Installation Instructions
Original Instructions

POINT I/O ControlNet Adapter

Catalog Numbers 1734-ACNR, 1734-ACNRK

Catalog numbers with the suffix `K' are conformal coated and their specifications are the same as non-conformal coated catalogs.

Topic

Page

Summary of Changes

1

About the Adapter

5

Before You Begin

5

Install the ControlNet Adapter

6

Set the Node Address

6

Install a Replacement ControlNet Adapter to an Existing System

6

Wire the ControlNet Adapter

7

Interpret the Status Indicators

8

Specifications

9

Additional Resources

11

Summary of Changes

This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes.

Topic

Page

Updated General Specifications

9

Updated Certifications

11

Updated Additional Resources

11

POINT I/O ControlNet Adapter Installation Instructions

ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

ATENCIÓN: Antes de instalar, configurar, poner en funcionamiento o realizar el mantenimiento de este producto, lea este documento y los documentos listados en la sección Recursos adicionales acerca de la instalación, configuración y operación de este equipo. Los usuarios deben familiarizarse con las instrucciones de instalación y cableado y con los requisitos de todos los códigos, leyes y estándares vigentes. El personal debidamente capacitado debe realizar las actividades relacionadas a la instalación, ajustes, puesta en servicio, uso, ensamblaje, desensamblaje y mantenimiento de conformidad con el código de práctica aplicable. Si este equipo se usa de una manera no especificada por el fabricante, la protección provista por el equipo puede resultar afectada. ATENÇÃO: Leia este e os demais documentos sobre instalação, configuração e operação do equipamento que estão na seção Recursos adicionais antes de instalar, configurar, operar ou manter este produto. Os usuários devem se familiarizar com as instruções de instalação e fiação além das especificações para todos os códigos, leis e normas aplicáveis. É necessário que as atividades, incluindo instalação, ajustes, colocação em serviço, utilização, montagem, desmontagem e manutenção sejam realizadas por pessoal qualificado e especializado, de acordo com o código de prática aplicável. Caso este equipamento seja utilizado de maneira não estabelecida pelo fabricante, a proteção fornecida pelo equipamento pode ficar prejudicada.
:    , ,     ,     ,    « ».       ,     .          ,       ,   .  ,  , ,   , , ,    ,           .       ,     .
:

ACHTUNG: Lesen Sie dieses Dokument und die im Abschnitt ,,Weitere Informationen"aufgeführten Dokumente, die Informationen zu Installation, Konfiguration und Bedienung dieses Produkts enthalten, bevor Sie dieses Produkt installieren, konfigurieren, bedienen oder warten. Anwender müssen sich neben den Bestimmungen aller anwendbaren Vorschriften, Gesetze und Normen zusätzlich mit den Installations- und Verdrahtungsanweisungen vertraut machen.

Arbeiten im Rahmen der Installation, Anpassung, Inbetriebnahme, Verwendung, Montage, Demontage oder Instandhaltung dürfen nur durch ausreichend geschulte Mitarbeiter und in Übereinstimmung mit den anwendbaren Ausführungsvorschriften vorgenommen werden.

Wenn das Gerät in einer Weise verwendet wird, die vom Hersteller nicht vorgesehen ist, kann die Schutzfunktion beeinträchtigt sein.

ATTENTION : Lisez ce document et les documents listés dans la section Ressources complémentaires relatifs à l'installation, la configuration et le fonctionnement de cet équipement avant d'installer, configurer, utiliser ou entretenir ce produit. Les utilisateurs doivent se familiariser avec les instructions d'installation et de câblage en plus des exigences relatives aux codes, lois et normes en vigueur.

Les activités relatives à l'installation, le réglage, la mise en service, l'utilisation, l'assemblage, le démontage et l'entretien doivent être réalisées par des personnes formées selon le code de pratique en vigueur.

Si cet équipement est utilisé d'une façon qui n'a pas été définie par le fabricant, la protection fournie par l'équipement peut être compromise.

:

, ,

,

.

,

.

, , , , , ,

.

. ATTENZIONE Prima di installare, configurare ed utilizzare il prodotto, o effettuare interventi di manutenzione su di esso, leggere il presente documento ed i documenti elencati nella sezione "Altre risorse", riguardanti l'installazione, la configurazione ed il funzionamento dell'apparecchiatura. Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio, oltre ai requisiti previsti dalle leggi, codici e standard applicabili.

