Danfoss CF-MC Master Controller Installation Guide

MAKING MODERN LIVING POSSIBLE

Brand: Danfoss

1. Introduction

The CF-MC Master Controller is part of the new trend-setting CF2+ wireless hydronic floor heating control system from Danfoss. Based on 2-way wireless communication technology CF2+ offers high transmission safety, easy wireless installation, a high level of individual room temperature control, and thus optimal comfort and improved energy efficiency. The system includes a CF-MC Master Controller with short-circuit protected outputs, regulation by Pulse Width Modulation (PWM) principles, an away function, separate relays for both pump and boiler control, a self-diagnostic program with error indication, and wireless transmission (link) test capability with each Room Thermostat. It also offers easy wireless system access and extended functionality via the optional CF-RC Remote Controller and CF-RU Repeater Unit for extended wireless range.

2. CF2+ System Overview

The CF2+ system comprises the following components:

  • CF-MC Master Controller
  • CF-RS, -RP, -RD and -RF Room Thermostats
  • CF-RC Remote Controller
  • CF-RU Repeater Unit
  • CF-DS Dew-point Sensor
  • CF-WR Wireless Relay
  • CF-EA External Antenna

3. Functional Overview

The CF-MC Master Controller features the following controls and indicators:

  • 1: Menu selection button
  • 2: Menu LEDs
  • 3: Output and configuration selection button
  • 4: OK button
  • 5: Output LEDs
  • 6: Output cable fixing point
  • 7: Relays for pump and boiler
  • 8: Input for heating/cooling (external ON/OFF switch)
  • 9: Input for away function (8 °C) (external ON/OFF switch)
  • 10: Input for PT1000 pipe sensor
  • 11: Front cover release mechanism
  • 12: External antenna connection

4. Mounting and Installation Procedure

The wireless system's transmission range is generally sufficient, but signals can be weakened by building structures. For optimal installation and wireless signal strength:

  • Ensure no metal objects are positioned directly between the CF-MC Master Controller and Room Thermostats.
  • Route wireless signals through walls along the shortest possible diagonal path.
  • Consider installing a CF-RU Repeater Unit to optimize the wireless signal.

Note: Danfoss recommends creating an installation plan before starting.

4.1 CF-MC Master Controller Mounting

Mount the CF-MC Master Controller in a horizontal upright position.

Wall Mounting:

  • Remove the front cover (refer to Figure 4).
  • Mount using screws and wall plugs (refer to Figure 5).

DIN-Rail Mounting:

  • Attach DIN-rail mounting parts (refer to Figure 6).
  • Click the unit onto the DIN-rail (refer to Figure 7).
  • Release from DIN-rail if necessary (refer to Figure 8).

Important: Complete all CF-MC Master Controller installations before connecting to a 230 V power supply.

4.2 24 V Actuators

  • Connect the two actuator wires to an output terminal (refer to Figure 9).
  • Secure the cable using the appropriate fixing for round (Figure 10) or flat/squared (Figure 11) cables.

Note: For NC (normally closed) actuators used with Pulse Width Modulation (PWM) regulation for floor heating, no further actuator output configuration is required (see Chapter 6.1).

4.3 Relays for Pump and Boiler Control

  • Pump: Connect the live wire (L) from an external power supply to the Pump Relay. Ensure the power supply is switched off before connecting. Complete other pump connections according to local regulations (refer to Figure 12). Secure the cable (Figure 13).
  • Boiler: Connect the live wire (L) from an external power supply to the Boiler Relay. Ensure the power supply is switched off before connecting. Complete other boiler connections according to local regulations.

Note: The pump and boiler relays are potential-free contacts and cannot be used as a direct power supply. Maximum load: 230 V and 8 A/2 A (inductive).

4.4 Input for Away Function

  • Connect the two wires from an external ON/OFF switch to the Away Function input terminals (refer to Figure 14).
  • When this switch is closed (ON), the system will override the current set point for all room thermostats to 8 °C.
  • Secure the cable (Figure 15).

