Owner's Manual for Honeywell models including: TC300B-G, TC300C-G, TC321B-G, TC320B-G, TC320C-G, TC320C-N, TC300 Thermostats, TC300, Thermostats
Honeywell (Beijing) Technology Solutions Labs Co.,Ltd. 00011 2ARTN-00011 2ARTN00011 00011
File Info : application/pdf, 11 Pages, 2.52MB
DocumentDocumentTC300 THERMOSTATS CONNECTED DEVICE FOR COMMERCIAL BUILDINGS TC300 thermostat models are advanced, highly configurable devices providing building automation connectivity well-suited for indoor commercial building applications. These models offer flexible I/O options that will satisfy the needs of most 2-pipe or 4-pipe fan coil applications, 1H/1C conventional, and 2H/1C heat pump. Supported functions include dehumidification with reheat using an embedded humidity sensor, auxiliary heat functions, and a more rapid transitional 2-pipe system seasonal changeover. There are 6 thermostat models available TC300B-G, TC300C-G, TC321B-G, TC320B-G, TC320C-G and TC320C-N. The TC300 models support BACnet MS/TP and Modbus communications, while the TC320 and TC321 models also support BACnet IP via Wi-Fi. All models have intelligent control algorithms, scheduling, and an intuitive touchscreen interface. The B models support low voltage power input, while the C models support line voltage power input. The TC320 and TC321 models also have Wi-Fi and Bluetooth connectivity. FEATURES AND HIGHLIGHTS CONVENIENT FOR USERS · Color, capacitive-touch screen display for intuitive, fast commissioning and exceptional user experience. · Embedded system monitoring screen for equipment and I/O status. · Customizable inactive display modes, Auto dim display, always on, or dark mode. · An LED ring indicator to show the operational status. · Real-Time Clock time-keeping accuracy with 72-hour retention during power loss. EASY FOR CONTRACTORS · Fan coil, 2H/1C Heat pump, 1H/1C Conventional-Water Source Heat Pump with water valve enable/ lock-out, On/Off Valve, Floating Valve, Modulating Valve, and 6-Way Modulating Valve. · 1-3 or variable speed fan · Dehumidification with and without reheat. · Enhanced 2-pipe fan coil functionality during seasonal or system changeover delivering improved occupant comfort. · Service mode for manually enabling outputs for quicker diagnostics and equipment testing. · Auxiliary heating options supporting peripheral or supplemental types. · Auto mode to switch between heating and cooling according to the current space temperature. · Staging control, PID Tuning, DAT Lockout, Modulating control, Compressor time delay. · System Switch and Ventilation options. · Integration with various external wired sensor types including Discharge air temperature, Drain pan, Occupancy, Proof of airflow, Proof of water flow, Space temperature, Outdoor air temperature, and Humidity. · Complies with ASHRAE guideline 36-2021, Section 5.22 sequence of operations for high-performance operation when using floating/ modulating valves and multispeed/variable speed fan. · Advanced commercial control algorithms such as auto changeover. CONNECTED FOR FACILITY MANAGERS · Thermostat can be configured via its own LCD human-machine interface (HMI) or a BACnet/Modbus client. · Multiple, configurable user types with customizable privileges to prevent unauthorized usage. · Customizable daily schedules include options for setting up to 10 recurring holidays (with support for floating holidays) and up to 10 specific special events. · Up to 4 schedule events per day. TECHNICAL SPECIFICATIONS ELECTRICAL CHARACTERISTICS TC320C-N Power Supply Rated voltage : 24 VAC 50/60 Hz Rated voltage : 24 VAC 50/60 Hz Working Voltage range: 20-30 VAC Working Voltage range: 20-30 VAC Rated voltage : UL listed class - 2 transformer or UL listed class - 2 transformer or IEC 100-277 VAC 50/60Hz IEC 61558 listed transformer 61558 listed transformer Rated voltage : 120 VAC(±15%) 50/60Hz Standby Power