Le attività come installazione, regolazioni, utilizzo, assemblaggio, disassemblaggio e manutenzione devono essere svolte da personale adeguatamente addestrato, nel rispetto delle procedure previste.

Qualora l'apparecchio venga utilizzato con modalità diverse da quanto previsto dal produttore, la sua funzione di protezione potrebbe venire compromessa.

DKKAT: Bu ürünün kurulumu, yapilandirilmasi, iletilmesi veya bakimi öncesinde bu dokümani ve bu ekipmanin kurulumu, yapilandirilmasi ve iletimi ile ilgili lave Kaynaklar bölümünde yer listelenmi dokümanlari okuyun. Kullanicilar yürürlükteki tüm yönetmelikler, yasalar ve standartlarin gereksinimlerine ek olarak kurulum ve kablolama talimatlarini da örenmek zorundadir.

Kurulum, ayarlama, hizmete alma, kullanma, parçalari birletirme, parçalari sökme ve bakim gibi aktiviteler sadece uygun eitimleri almi kiiler tarafindan yürürlükteki uygulama yönetmeliklerine uygun ekilde yapilabilir. Bu ekipman üretici tarafindan belirlenmi amacin diinda kullanilirsa, ekipman tarafindan salanan koruma bozulabilir.

 





 POZOR: Nez zacnete instalovat, konfigurovat ci provozovat tento výrobek nebo provádt jeho údrzbu, pectte si tento dokument a dokumenty uvedené v cásti Dodatecné zdroje ohledn instalace, konfigurace a provozu tohoto zaízení. Uzivatelé se musejí vedle pozadavk vsech relevantních vyhlásek, zákon a norem nutn seznámit také s pokyny pro instalaci a elektrické zapojení.

Cinnosti zahrnující instalaci, nastavení, uvedení do provozu, uzívání, montáz, demontáz a údrzbu musí vykonávat vhodn proskolený personál v souladu s píslusnými provádcími pedpisy.

Pokud se toto zaízení pouzívá zpsobem neodpovídajícím specifikaci výrobce, mze být narusena ochrana, kterou toto zaízení poskytuje.

UWAGA: Przed instalacj, konfiguracj, uytkowaniem lub konserwacj tego produktu naley przeczyta niniejszy dokument oraz wszystkie dokumenty wymienione w sekcji Dodatkowe ródla omawiajce instalacj, konfiguracj i procedury uytkowania tego urzdzenia. Uytkownicy maj obowizek zapozna si z instrukcjami dotyczcymi instalacji oraz oprzewodowania, jak równie z obowizujcymi kodeksami, prawem i normami.

Dzialania obejmujce instalacj, regulacj, przekazanie do uytkowania, uytkowanie, monta, demonta oraz konserwacj musz by wykonywane przez odpowiednio przeszkolony personel zgodnie z obowizujcym kodeksem postpowania.

Jeli urzdzenie jest uytkowane w sposób inny ni okrelony przez producenta, zabezpieczenie zapewniane przez urzdzenie moe zosta ograniczone.

OBS! Läs detta dokument samt dokumentet, som står listat i avsnittet Övriga resurser, om installation, konfigurering och drift av denna utrustning innan du installerar, konfigurerar eller börjar använda eller utföra underhållsarbete på produkten. Användare måste bekanta sig med instruktioner för installation och kabeldragning, förutom krav enligt gällande koder, lagar och standarder.

Åtgärder som installation, justering, service, användning, montering, demontering och underhållsarbete måste utföras av personal med lämplig utbildning enligt lämpligt bruk.

Om denna utrustning används på ett sätt som inte anges av tillverkaren kan det hända att utrustningens skyddsanordningar försätts ur funktion.

LET OP: Lees dit document en de documenten die genoemd worden in de paragraaf Aanvullende informatie over de installatie, configuratie en bediening van deze apparatuur voordat u dit product installeert, configureert, bediend of onderhoudt. Gebruikers moeten zich vertrouwd maken met de installatie en de bedradingsinstructies, naast de vereisten van alle toepasselijke regels, wetten en normen.