Note: The Away Function sets a fixed room temperature of 8 °C for all Room Thermostats, which can be adjusted via the CF-RC Remote Controller. If the system is configured for cooling, a dew-point sensor can be connected instead of an external switch.

4.5 Input for Heating and Cooling

  • Connect both wires from an external ON/OFF switch to the heating and cooling input terminals (refer to Figure 16).
  • When the switch is closed (ON), the system switches between heating and cooling modes.
  • Secure the cable (Figure 17).

Note: In cooling mode, the actuator output activates (ON for NC actuators/OFF for NO actuators) when the room temperature exceeds the set point by 2 °C. In cooling mode, a dew-point sensor should be installed and connected to the Away Function input, placed on the primary supply side.

4.6 Wiring Diagram

The wiring diagram illustrates connections for inputs (PT1000, Away Function, Heating/Cooling), relays (Pump, Boiler), and actuator outputs (1-10). It also shows the external antenna connection and the 230 V AC power supply (L, N, ~).

Diagram Description:

  • Inputs: PT1000 sensor, Away Function switch, Heating/Cooling switch.
  • Relays: L+N terminals for pump and boiler control.
  • Actuator Outputs: Terminals 1 through 10 for actuators.
  • Power Supply: 230 V AC, 50 Hz connection.
  • External Antenna: Connection point shown. Maximum cable length for sensors is 3 m.

4.7 Power Supply

Connect the CF-MC Master Controller power supply plug to a 230 V power supply only after all actuators, pump and boiler controls, and other inputs are installed. If the power supply plug is removed from the cable during installation, ensure the connection is made according to existing legislation.

4.8 CF-EA External Antenna

The CF-EA External Antenna is used when transmission is obstructed by large buildings, heavy construction, or metal barriers (e.g., if the CF-MC Master Controller is in a metal cabinet).

  • Remove the plastic cover from the antenna connection on the CF-MC Master Controller (refer to Figure 18).
  • Connect the CF-EA External Antenna (refer to Figure 19).
  • Position the CF-EA External Antenna on the opposite side of the transmission barrier from the CF-MC Master Controller.

4.9 More (2 to 3) CF-MC Master Controllers

For a trouble-free installation of a second or third CF-MC Master Controller, it is recommended to complete the installation of the first one. CF-MC Master Controller 1 should be connected to the local supply pump. Up to 3 CF-MC Master Controllers can be connected in one system. If 2 or 3 controllers are used, connect them to a 230 V power supply within 1.5 meters of CF-MC Master Controller 1 to allow simultaneous handling.

Initiating Installation:

  • On CF-MC Master Controller 1 (Figure 20): Use the menu selection button (1) to select 'Install' mode. The Install LED (2) will flash. Press OK (3) to activate Install mode; the Install LED (2) will turn ON.
  • On CF-MC Master Controller 2 or 3 (Figure 20): Activate installation to CF-MC Master Controller 1 by pressing OK (3). The Install LED (2) will flicker during communication and turn OFF upon completion.

Relocate CF-MC Master Controller 2 or 3 if necessary. A link test will initiate automatically upon reconnection to the 230 V power supply. If CF-MC Master Controller 2 or 3 has its own pump, its relays must be configured accordingly (see Chapter 6.5).

Note: Later removal of CF-MC Master Controller 2 or 3 from CF-MC Master Controller 1 can only be done by resetting CF-MC Master Controller 1 (see Chapter 7.2).

4.10 CF-RS, -RP, -RD and -RF Room Thermostats

Note: Assign Room Thermostats to the CF-MC Master Controller within a distance of 1.5 meters.

Activating Install Mode:

  • On CF-MC Master Controller (Figure 20): Use the menu selection button (1) to select 'Install' mode. The Install LED (2) flashes. Press OK (3) to activate; the Install LED (2) turns ON.
  • On CF-RD and -RF Room Thermostats (Figures 20/21): Press the push button (10). LEDs (11) and (2) flicker during communication.
  • On CF-RS and -RP Room Thermostats (Figures 20/21): Press the push button (10)/(12). LEDs (11) and (2) flicker during communication.