Consumption (Display On, All DOs Off, All 1.5 VA@24 VAC(65 mA@24 VAC UIOs As Input) 2.0 VA@24 VAC (85 mA@24 VA 3.3 VA@Rated voltage 3.3 VA@Rated voltage Max. Load 96 VA (all DOs ON) 96 VA (all DOs ON) 1200 VA@120 VAC 1500VA@240/277 VAC 1200 VA@120 VAC (all DOs ON) (all DOs ON) Rated Impulse Voltage 500 V 500 V 2.5 KV 2.5 KV (Overvoltage Category II) (Overvoltage Category III) Pollution Degree 2 Relay Type Type 1, Form B DO/DIO Combined Max. Current Limit Total current cannot exceed 4 A Total current cannot exceed 10 A USER INTERFACE PARAMETER Display Type Backlight LED Color Ring SPECIFICATIONS Capacitive touch TFT, 320x240 pixels, 2.4 in. diag. LCD (Dimmable) Blue (cooling), Orange (heating) OPERATING ENVIRONMENT PARAMETER Ambient Operating Temperature Ambient Operating Humidity Storage Temperature Protection Class SPECIFICATIONS Range: 32 to 122 °F (0 to 50 °C) 10 to 90 % relative humidity (non-condensing) -40 to 150 °F(-40 to 65.5 °C) IP20 ONBOARD SENSORS PARAMETER Temperature Humidity SPECIFICATIONS Range: 32 to 122 °F (0 to 50 °C) Resolution: 1 °F (0.5 °C) Control Accuracy: ±1.5 °F (0.8 °C) at 60 to 85 °F (15 to 30 °C) Range: 20 to 90 % RH Resolution: 1 % RH Accuracy: ±5 % RH at 77 °Fc25 °C COMPLIANCES SKU TC300B-G TC320B-G Certificates CE, FCC, ICES, UL/cUL, RoHS, REACH, Prop65 Standards EN 60730-1 EN 60730-2-9 UL60730-1 UL60730-2-9 Title 47 part 15 subpart B ICES-003 EN 60730-1 EN 60730-2-9 UL60730-1 UL60730-2-9 Title 47 part 15 subpart B Title47 part15 subpart C ICES-003 RSS247 EN 300 328 EN 301 489-1 EN 301 489-17 EN 62479 EN 62311 TC300C-G TC320C-G CE, FCC, ICES, RoHS, REACH, Prop65 TC320C-N UL/cUL, FCC, ICES, RoHS, REACH, Prop65 EN 60730-1 EN 60730-2-9 Title 47 part 15 subpart B ICES-003 EN 60730-1 EN 60730-2-9 Title 47 part 15 subpart B Title47 part15 subpart C ICES-003 RSS247 EN 300 328 EN 301 489-1 EN 301 489-17 EN 62479 EN 62311 UL60730-1 UL60730-2-9 Title 47 part 15 subpart B Title47 part15 subpart C ICES-003 RSS247 TC300 Thermostats Product Datasheet | buildings.honeywell.com | 2 WIRED AND WIRELESS TECHNOLOGIES PARAMETER SylkTM BACnet MS/TP Modbus RTU BACnet IP (TC320B/TC320C/ TC321B) Wi-Fi 2.4 GHz (TC320B/ TC320C/TC321B) Bluetooth (TC320B/TC320C/ TC321B) SPECIFICATIONS Honeywell SylkTM, 2-wire Bus RS485 (9.6, 19.2, 38.4, 76.8, 115.2 Kbps) RS485 (1.2 to 115.2 Kbps) Over Wi-Fi IEEE802.11 b/g/n NONE WPA_PSK WPA_WPA2_PSK WPA2_PSK WPA2_WAP3_PSK WPA3_PSK BLE 5.0 Class 2 IEEE802.15.4 Open Thread EIRP INFORMATION STANDARD Wi-Fi 2.4GHz for CE BLE for CE MAX EIRP 20dBm 10dBm TC300 MODELS SKU INPUT POWER WIRELESS WIRED COMMUNICATIONS EQUIPMENT TYPES TC300B-G TC320B-G/ TC321B-G 24 VAC TC300C-G TC320C-G 100-277 VAC TC320C-N 120 VAC No Wi-Fi/BACnet IP, Bluetooth No RS485 BACnet MS/TP Modbus RTU FCU - 4 Pipe/2 Pipe 2H/1C Heat Pump (air/ water source) 1H/1C Conventional Wi-Fi/BACnet IP, Bluetooth FCU - 4 Pipe/2 Pipe OUTPUTS 3 x DO (24 VAC) 2 x DIO 3 x UIO 5 x DO (100-277 VAC) 3 x UIO ACCESSORY PART NUMBER TRTC-DECOPLATE-1 Note: The accessory is available in separate order. DESCRIPTION Decorative wall plate, TR and TC Series 3 DIMENSIONS ALL MODELS THERMOSTATS All Models front view 3.93" (100 mm) 4.47" (113.6 mm) TC300B/ TC320B/ TC321B 1.02" (26 mm) TC300C/ TC320C 1.24" (31.5 mm) 5.51" (140 mm) 0.76" (19.4 mm) 0.82" (21 mm) 0.27" (7 mm) 5.51" (140 mm) TC300 Thermostats Product Datasheet | buildings.honeywell.com | 4 TERMINAL LAYOUT TC300B/TC320B/TC321B (24 VAC) TERMINAL NAME UIO1 COM UIO2 COM UIO3 RS485 SLAVE RS485 SLAVE SYLK MASTER SYLK MASTER DO1 DO2 DO3 DIO1 TERMINAL NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 TERMINAL LABEL UIO1 COM UIO2 COM UIO3 + DO1 DO2 DO3 13 DIO1 DIO2 24 VAC POWER 24 VAC POWER COM 14 15/16 17 18 DIO2 R C COM DESCRIPTION Universal input/output Common Universal input/output Common Universal input/output BACnet/Modbus Communications BACnet/Modbus Communications Sylk bus Sylk bus Relay