. The use of studer equipment is in any case under the responsibility of the customer.
Read carefully the safety and operation instructions / Installation must be entrusted to qualified personnel / Check the user manual online / Need help ?
FR Exclusion de la responsabilité Studer décline toute responsabilité pour les dommages, les coûts ou les pertes résultant d'une installation non conforme aux prescriptions, d'un fonctionnement défectueux, ou d'un entretien déficient. L'utilisation des appareils studer relève dans tous les cas de la responsabilité du client.
Lisez attentivement les instructions de sécurité et d'utilisation / L'installation doit être confiée à du personnel qualifié / Consultez le manuel d'utilisation en ligne / Besoin d'aide ?
DE Haftungsausschluss Studer übernimmt keinerlei Verantwortung und Haftung für Schäden, Kosten oder Verluste, die sich aus unsachgemäßer Installation, unsachgemäßem Betrieb sowie fehlerhafter Wartung ergeben oder in irgendeiner Art und Weise damit zusammenhängen. Der Einsatz und Betrieb der studer-Geräte obliegt in jedem Fall der Verantwortung des Kunden.
Lesen Sie die Sicherheits- und Betriebsanweisungen sorgfältig durch / Die Installation muss qualifiziertem Personal anvertraut werden / Überprüfen Sie die Bedienungsanleitung online / Brauchen Sie Hilfe ?
ES Exclusión de responsabilidad Studer declina cualquier responsabilidad por los daños, costes o pérdidas resultantes de una instalación no conforme con las recomendaciones, de un funcionamiento defectuoso o de un mantenimiento deficiente. El uso de equipos de studer es en cualquier caso responsabilidad del cliente.
Lea atentamente las instrucciones de seguridad y funcionamiento / La instalación debe confiarse a personal cualificado / Consulte el manual de usuario en línea / ¿Necesitas ayuda?

Compatible with :

rcc 02/03 Configuration, display,
datalogger

xtender Battery inverter/charger

vario Solar charge controller

CAN

BSP

xcom CAN

bsp

xconnect

Communication with lithium Advanced battery processor

Three-phase mounting frame

BMS

(lead-acid)

232i CAN 485i

xcom 232i/CAN/485i Communication bridges
(openstuder)

xcom LAN/GSM Remote monitoring (Portal
& App)

bts 01 Temperature sensor

5

Mounting and installation
Storage and content
60°C
-20°C
Mounting place The batteries should only be installed by qualified personnel.
6

Fixing and dimensions
1

(¢ ¡¡ &&£¤¤

4x
2

11 ¡¡

min. 200mm

min. 200mm

min. 200mm

497mm

34 - 46kg

300mm

230mm

3
7

Wiring

Jumpers L1 L2 L3

Auxiliary Contacts

AUX1 AUX2

NC C NO

+-
L1 L2 L3 BATTERY

L NL N

Temperature sensor bts 01 · 1x RJ 11 black flat cable
Communication · 2x RJ 45 black flat cable :
rcc 02/03 / multi-units : xtender, vt, vs, bsp, xcom

Bus termination Remote entry

A

B

1

2

3

Remote On/off

A

B

1

2

3

Remote On/off

EN The device must be installed in accordance with local standards and regulations in force. FR L'appareil doit être installé conformément aux normes et réglementations locales en vigueur. DE Das Gerät muss gemäß den geltenden örtlichen Normen und Vorschriften installiert werden. ES El dispositivo debe instalarse de acuerdo con las normas y regulaciones locales vigentes.
8

M6

T10

Battery connection
BAT+, M8 BAT-, M8
· 95mm2 cable M8, 10Nm xth 8000-48 xth 5000-24 xth 3000-12 · 70mm2 cable M8, 10Nm xth 6000-48
Protection device (battery side)* · 300A xth 8000-48 xth 5000-24 xth 3000-12 · 350A xth 3000-12

AC out connection
· 3x10mm2 cable, 1.6Nm · 3x25mm2 cable, 1.6Nm (xth 8000)
Protection device to protect cables Up to 56Aac (80Aac xth 8000), circuit breaker type B Protection device to protect people Up to 56Aac (80Aac xth 8000), RCCB/RCD, check earth scheme Overvoltage protection, SPD

AC in connection
· 3x10mm2 cable, 1.6Nm · 3x25mm2 cable, 1.6Nm (xth 8000)
Protection device AC 50Aac, circuit breaker type B Overvoltage protection, SPD