Selecting Output on CF-MC Master Controller (Figure 20/22):

  • All available output LEDs (13) on the CF-MC Master Controller light up, then the first one flashes.
  • Press the output selection button (8) to select the desired output (it will flash). Confirm with OK (3).
  • All output LEDs (13) turn OFF. The selected output stays ON briefly.

Room Thermostat Installation Status (Figure 21):

  • Satisfactory: LED (11) goes OFF.
  • Not satisfactory: LED (11) flashes 5 times.

Note: A Room Thermostat can be assigned to multiple outputs by repeating the installation process.

4.11 Other System Components

Installation procedures for other system components (CF-RC Remote Controller, CF-RU Repeater Unit) are detailed in their respective instruction manuals.

4.12 Transmission Test (Link Test)

The transmission test between the CF-MC Master Controller and other system components is initiated from those components (e.g., CF-RU Repeater Unit, CF-RC Remote Controller). Refer to their instructions for specific procedures.

Room Thermostats:

When the CF-MC Master Controller receives a transmission test signal from a Room Thermostat, the assigned output(s) will flash, allowing identification of the outputs to which the thermostat is assigned (Figure 22).

Initiating Transmission Test on Room Thermostat (Figure 27):

  • Press the push button (3); LED (4) goes ON.
  • Satisfactory: LED (4) goes OFF.
  • Not satisfactory: LED (4) flashes 5 times.

No Link Connection to Room Thermostat:

  • Try relocating the Room Thermostat within the room.
  • Alternatively, install a CF-RU Repeater Unit between the CF-MC Master Controller and the Room Thermostat.

Note: CF-MC Master Controller output LED(s) connected to a Room Thermostat will flash during a Link test.

4.13 Mounting of CF-RS, -RP, -RD and -RF Room Thermostats

Mount the CF-RS, -RP, -RD, and -RF Room Thermostats sheltered from direct sunlight and other heat sources (refer to Figure 23).

Mounting with screws (Figure 24):

  • 1: Back plate
  • 2: Turning knob release (CF-RS and -RD only)
  • 3: Back plate lock/unlock (rotate 90°)
  • 4: Screw hole for wall mounting
  • 5: Battery placement
  • 6: Screw and wall plug

Note: Remove enclosed battery strips to activate. A Room Thermostat can be assigned to multiple outputs by repeating the installation process.

5. Temperature Settings

5.1 CF-RS and -RP Room Thermostat

Turning knob/cover (Figure 25):

  • 1: Turning knob/cover release

CF-RS Room temperature limitation (Figure 26):

  • 1: Minimum limitation (blue) (from 10 °C)
  • 2: Maximum limitation (red) (up to 30 °C)

5.2 CF-RD and CF-RF Room Thermostat with Digital Display (Figure 21)

SET Description
MIN Minimum temperature limitation
MAX Maximum temperature limitation
? Transmission link icon
? Low battery indicator
⚠️ Alarm icon
? Room temperature icon*
?️ Floor temperature icon*

* Only valid for CF-RF Room Thermostat.

Settings available via CF-RC Remote Controller:

  • ? Lock icon
  • ⏰ Timer icon
  • ❄️ Cooling icon**
  • ? AUTO Automatic change-over icon**
  • ? Heating icon**

** Only valid for CF-RD Room Thermostat. A standard CF-RD Room Thermostat can be defined as a master thermostat for sequential control of heating and cooling stages, according to room temperature. This function is available via the CF-RC Remote Controller.

Changing Default Display Temperature:

  • The actual room temperature is displayed by default.
  • To change the default display to actual floor surface temperature, press and hold the push button (10) until 'SET MAX' is shown.
  • Press button (10) repeatedly until or is flashing.
  • Use the up/down selector (9) to choose the new default display temperature: Room temperature or Floor surface temperature.