output Relay output Relay output Relay output Analog input Dry contact digital input Relay output Analog input Dry contact digital input 24 VAC power from Class2 transformer 24 VAC common (Neutral) from Class2 transformer Common 5 -G -G TERMINAL NAME UIO1 COM UIO2 COM UIO3 RS485 SLAVE RS485 SLAVE SYLK MASTER SYLK MASTER DO1 DO2 DO3 DO4 DO5 100 to 277 VAC POWER 100 to 277 VAC POWER TERMINAL NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15/16 17 TERMINAL LABEL UIO1 COM UIO2 COM UIO3 + DO1 DO2 DO3 DO4 DO5 L N DESCRIPTION Universal input/output Common Universal input/output Common Universal input/output BACnet/Modbus Communications BACnet/Modbus Communications Sylk bus Sylk bus Relay output Relay output Relay output Relay output Relay output Line - Line voltage power input Neutral - Line voltage power input TC300 Thermostats Product Datasheet | buildings.honeywell.com | 6 TERMINAL NAME UIO1 COM UIO2 COM UIO3 RS485 SLAVE RS485 SLAVE SYLK MASTER SYLK MASTER DO1 DO2 DO3 DO4 DO5 120 VAC POWER 120 VAC POWER TERMINAL NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15/16 17 TERMINAL LABEL UIO1 COM UIO2 COM UIO3 + DO1 DO2 DO3 DO4 DO5 L N DESCRIPTION Universal input/output Common Universal input/output Common Universal input/output BACnet/Modbus Communications BACnet/Modbus Communications Sylk bus Sylk bus Relay output Relay output Relay output Relay output Relay output Line - Line voltage power input Neutral - Line voltage power input TC300 Thermostats Product Datasheet | buildings.honeywell.com | 6 TERMINAL ASSIGNMENT TERMINAL ASSIGNMENT TYPE TC300B/ TC320B/ TC321B (Digital Output) TC30OC/ TC320C (Digital Output) TC300B/ TC320B/ TC321B (Universal Input/ Output) TERMINAL LABEL DO1 DO1 DO2 DO2 D03 DO3 DIO1 DIO1 DIO2 DIO2 DO1 DO2 D03 DO4 DO5 UIO1 UIO2 UIO3 DO1 DO2 D03 DO4 DO5 UIO1 UIO2 UIO3 DEFAULT On/Off Heat On/Off Cool NA NA Fan command On/Off Heat On/Off Cool Low Speed Fan Medium Speed Fan High Speed Fan /Fan Command NA NA NA INPUTS NA NA NA Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Airflow, Pipe Sensor, Space Temp Sensor, Changeover Switch, Proof of Waterflow, Outdoor Air Sensor, Shutdown Sensor, Customized1, Customized2, Customized3 Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Airflow, Pipe Sensor, Space Temp Sensor, Changeover Switch, Proof of Waterflow, Outdoor Air Sensor, Shutdown Sensor, Customized1, Customized2, Customized3 NA NA NA NA NA Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Airflow, Pipe Sensor, Space Temp Sensor, Changeover Switch, Proof of Waterflow, Outdoor Air Sensor, Shutdown Sensor, Customized1, Customized2, Customized3 OUTPUTS Heating On/Off, Heating Floating Open, Cooling Floating Open, Valve On/Off, Valve Floating Open, Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat, Heat Stage1(Heat/Cool Stage1 for heat pump), Valve Stage1 Note: FCU changeover valve used to switch between heating and cooling modes Heating Floating Close, Cooling Floating Close, Cooling On/Off, Valve Floating Close, Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat, Cool Stage1, Reversing Valve, Dehumidifier, Humidifier Cooling Floating Open, Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat, Heat Stage1, Cool Stage1, Water Flow Valve, Dehumidifier, Humidifier Cooling Floating Close, Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat, Dehumidifier, Humidifier Changeover Valve, Fan Command, High Speed Fan, Medium Speed Fan, Low Speed Fan, Auxiliary Heat, Dehumidifier, Humidifier Heating On/Off, Valve On/Off, Changeover Valve, Auxiliary Heat, Heat Stage1, Valve Stage1 Cooling On/Off, Changeover Valve, Auxiliary Heat, Cool Stage1 Changeover Valve, Low Speed Fan, Auxiliary Heat, Heat Stage1, Cool Stage1 Changeover Valve, Medium Speed Fan Auxiliary Heat Changeover Valve, Fan Command, High Speed Fan, Auxiliary Heat 6-Way Valve, Modulating Cool , Modulating Heat, Modulating Valve, Variable