Activiteiten zoals het installeren, afstellen, in gebruik stellen, gebruiken, monteren, demonteren en het uitvoeren van onderhoud mogen uitsluitend worden uitgevoerd door hiervoor opgeleid personeel en in overeenstemming met de geldende praktijkregels.

Indien de apparatuur wordt gebruikt op een wijze die niet is gespecificeerd door de fabrikant, dan bestaat het gevaar dat de beveiliging van de apparatuur niet goed werkt.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a source compliant with the Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

2

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

POINT I/O ControlNet Adapter Installation Instructions

WARNING: · Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with
this product. · Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

Prevent Electrostatic Discharge ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: · Touch a grounded object to discharge potential static. · Wear an approved grounding wriststrap. · Do not touch connectors or pins on component boards. · Do not touch circuit components inside the equipment. · Use a static-safe workstation, if available. · Store the equipment in appropriate static-safe packaging when not in use.

Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments. This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to help prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to help prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see the following: · Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements. · NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

North American Hazardous Location Approval

The Following Information Applies When Operating This Equipment In Hazardous Locations.

Informations sur l'utilisation de cet équipement en environnements dangereux.

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.

WARNING: Explosion Hazard ­ · Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous. · Do not disconnect connections to this equipment unless
power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. · Substitution of components may impair suitability for Class I Division 2.

AVERTISSEMENT: Risque d'Explosion ­ · Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher l'équipement. · Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit. · La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I Division 2.

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

3

POINT I/O ControlNet Adapter Installation Instructions
UK and European Hazardous Location Approval The following applies to products marked II 3 G: · Are intended for use in potentially explosive atmospheres as defined by UKEX regulation 2016 No. 1107 and European Union Directive 2014/34/EU and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Schedule 1 of UKEX and Annex II of this Directive. · Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN IEC 60079-7, and EN IEC 60079-0. · Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Schedule 1 of UKEX and Annex II of EU Directive 2014/34/EU. See the UKEx and EU Declaration of Conformity at rok.auto/certifications for details. · The type of protection is Ex ec IIC T4 Gc according to EN IEC 60079-0:2018, EXPLOSIVE ATMOSPHERES - PART 0: EQUIPMENT - GENERAL REQUIREMENTS, Issue Date 07/ 2018, and CENELEC ENIEC 60079-7:2015+A1:2018, Explosive atmospheres. Equipment protection by increased safety "e". · Comply with Standard EN IEC 60079-0:2018, EXPLOSIVE ATMOSPHERES - PART 0: EQUIPMENT - GENERAL REQUIREMENTS, Issue Date 07/2018, CENELEC EN IEC 600797:2015+A1:2018 Explosive atmospheres. Equipment protection by increased safety "e", reference certificate number DEMKO 04 ATEX 0330347X and UL22UKEX2478X. · Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification according to UKEX regulation 2016 No. 1107 and ATEX directive 2014/34/EU. · May have catalog numbers followed by a "K" to indicate a conformal coating option.
IEC Hazardous Location Approval The following applies to products marked with IECEx certification: · Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification to IEC 60079-0. · The type of protection is Ex eC IIC T4 Gc according to IEC 60079-0 and IEC 60079-7. · Comply with Standards IEC 60079-0, Explosive atmospheres - Part 0: Equipment - General requirements, Edition 7, Revision Date 2017 and IEC 60079-7, 5.1 Edition revision date 2017, Explosive atmospheres - Part 7: Equipment protection by increased safety "e", reference IECEx certificate number IECEx UL 20.0072X. · May have catalog numbers followed by a "K" to indicate a conformal coating option.
WARNING: Special Conditions for Safe Use · This equipment is not resistant to sunlight or other sources of UV radiation. · This equipment shall be mounted in an UKEX/ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in
accordance with EN/IEC 60079-0) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The enclosure must be accessible only by the use of a tool. · This equipment shall be used within its specified ratings that are defined by Rockwell Automation. · Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage at the supply terminals to the equipment. · The instructions in the user manual shall be observed. · This equipment must be used only with UKEX/ATEX/IECEx certified Rockwell Automation backplanes. · Earthing is accomplished through mounting of modules on rail. · Devices shall be used in an environment of not more than Pollution Degree 2. · The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments.
ATTENTION: · If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. · Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this equipment
before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. · Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle the module. · This equipment is certified for use only within the surrounding air temperature range of -20...+55 °C (-4...+131 °F). The equipment must not be used outside of this range. · Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.