Setting Room Temperature:

  • Ensure the actual room temperature is displayed.
  • Use the up/down selector (9) to set the desired room temperature value. 'SET' will be shown.
  • Releasing the up/down selector (9) returns the display to the actual temperature.

Note: The thermostat regulates the floor heating system based on the room temperature set point, within the defined maximum and minimum floor surface temperature limitations.

Room Temperature Limitation:

  • Ensure the actual room temperature is displayed.
  • Press and hold the push button (10) until 'SET MAX' is shown.
  • Use the up/down selector (9) to set the maximum room temperature limitation.
  • Press button (10) briefly; 'SET MIN' is shown.
  • Use the up/down selector (9) to set the minimum room temperature limitation.
  • Press button (10) briefly; the actual floor surface temperature is shown.

Floor Surface Temperature Limitation (CF-RF only):

  • Ensure the actual floor surface temperature is displayed (indicated by ?️).
  • Press and hold the push button (10) until 'SET MAX' is also shown.
  • Use the up/down selector (9) to set the maximum floor surface temperature limitation.
  • Press button (10) briefly; 'SET MIN' is shown.
  • Use the up/down selector (9) to set the minimum floor surface temperature limitation.

IMPORTANT: Heat emission from the floor can vary, potentially affecting temperature measurement. Adjust max. and min. floor surface temperatures accordingly. Always follow the floor manufacturer's recommendations for maximum floor surface temperature. Using a mixing shunt for floor heating circuits is recommended to ensure optimal flow temperature and minimize energy consumption, preventing excessive heat transfer to the floor.

6. Configuration

6.1 Actuator Outputs

Activate Output Mode:

  • On the CF-MC Master Controller (Figure 20/22), use the menu selection button (1) to select 'Output' mode. The Output LED (5) will flash.
  • Press OK (3) to activate Output mode; the Output LED (5) turns ON.

Select Output Configuration:

Press the output selection button (8) and toggle through the possible configurations. The output LEDs will indicate the selection:

  • 1 LED: Outputs configured for NC actuators with ON/OFF regulation.
  • 2 LEDs: Outputs configured for NO actuators with ON/OFF regulation.
  • 3 LEDs: Outputs configured for NC actuators with Pulse Width Modulation (PWM) regulation for floor heating (default).
  • 4 LEDs: Outputs configured for NO actuators with Pulse Width Modulation (PWM) regulation for floor heating.
  • 5 LEDs: A Remote Controller is installed; settings cannot be changed from the CF-MC Master Controller.

Activate the selected output configuration by pressing OK (3).

Note: During periods with no output activations, the CF-MC Master Controller runs a valve motion program every 2 weeks, lasting up to 12 minutes. Individual output configuration is possible via the CF-RC Remote Controller (see separate instruction).

6.2 Relays for Pump and Boiler Control

Activate Relay Mode:

  • On the CF-MC Master Controller (Figure 20), use the menu selection button (1) to select 'Relay' mode. The Relay LED (4) flashes.
  • Press OK (3) to activate Relay mode; the Relay LED (4) turns ON.

Select Relay Configuration (Figure 20/22):

Press the output selection button (8) and toggle through the possible Relay configurations. The output LEDs indicate the selection:

  • NO LEDs: Relays are not used.
  • 1 LED: Pump control.
  • 2 LEDs: Boiler control.
  • 3 LEDs: Pump and boiler control.
  • 4 LEDs: Pump control with 2 min. start/stop delay.
  • 5 LEDs: Pump and boiler control, with 2 min. start/stop delay on pump (default).

Activate the selected relay configuration by pressing OK (3).

Note: If the pump relay is active, the CF-MC Master Controller runs a pump motion program every 3rd day for one minute. More relay configurations are available via the CF-RC Remote Controller (see separate instruction).