Lithium batteries communication BMS CAN

CAN

Li

¥com CAN

* Check xcom CAN manual
9

Multi units and power up
Up to 9 Xtenders in the same communication bus

T

O

O

O T

1

3

2

10

Display
Display system
on ­ AC in source present blink ­ AC input current limit is reached
on ­ bulk 1x ­ floating 2x ­ absorption 3x ­ equalization
on ­ the device is on blink ­ temporarily stopped due to a fault (Auto restart) or idle mode by master unit in multi units

on ­ AC out present 230V / 120V ac blink ­ standby, load search

Blinking indicator

AC out AC in Charge ON OFF

1x Load search
1x Input limited 1x Floa. 2x Absorbtion 3x Equalize 1x Auto restart 1x Battery low 2x Overload 3x Overtemp. 4x Bat. over volt.

on ­ the device is off blink ­ error, check the manual

Manual ON/OFF Button

Stop acoustic warning
11

Configuring the xtender

rcc 02/03

0 Vac 0 Aac

xtender
L1 1 231 Vac 0.03 kW

1A

ON

2I

27.7 Vdc

-2 Adc

xtender setting

configuration assistant

Displaying real time user information
Basic settings

Configurating parameters
Basic settings Battery management and cycle Inverter AC in and transfer Auxiliary contacs 1&2 System Multi xtender system Grid feeding

Input limit max current form the source {1107}

Max battery charge current {1138}

Lead-acid · Configure charge profile
according to manufacturer
Lithium (comm BMS, xcom CAN) · Check compatibility list and
xcom CAN manual
Others : NiCd, NiFe, Redoxflow, saltwater, etc. · Check battery manufacturer

12

Multi units
3 phase and parallel combination
L3 L1 L2 L3
L2 L1 N
variotrack, variostring

L3 L2 L1 N
Automatic detection and configuration for 3 phase and multi unit system
Solar priority for self comsumption In combination with a vario
Automatic start generator & self consumption configuration See FAQ section !
13

Technical data

IP 20
Protection Class I

xth

xth

xth

xth

3000-12 5000-12 6000-24 8000-48

Batt norminal voltage Batt charge current Batt min-max voltage

12Vdc 24Vdc 48Vdc 48Vdc 160Adc 140Adc 100Adc 120Adc 9.5-17Vdc 19-34Vdc 38-68Vdc 38-68Vdc

AC input voltage

230V (150-265V) *120V (50-140V)

AC input max current

50A

Continuos Power Power 30min Power 5sec AC output voltage AC output frequency AC output max current

2500VA 4500VA 5000VA 7000VA

3000VA 5000VA 6000VA 8000VA

7.5kVA 12kVA 15kVA 21kVA

230V (150-245V) / *120V (50-140V)

45-65Hz (configurable)

56A

56A

56A

80A

* Version - 01 120Vac/60Hz version

Maintenance and recycling
EN Maintenance and recycling Except for the periodic check of the connections (tightening, general condition), the xtender does not require any particular maintenance. To dispose of this product, please use the service for the collection of electrical waste and observe all obligations in force in the place of purchase.
FR Entretien et recyclage À l'exception du contrôle périodique des branchements (serrage, état général), le xtender ne nécessite pas d'entretien particulier. Pour vous débarrasser de ce produit, veuillez utiliser les services de collecte des déchets électriques et observer toutes les obligations en vigueur selon le lieu d'achat.
DE Wartung und Recycling Abgesehen von der regelmäßigen Kontrolle der Anschlüsse (Fixierung, allgemeiner Zustand) bedarf der xtender keinerlei besonderer Wartungsarbeiten. Beachten Sie bei der Entsorgung dieses Gerätes die geltenden örtlichen Vorschriften und nutzen Sie die Sammeldienste/stellen für Elektro-/Elektronik-Altgeräte.
ES Mantenimiento y reciclaje A excepción del control periódico de las conexiones (apriete, estado general), el xtender no requiere un mantenimiento particular. Para la eliminación del producto, acuda a los servicios de recogida de residuos eléctricos y cumpla todas las obligaciones vigentes en el lugar de compra.

Serial Number : Installed by :
Date : Signature :
Call our specialists +41 27 205 60 80 or visit studer-innotec.com/support Studer Innotec SA rue des Casernes 57 1950 Sion, Switzerland info@studer-innotec.com
© All rights reserved Studer Innnotec SA ­ V1.0

4O92