4

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

POINT I/O ControlNet Adapter Installation Instructions

About the Adapter

The POINT I/OTM ControlNet® adapter is a communications interface for POINT I/O modules. The adapter provides an interface for controlling and communicating with POINT I/O modules from a ControlNet network. See Figure 1 to identify the external features of the adapter.

Figure 1 - POINT I/O ControlNet Adapter

2

3

MoSdtualteus PoiSnttaBtuuss CoSnttarotulNsCetoSAnttarotulNset B 1734-ACNR

1

SysPtoewmFeierPldower

4

2

5

9 8

7 6

Description 1 Node address thumbwheel 2 Status indicators 3 Safety end cap 4 Removable Terminal Block (RTB) removable handle 5 RTB

Description 6 Coaxial channel B 7 Coaxial channel A 8 DIN rail locking screw (orange) 9 Network Address Port (NAP)

ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate-passivated steel DIN rail to ensure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. See Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more information.

Before You Begin
To use your adapter effectively, note the following considerations. · Understand Messaging Class 3 (Explicit Message) requests through the 1734-ACNR or 1734-ACNRK adapter to a specific POINT I/O module may not always receive a response from the I/O module. In the case where the I/O module does not reply to the request, the adapter responds with an error code indicating a timeout. · Establish I/O Connections When you power up a POINT I/O system and establish I/O connections, the outputs transition to the Idle state, applying Idle state data before going to RUN mode. This occurs even when the controller making the connection is already in RUN mode. · Configure Autobaud The adapter cannot reconfigure an I/O module that you previously configured to operate at a fixed baud rate. When you reuse a POINT I/O module from another POINT I/O system, configure the module to autobaud before using it with the 1734-ACNR or 1734-ACNRK adapter.

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

5

POINT I/O ControlNet Adapter Installation Instructions
Install the ControlNet Adapter
ATTENTION: You must use series C POINT I/O modules with the 1734-ACNR or 1734-ACNRK adapter. Series A and B POINT I/O modules will not work with the 1734-ACNR or 1734-ACNRK adapter.
To install the adapter on the DIN rail before installing other base units, proceed as follows: 1. Position the adapter vertically above the DIN rail. 2. Press down firmly to install the adapter on the DIN rail. The locking mechanism locks the adapter to the DIN rail. 3. Set the node address on the node address thumbwheel.
WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation. 4. Remove the safety end cap by sliding it up. This exposes the backplane and power interconnections.
ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.

Set the Node Address
Set the node address using the 2-position thumbwheel switch. Valid settings range from 01...99. Press the + or - buttons to change the number. Network Node Address Thumbwheel

Network node address pen push thumbwheel ­ Press the center of either the + or - buttons to change the number.

02
A

Module Status
PointBus Status
ControlNet A Status
ControlNet B Status
1734-ACNR

WARNING: When you change switch settings while power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Install a Replacement ControlNet Adapter to an Existing System

ATTENTION: You must use series C POINT I/O modules with the 1734-ACNR or 1734-ACNRK adapter. Series A and B POINT I/O modules does not work with the 1734-ACNR or 1734-ACNRK adapter.

WARNING: When you connect or disconnect the RTB with field side power applied, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Remove the existing adapter from the DIN rail as follows: 1. Disconnect the ControlNet connector from the adapter. 2. Pull up on the RTB removal handle to remove the RTB. 3. Remove the adjacent module from its base. 4. Use a small bladed screwdriver to rotate the DIN rail locking screw to a vertical position. This releases the locking mechanism. 5. Lift straight up to remove.
Install the replacement adapter on the DIN rail as follows: 1. Remove the safety end cap on the replacement adapter by sliding it up. This exposes the backplane and power connections. 2. Position the replacement adapter vertically above the DIN rail.

6

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

POINT I/O ControlNet Adapter Installation Instructions
Verify that the DIN rail lock is in the horizontal position. 3. Slide the adapter down so that the interlocking side pieces engage the adjacent module. 4. Press firmly to seat the adapter on the DIN rail.
The adapter locking mechanism snaps into place. 5. Set the node address on the node address thumbwheel. 6. Insert the end opposite the handle into the base unit.
This end has a curved section that engages with the wiring base. 7. Rotate the RTB into the wiring base until it locks itself into place. 8. Replace the adjacent module in its base. 9. Connect the ControlNet cable to the adapter.
Use a tap to connect the adapter to the ControlNet cable. Do not directly connect the adapter to the coax cable.