6.3 Input for Away Function and Heating and Cooling

Activate Input Mode:

  • On the CF-MC Master Controller (Figure 20), use the menu selection button (1) to select 'Input' mode. The Input LED (6) flashes.
  • Press OK (3) to activate Input mode; the Input LED (6) turns ON.

Select Input Configuration (Figure 20/21/22):

Press the output selection button (8) and toggle through the possible Input configurations. The output LEDs indicate the selection:

  • 1 LED: Input ports are not used.
  • 2 LEDs: System switches to cooling mode when heating/cooling input is activated (Figure 2 - 8).
  • 3 LEDs: System switches to a fixed set room temperature of 8 °C for all Room Thermostats when the away function input is activated (Figure 2 - 9).
  • 4 LEDs: System switches to cooling mode when heating/cooling input is activated (Figure 2 - 8). In heating mode, system switches to a fixed set room temperature of 8 °C for all Room Thermostats when the away function input is activated (Figure 2 - 9) (default).

Activate the selected input configuration by pressing OK (3).

6.4 Heating/Cooling

A 2-pipe system can be configured for automatic heating/cooling change-over.

  • A PT-1000 pipe sensor must be connected to the PT-1000 input (Figure 2 - 10).
  • Configuration is only possible via the CF-RC Remote Controller (see separate instruction).

6.5 Relays on more (2 to 3) CF-MC Master Controllers

If multiple CF-MC Master Controllers are connected in a system, their pump and boiler control relays should be configured separately.

Activate Relay Mode on CF-MC Master Controller 2/3 (Figure 20):

  • Use the menu selection button (1) to select 'Relay' mode. The Relay LED (4) flashes.
  • Press OK (3) to activate Relay mode; the Relay LED (4) turns ON.

Select Relay Configuration (Figure 20/22):

Press the output selection button (8) and toggle through the possible Relay configurations. The output LEDs indicate the selection:

Uses pump and boiler connected to CF-MC Master Controller 1:

  • NO LEDs: Relays are not used (default).

If local manifold and pump are separate:

  • 1 LED: Pump control.
  • 4 LEDs: Pump control with 2 min. start/stop delay.

Activate the selected relay configuration by pressing OK (3).

6.6 Wireless Relay

The CF-WR Wireless Relay can be connected to the CF-MC Master Controller and configured using the CF-RC Remote Controller (see separate instruction).

7. Replacing/Resetting the CF-MC Master Controller

7.1 When?

If the CF-MC Master Controller in an existing CF2+ system is reset to factory settings or replaced, all other CF2+ system components must also be reset to allow re-installation to the new or reset controller.

7.2 How?

Note: Only reset the CF-MC Master Controller to factory settings if normal in- and uninstallation procedures cannot be followed.

Resetting the CF-MC Master Controller (Figure 20/22):

  • Disconnect the 230 V power supply to the CF-MC Master Controller until the Power LED (7) is OFF.
  • Simultaneously press and hold the menu selection button (1), OK button (3), and output selection button (8).
  • Reconnect the 230 V power supply. Release the three buttons when the Power LED (7) and all output LEDs are ON.
  • The CF-MC Master Controller is reset when all output LEDs (13) go OFF.

Resetting the CF-RS, -RP, -RD and -RF Room Thermostats (Figure 27):

  • Remove the Room Thermostat from its back plate (1) and disconnect one battery (2).
  • Press and hold the push button (3) (Link test) and reconnect the battery (2).
  • Release the push button (3) when the red LED (4) has been ON and OFF again.
  • The Room Thermostat is now reset and ready for installation to a CF-MC Master Controller.

Resetting the CF-RC Remote Controller (Figure 28):

  • Simultaneously activate soft key (1), soft key (2), and the down selector (3).
  • The CF-RC Remote Controller will request confirmation before resetting.
  • Confirming with 'yes' resets the CF-RC Remote Controller, making it ready for installation to a CF-MC Master Controller.