Speed Fan TC300B/ TC320B/ TC321B/ TC300C/ TC320C (Universal Input/ Output) UIO1 UIO2 UIO3 UIO1 NA UIO2 NA UIO3 NA Discharge Air Sensor, Drain Pan Sensor, Occupancy Sensor, Proof of Airflow, Pipe Sensor, Space Temp Sensor, Changeover Switch, Outdoor Air Sensor, Shutdown Sensor 6-Way Valve, Modulating Cool , Modulating Heat, Modulating Valve, Variable Speed Fan 7 WIRING SKU TC30OB/ TC320B/ TC321B TC30OC/ TC320C TERMINAL WIRE GAUGE NORMAL LOAD FAN TYPE R, C 14-18 AWG 0-4 A 0-96 VA@24 VAC DO 14-26 AWG 0-1 A 0-24 VA@24 VAC Others 14-26 AWG N/A 14 AWG 0-10 A 0-1200 VA@120 VAC 0-1500 VA@240 VAC 0-1500 VA@277 VAC 1-3 Speed L,N 16 AWG 0-7 A 0-1500 VA@240 VAC 0-1500 VA@277 VAC fan 24-26 AWG 0-2 A 0-240 VA@120 VAC 0-480 VA@240 VAC 0-550 VA@277 VAC Variable speed fan DO4, DO5 14-16 AWG 0-6 A 0-720 VA@120 VAC 24-26 AWG 0-2 A 0-240 VA@120 VAC 0-720 VA@240 VAC 0-480 VA@120 VAC 0-830 VA@277 VAC 0-550 VA@277 VAC 1-3 Speed fan Variable speed fan DO1-DO3 14-22 AWG 0-3 A 0-360 VA@120 VAC 24-26 AWG 0-2 A 0-240 VA@120 VAC 0-720 VA@240 VAC 0-480 VA@240 VAC 0-830 VA@277 VAC 0-550 VA@277 VAC 3-Speed fan Variable speed fan WIRE TYPE Copper Others 14-26 AWG N/A Note: The recommended wire gauge 14-26 AWG (0.2-1.5 mm² for solid or stranded, max 2.5 mm² for solid). Use supply wires suitable for at least 105 °C for TC300C/TC320C models. IO CHARACTERISTICS PARAMETER All models UIO x 3 DIO x 2 TC300B/TC320B/TC321B TC30OC/TC320C DO x 3 DIO x 2 DO1 DO2 DO3 DO4 DO5 SPECIFICATIONS · Resistive Temperature Sensor Input - NTC10K Type II, C7021 series - NTC10K Type III, C7023 series - NTC20K, TR21, and C7041 series · Digital Input - Dry contact closure - Open circuit ( 100 Kohms) - Closed circuit (100 ohms) · Voltage Output - 0-10 V, ±1.5% of full scale @2 Kohms · Resistive Temperature Sensor Input - NTC10K Type II, C7021 series - NTC10K Type III, C7023 series - NTC20K, TR21, and C7041 series · Digital Input - Dry contact closure - Open circuit ( 100 Kohms) - Closed circuit (100 ohms) · Relay Output · Rated Average Current - 1 A Resistive at 24 VAC · Rated Pulse Current - 3.5 A Resistive at 24 VAC · Relay Output · Rated Average Current - 3 A Inductive at 100-277 VAC · Power Factor > 0.85 · Relay Output · Rated Average Current - 6 A Inductive at 120 VAC - 3 A Inductive at 240-277 VAC · Power Factor > 0.85 TC300 Thermostats Product Datasheet | buildings.honeywell.com | 8 SUPPORTED SENSORS AND FUNCTIONS SENSORS Occupancy Sensor OPTIONS Direct (Normally Open) Reverse (Normally Closed) Proof Of Air Flow Sensor Direct (Normally Open) Reverse (Normally Closed) Discharge Air Temperature Sensor NTC 20K NTC 10K Type II NTC 10K Type III Sylk Space Temperature Sensors NTC 20K NTC 10K Type II NTC 10K Type III Sylk Pipe Sensor Changeover Switch Drain Pan / Leak Detector Proof of Water Flow Sensor Shutdown sensor Customized sensor (remote monitoring) NTC 20K NTC 10K Type II NTC 10K Type III Closed with heat Closed with cool Direct (Normally Open) Reverse (Normally Closed) Direct (Normally Open) Reverse (Normally Closed) Direct (Normally Open) Reverse (Normally Closed) Digital Input - NO or NC Analog Input - 0-10VDC - 0-100% scaled Temperature Input - NTC 20K, NTC 10K. PART NUMBERS Dry contact occupancy sensor DPS200 DPS400 DPS1000 MCS, CS, CSP current switches (Dry contact switches) C7250A C7041 C7021 C7023 C7400S TR21 C7041, C7772A, C7021, C7772F, C7023, C7772G, TR40, TR40-H, TR40-CO2, TR40-H-CO2, TR50-3N, TR50-3D C7250A C7041 C7021 C7023 Digital input Dry contact float switch or water sensor Dry contact pressure switch Digital input Digital input Analog input GENERAL SAFETY INFORMATION · When performing any work (installation, mounting, start-up), all manufacturer instructions and in particular the Mounting and Installation Instructions guide (31-00642) and the user guide (31-00644) are to be observed. · The thermostats be installed and mounted only by authorized