Wire the ControlNet Adapter
To wire the adapter, see the diagrams and tables. Figure 2 - Adapter Wiring

NC = No connection CHAS GND = Chassis ground C = Common V = Supply

Node address thumbwheel
Network access port Coaxial channel A Coaxial channel B

02

Module Status
PointBus Status
ControlNet A Status ControlNet B Status
1734-ACNR

System Power Field Power
A

B

NC CHAS GND C V

WARNING: The NAP port is intended for temporary local programming purposes only and requires the use of a 1786-CP cable assembly. The NAP is not intended for permanent connection. If you connect or disconnect the NAP cable with power applied to this module or any device on the USB network, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Figure 3 - 12/24V DC Wiring

12/24V DC Do not connect 120/240V AC power to this supply.

NC = No connection

C = Common

V DC

CHAS GND = Chassis ground

V = Supply

0

1

NC NC

2 CHAS

3
CHAS

GND GND

4

5

C

C

6

7

V

V

Connect this DC supply to the internal power bus.

ATTENTION: Do not wire more than 2 conductors on any single terminal.

WARNING: If you connect or disconnect wiring while the field-side power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

7

POINT I/O ControlNet Adapter Installation Instructions
Interpret the Status Indicators
Figure 4 and Table 1 show the status indicators to troubleshoot your adapter. Figure 4 - Status Indicators for 1734-ACNR and 1734-ACNRK Adapters

02
A B

Module Status
PointBus Status
ControlNet A Status ControlNet B Status
1734-ACNR
System Power Field Power

Module status POINTBusTM status ControlNet A status ControlNet B status
System power Field power

Table 1 - Interpret the Status Indicators

Indicator Field power

Status Off Green

System power

Off
Green Off Alternating red/green

Module status ControlNet A/B status Viewed together ControlNet A/B status Viewed individually

Flashing red
Steady red
Flashing green Steady green Both steady off Alternating red/green Alternating red/off Both steady red Steady off Flashing red/green Flashing red/off Flashing green/off Steady green

Description Not active Field power is off. Power is on. 24V is present. Not active Field power is off. DC-DC converter problem exists. System power is on. DC-DC converter is active (5V). No power is applied to the device. LED powerup test (module self-test) is in progress. A recoverable fault has occurred: · Firmware (NVS) update · MAC ID changed · CPU load exceeded An urecoverable fault has occurred: · Self test failure (checksum failure at powerup, ramtest failure at powerup) · Firmware fatal error Waiting for connection or a ControlNet cable break is present The module is operating correctly (normal mode). Reset, no power, or entire network interface is deactivated.
The module is in self test mode.
Bad or invalid node configuration (such as duplicate MAC ID) is present.
Failed link interface has occurred. The channel is disabled or the channel is not supported. Invalid link configuration Severe link error ­ Link has faulted or no MAC frames is received. A temporary channel error has occurred or in listen-only mode. Normal operation ­ MAC frames are being received without detected errors.

8

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

Table 1 - Interpret the Status Indicators (Continued)

Indicator

Status Off Alternating red/green

Flashing red

POINTBus status Red

Flashing green Green

POINT I/O ControlNet Adapter Installation Instructions
Description The device is not powered. Check the module status indicator. LED power up test in progress. A recoverable fault has occurred: · The number of expected modules does not equal the number of modules present at power up. · A module is missing. · Node fault occurred (I/O connection timeout). An unrecoverable fault has occurred: · The adapter is bus off. · The adapter has failed its duplicate MAC ID check. The adapter is online with no connections established: · The adapter chassis size has not been configured. · The controller is in Program/Idle mode. · There is a ControlNet cable break. The adapter is online with connections established (normal operation, in run mode).

Specifications

POINT I/O ControlNet Adapter - 1734-ACNR, 1734-ACRNK

Attribute Number of nodes, max Module location Input voltage rating, nom Input voltage rating range
Isolation voltage

Value 1 Starter module ­ Left side of POINT I/O system 24V DC 10...28.8V DC 50V (continuous), Basic insulation type Type tested at 750V AC for 60 s, comm to system, user power to system, user power to comm, and all circuits to chassis ground.

