User Manual for DATAKOM models including: DKM-250 DC Energy Analyzer and Earth Leakage Detector, DKM-250, DC Energy Analyzer and Earth Leakage Detector, Earth Leakage Detector, Leakage Detector

Datakom Electronics

DKM-250 User Manual - download

DKM-250 DC - Datakom Power

DKM-250

PDF preview unavailable. Download the PDF instead.

250 DATA
DKM-250
DC ENERGY ANALYZER & EARTH LEAKAGE DETECTOR

DESCRIPTION
The DKM-250 is a precision instrument designed for measuring, displaying and remote monitoring earth leakage and various DC parameters in a DC distribution box.
The unit features a 32-bit ARM core microcontroller.
The unit is supplied from the measuring DC voltage input. Operating range is between 19 and 270VDC.
The current input of the unit is isolated from the rest of the circuit and has different circuit options:
 External current shunt (standard)  Internal current shunt  Hall Effect sensor input  4-20mA analog input
The unit has 2 digital inputs and 2 relay outputs, both of them programmable for required functions.
Thanks to its isolated RS-485 Modbus RTU comport, the device is free from ground potential difference issues and data are safely transferred to automation and monitoring systems. Program parameters may be uploaded to the unit through the RS485 port.
The unit may output any measured value as analog signal through its 4-20mA port. This output allows easy connection to PLC systems.

FEATURES
 Displays earth leakage in %  Various current input options  2 programmable relay outputs  2 programmable digital inputs  Programmable 4-20mA analog output  Demand, Min & Max records  Fully isolated RS-485 serial port  MODBUS-RTU communications  Bidirectional current & power measurement  Bidirectional kW-h energy counter  Bidirectional A-h counter  Hours run counter  Front panel programming  Wide operating temperature range  Sealed front panel (IP65 with gasket)  Two part connection system

CONNECTION DIAGRAM INSTALLATION

TECHNICAL SPECIFICATIONS

Supply Input: 19-270VDC

Power Consumption: < 4W

Voltage Measurement Input:

Measurement range: 0-300V

Accuracy: 0.5% Current Measurement Input:
Measurement range: -100mV to +100mV. Accuracy: 0.5%

Isolation: 1000V AC, 1 minute

Internal Current Shunt Option:

Measurement range: 0-15A

Analog Output: 0-20mA

Analog Output Precision: 16 bit

Digital Input Range: 19 to 270VDC

Relay Outputs: 5 Amps @ 28VDC

Serial Port:

Signal type: RS-485

Protocol:

Modbus RTU

Data Rate: 2400-38400baud

Isolation:

1000V AC, 1 minute

Operating Temp. Range: -20°C...+70 °C (-4°F...158°F)
Max. Relative Humidity: %95 non-condensing

Protection Degree: IP 65 (Front panel, w. gasket) IP 30 (Back panel)
Enclosure: Flame retardent, ROHS compliant high temperature ABS/PC (UL94-V0)
Installation: Flush mounting with rear brackets Dimensions: 102x102x53mm (WxHxD)

Panel Cutout: 92x92mm

Weight: 200 gr

EU Directives: 2014/35/EC (LVD) 2014/30/EC (EMC)

Reference Standards: EN 61010 (safety) EN 61326 (EMC)

PANEL CUTOUT