and trained personnel. · Rules regarding electrostatic discharge should be followed. · If the thermostats are modified in any way, except by the manufacturer, all warranties concerning operation and safety are invalidated. · Make sure that the local standards and regulations are always observed. · Use only accessory equipment that comes from or has been approved by Honeywell. · It is recommended that out-of-the-box devices be kept at room temperature for at least 24 hours before applying power. This is to allow any condensation resulting from low shipping/storage temperatures to evaporate. · Investigated according to United States Standard UL60730-1, UL60730-2-9, EN 60730-1 and EN 60730-2-9. · Do not open the thermostats, as they contain no user-serviceable parts inside! · For TC300B/TC320B/TC321B models, CE declarations according to EMC Directive 2014/30/EU. · For TC320C models, CE declarations according to RED Directive 2014/53/EU. · For TC300C models, CE declarations according to Low Voltage Directive 2014/35/EU. · The thermostats are Class B digital apparatus and comply with Canadian ICES-003. · This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. · Caution: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. · Prudence: Les changements ou modifications apportés à cet appareil non expressément approuvés par la partie responsable de la conformité pourraient annuler le droit de l'utilisateur à utiliser l'équipement. · This device contains license-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic Development Canada's license-exempt RSS(s). Operation is subject to the following two conditions: - This device may not cause interference. - This device must accept any interference, including interference that may cause undesired operation of the device. 9 · L'émetteur/récepteur exempt de licence contenu dans le présent appareil est conforme aux CNR d'Innovation, Sciences et Développement économique Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes: - L'appareil ne doit pas produire de brouillage; - L'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement. · This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: - Reorient or relocate the receiving antenna. - Increase the separation between the equipment and receiver. - Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. - Consult the dealer or an experienced radio/TV technician for help. · Limited by local law regulations, version for North America does not have region selection option. · To satisfy FCC&IC&CE RF exposure requirements, a separation distance of 20 cm or more should be maintained between the antenna of this device and persons during device operation. To ensure compliance, operations at closer than this distance is not recommended. · Les antennes installées doivent être situées de facon à ce que la population ne puisse y être exposée à une distance de moin de 20 cm. Installer les antennes de facon à ce que le personnel ne puisse approcher à 20 cm ou moins de la position centrale de l' antenne. Region Selection (for Wi-Fi 2.4G device). SAFETY INFORMATION The thermostats are intended for commercial environments. The thermostats are independently mounted electronic control systems with fixed wiring. The thermostats are used for the purpose of building HVAC control and are suitable for use only in non-safety controls for installation on or in appliances. Note: All images used in this document are for illustrative purposes only and may not match the actual product. L L R CR US LISTED By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys' fees, arising out of, or resulting from, any modification to the literature by you. Honeywell | Building Automation 715 Peachtree Street, N.E., Atlanta, Georgia, 30308, United States. https://buildings.honeywell.com @U.S. Registered Trademark © 2024 Honeywell International Inc. 31-00645-03 | Rev. 07-24