Resetting the CF-RU Repeater Unit (Figure 29):

  • Disconnect the CF-RU Repeater Unit from the 230 V power supply.
  • Press and hold the push button (1) (Link test) and reconnect the 230 V power supply.
  • Release the push button (1) when the red LED (2) has been ON and OFF again.
  • The CF-RU Repeater Unit is now reset and ready for installation to a CF-MC Master Controller.

8. Technical Specifications

8.1 CF-MC Master Controller

Parameter Specification
Transmission frequency 868.42 MHz
Transmission range in normal constructions (up to) 30 m
Transmission power < 1 mW
Supply voltage 230 V AC
Actuator outputs 10 x 24 V DC
Max. continued output load (total) 35 VA
Relays 230 V AC/8 (2) A
Ambient temperature 0 - 50 °C
IP class 30

8.2 CF-RS, -RP, -RD and -RF Room Thermostats

Parameter Specification
Temperature setting range 5 - 35 °C
Transmission frequency 868.42 MHz
Transmission range in normal constructions (up to) 30 m
Transmission power < 1 mW
Battery Alkaline 2 x AA, 1.5 V
Battery lifetime (up to) 1 to 3 years
Ambient temperature 0 - 50 °C
IP class 21
Floor sensor accuracy* +/- 1 °C
Floor sensor emission coefficient* 0.9

* Only valid for CF-RF Room Thermostat.

Note: See separate instructions for other components.

9. Troubleshooting

9.1 CF-MC Master Controller

Error Indication Possible Causes
Output LED(s), alarm LED and output menu LED flash. Buzzer is ON* Output or actuator is short-circuited or the actuator is disconnected.
Output LED(s), alarm LED and input menu LED flash. Buzzer ON after 12 hours** No wireless signal from room thermostat connected to this or these outputs, or the temperature in the according room is below 5 °C. (Try to verify the function of the room thermostat by making a link test).
Output LEDs 1-4, alarm LED and input LED flash No signal from the CF-RC Remote Controller.
Output LEDs 1-5, alarm LED and input menu LED flash No signal from CF-MC Master Controller 2 or 3.
CF-MC Master controller 1: Alarm and Install LED's flash for approx. 20 sec. CF-MC Master Controller 2: Alarm LED lights up for approx. 1 sec. CF-MC Master Controller 2 has an older version of software, which is not compatible with the newer software in CF-MC Master Controller 1.

* Buzzer is shut off by pressing OK. The error indication continues until the error is fixed.

** If the room thermostat signal is lost, the CF-MC Master Controller output will be activated 15 minutes every hour for frost protection until the error is fixed.

9.2 CF-RS, -RP, -RD and -RF Room Thermostats

Error Indication Possible Causes
The LED ? and ?️ flashes every 5th minute Low battery.
The LED ? and ?️ flashes every 30 sec. Critical low battery.
The LED ?, ? and ⚠️ flashes* Critical low battery - transmission has stopped.
The LED ? and ?️ flashes 5 times Installation/Link Test is unsatisfactory.
E03 and ?* Actuator error on output (CF-MC).
E05 and ?* Room temperature below 5 °C.

* Only valid for CF-RD and -RF Room Thermostats.

Figures and Illustrations

Refer to the following figures for visual guidance:

  • Figure 1a: CF-MC Master Controller unit.
  • Figure 1b: CF-RS, CF-RP, CF-RD, and CF-RF Room Thermostats.
  • Figure 1c: CF-RC Remote Controller.
  • Figure 1d: CF-RU Repeater Unit.
  • Figure 1e: CF-DS Dew-point Sensor.
  • Figure 1f: CF-WR Wireless Relay.
  • Figure 1g: CF-EA External Antenna.
  • Figure 2: Diagram of CF-MC Master Controller with numbered components and connections.
  • Figure 3: Diagram illustrating wireless signal propagation. The left side shows signal weakening without a repeater, while the right side shows improved signal strength with the CF-RU Repeater Unit.
  • Figures 4-11: Depict steps for mounting the CF-MC Master Controller on a wall or DIN-rail, including cover removal, screw mounting, and cable fixing.
  • Figures 12-19: Illustrate wiring connections for actuators, relays, power supply, and the external antenna.
  • Figure 20: Close-up view of the CF-MC Master Controller's buttons and LEDs, with labels for Power, Alarm, Input, Output, Relay, Uninstall, and Install functions.
  • Figure 21: Shows the digital display of the CF-RD/RF Room Thermostat and its control buttons.
  • Figure 22: Back view of the CF-MC Master Controller showing terminal blocks.
  • Figure 23: Diagram showing optimal placement distances for room thermostats relative to windows and doors (e.g., 1.5m from window, 0.25m from door).
  • Figures 24-26: Detail the mounting process for Room Thermostats, including attaching the back plate, using screws, and releasing covers.
  • Figures 27-29: Illustrate the procedure for resetting Room Thermostats, the CF-RC Remote Controller, and the CF-RU Repeater Unit, showing button presses and LED indicators.

Contact Information

Danfoss A/S
Indoor Climate Solutions
Ulvehavevej 61
7100 Vejle
Denmark

Phone: +45 7488 8500
Fax: +45 7488 8501
Email: heating.solutions@danfoss.com
Website: www.heating.danfoss.com

Danfoss A/S reserves the right to alter its products without notice. All trademarks are property of their respective companies.

Models: VIUHK902, AN184786465310en-010901, CF-MC Master Controller, CF-MC, Master Controller, Controller

File Info : application/pdf, 18 Pages, 2.36MB

PDF preview unavailable. Download the PDF instead.

AN184786465310en-010901

References

Danfoss A/S GPL Ghostscript 10.03.1

Related Documents

Preview CF-WR Wireless Relay Datasheet - Danfoss
Technical datasheet for the Danfoss CF-WR Wireless Relay, a wireless accessory for the CF2+ floor heating/cooling control system. Includes specifications, wiring diagrams, and application details.
Preview Danfoss CF-RS Standard Room Thermostat - Installation and User Guide
A comprehensive guide for the Danfoss CF-RS Standard Room Thermostat, detailing its features, installation, operation, specifications, and troubleshooting steps for efficient home heating control.
Preview Danfoss CF-RC Remote Controller Instruction Manual
This document provides comprehensive instructions for the Danfoss CF-RC Remote Controller, covering installation, setup, operation, and troubleshooting. Learn how to manage heating and cooling systems efficiently.
Preview Danfoss CF-RU Repeater Unit Instruction Manual
Comprehensive guide for installing, operating, and troubleshooting the Danfoss CF-RU Repeater Unit, designed to extend wireless transmission range in Danfoss floor heating systems.
Preview Danfoss CF-RF Room Thermostat with Infrared Floor Sensor - Installation and User Guide
Comprehensive instructions for the Danfoss CF-RF Room Thermostat with Infrared Floor Sensor, covering installation, temperature settings, troubleshooting, and specifications for efficient floor heating control.
Preview Danfoss Link CC Central Controller Installation Guide for Smart Home Heating Systems
Comprehensive installation guide for the Danfoss Link CC Central Controller, a programmable wireless heating control system for homes up to 300 m². Learn how to install, configure, and manage your smart home heating solution, including device pairing, Wi-Fi setup, and software updates.
Preview Danfoss Link™ CC Central Controller Installation Guide
This guide provides comprehensive instructions for installing and setting up the Danfoss Link™ CC Central Controller. It covers system overview, installation guidelines, device pairing, Wi-Fi connection, app integration, software updates, troubleshooting, and technical specifications for a seamless wireless heating control experience in residential buildings.
Preview Anwendungsleitfaden Danfoss Icon2TM: Regelung für Warmwasser-Fußbodenheizung
Umfassender Anwendungsleitfaden für das Danfoss Icon2TM Raumtemperaturregelungssystem für Warmwasser-Fußbodenheizung. Beinhaltet Installation, Verdrahtung, Smart Home-Integration und Fehlerbehebung.