LED Series

IXL Remote Annunciators

ENGINEER AND ARCHITECT SPECIFICATIONS

Models LED-1 and LED-2
l 8 Separate Points or Zones for Annunciating either Trouble or Alarm Conditions

l Contemporary LED Annunciator

l Surface or Semi-flush Installation

l Operates on the IXL Network Communication Line

l Field Programmable

l

Listed, ULC Listed, FM, CSFM and

NYMEA Approved

Description
Cerberus Pyrotronics Remote LED Annunciator units are designed to be used with the IXL Control Panel. It is an eight-point annunciator containing sixteen LED's for the display of trouble and alarm status or initiating devices.
LED Series Remote Annunciators can be located in the building lobby or in a protected area. In its quiescent mode of operation, all LED's are off. In the event of an alarm, a red LED will light to indicate which device or zone is in alarm. To report troubles (i.e., removal of a detector head), the corresponding yellow LED will light, indicating which devices have been programmed as a single zone, then only one LED will light regardless of the number of devices in that zone indicating the trouble condition. The Remote Annunciator may be tested by using the Lamp Test feature of the Control Panel.
Annunciators perform the important service of pinpointing the location of the alarm device or the zone from which an alarm originates.
Engineer and Architect Specifications
Remote LED annunciators will have LED's for Alarm and Trouble per point. There will be eight points per annunciator, and it shall be connected to the IXL Network Communi-

cation Line. This annunciator shall be addressable and shall not require DIP switches or jumper settings for its identification. The remote LED annunciator shall be Cerberus Pyrotronics model LED-1, LED-2.
Operation
Upon actuation of a zone, the corresponding red LED will light. Each additional actuated zone will light its corresponding LED. The Remote Annunciator can be tested using the Lamp Test feature of the Control Panel to indicate proper functioning of the LEDs.
Programming
Remote LED annunciators are field programmable. Field programming for the LED Series Remote Annunciator must be performed when a new unit is installed. Annunciators are programmed by placing the Control Panel in the programming mode and the next available address will be assigned to the annunciator when it has the programming tool applied to it.
Installation
LED Series Remote Annunciators must be installed in easily accessible locations. The unit(s) can be semi-flush wall mounted using a single gang electrical box. Multiple

9356 CATALOG NUMBER

firealarmresources.com

Remote Annunciators may be mounted side by side, by using modular electrical boxes. Add two additional gangs for each additional Remote Annunciator (i.e., use a three gang box for two annunciators). Remote Annunciators can be connected to the Network Communication Line by utilizing the screw terminals provided on the module.

Mechanical and Environmental

Input Power:

24 VDC

Operating Current:

10mA (Alarm LEDs only)

54mA (All LEDs lit)

Operating Temperature: 0°C to +49°C

Relative Humidity:

85% non-condensing

Dimensions:

41/4" H x 35/8" W x 11/16" D

Weight:

12 oz.

Optional Cabinet for

Multiple Units (12 max.): 245/8" x 141/2" x 55/8"

Mounting (Single Units): Single gang electrical box

(standard)

Ordering Information

Model No.

Part No.

Description

LED-1

5 0 0 - 6 7 9 5 8 8 Remote Annunciator Unit-White

LED-2 LED-CAB
MAG

5 0 0 - 6 7 9 5 9 4 Remote Annunciator Unit-Black Annunciator Cabinet (Max. 12
500-679649 LED-1s or LED-2s)
5 0 0 - 6 7 9 6 0 1 Programming Tool

Wiring Diagram

NOTICE: The use of other than Cerberus Pyrotronics detectors and bases with Cerberus Pyrotronics control equipment will be considered a misapplication of Cerberus Pyrotronics equipment and as such void all warranties either expressed or implied with regards to loss, damage, liabilities and/or service problems.

Cerberus Pyrotronics 8 Ridgedale Ave. Cedar Knolls, NJ 07927 Tel: (201) 267-1300 FAX: (201) 397-7008

3/94 10M CPY-IG
Printed in U.S.A.

Cerberus Pyrotronics 50 East Pearce Street
Richmond Hill, Ontario L4B, 1B7 CN Tel: (905) 764-8384
FAX: (905) 731-9182

firealarmresources.com

March 1994 Supersedes sheet dated 8/93



References

Acrobat PDFWriter 3.0 for Windows