General Specifications

Attribute

Value

Dimensions (HxWxD), approx.

76.2 x 54.9 x 133.4 mm (3.0 x 2.16 x 5.25 in.)

Weight, approx.

255 g (9 oz)

Network name

ControlNet

Termination type

None

Electronic protection

No

Diagnostics

No

Enclosure type rating

None (open-style)

Platform/processor compatibility

1747, 1756, 1761, 1762, 1764, 1789, 1794

Communication interface type

Adapter

Device type

Communication interface

Input byte capacity

248

Output byte capacity

248

Power supply 24V current load

425 mA

Field-side power requirements max

24V DC (+20% = 28.8V DC) @ 425 mA

Interruption protection

The output voltage stays within specifications when the input drops out for 10 ms at 10V with max load.

Field power bus, nominal voltage

24V DC

Field power bus, supply voltage range

10...28.8V DC

Field power bus, supply current, max

10 A

Operating voltage range

10...28.8V DC

Wire size Power wiring(1)

0.25...2.5 mm2 (22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F), or greater. 1.2 mm (3/64 in.) insulation max

Wire category(2)

1 on power ports 2 on communications ports

Terminal base screw torque

0.6 N·m (7 lb·in)

POINTBus output current, max

1 A @ 5V DC +5% (4.75...5.25V DC)

Input overvoltage protection

Reverse polarity protected

Power consumption

10.2 W @ 28.8V DC

Power dissipation, max

5.0 W @ 28.8V

Thermal dissipation, max

16.9 BTU/hr @ 28.8V DC

North American temp code

T4A

UKEX/ATEX temp code

T4

IECEx temp code

T4

(1) For information on ControlNet wire size, see ControlNet Coax Media Planning and Installation Guide Installation Instructions, publication CNET-IN002. (2) Use this Conductor Category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

9

POINT I/O ControlNet Adapter Installation Instructions

Power Supply
Attribute Input voltage rating, nom Input voltage range Field-side power requirements, max Inrush current, max Interruption

Value 24V DC 10...28.8V DC 24V DC (+20% = 28.8V DC) @ 425 mA 6 A for 10 ms The output voltage stays within specifications when the input drops out for 10 ms at 10V with max load.

1734-ACNR, 1734-ACNRK Communication Interface

Attribute Expansion I/O capacity
Expansion I/O capacity
Communication rate max

Value

Up to 17 modules, dependent on backplane bus current draw (17 X 75 mA = 1.275 A, just under the limit of 1.3 A). The actual number of modules can vary. Add up the current requirements of the modules you want to use to make sure they do not exceed the amperage limit of the 1734-ACNR or 1734-ACNRK adapter.

Catalog Number 1734-IB2 1734-IB4 1734-IB4D 1734-IB8 1734-IB2 1734-IB4 1734-IB4D 1734-IB8 1734-IV2 1734-IV4 1734-IV8 1734-OB2 1734-OB4 1734-OB8 1734-OB2E 1734-OB2EP 1734-OB4E 1734-OB8E 1734-OV2E 1734-OV4E 1734-OV8E 1734-OW2

POINTBus Current Requirements 75 mA 75 mA 50 mA 75 mA 75 mA 75 mA 50 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 80 mA

Catalog Number 1734-OW4 1734-OX2 1734-IE2C 1734-OE2C 1734-IE2V 1734-OE2V 1734-IA2 1734-IA4 1734-IM2 1734-IM4 1734-OA2 1734-OA4 1734-IJ 1734-IK 1734-IR2 1734-IR2E 1734-IT2I 1734-SSI 1734-VHSC5 1734-VHSC24 1734-232ASC 1734-485ASC

POINTBus Current Requirements 80 mA 100 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 75 mA 160 mA 160 mA 220 mA 220 mA 175 mA 110 mA 180 mA 180 mA 75 mA 75 mA

128K bit/s (500 m) 250K bit/s (250 m) 500K bit/s (100 m)

Environmental Specifications
Attribute Temperature, operating
Temperature, nonoperating Temperature, surrounding air, max Relative humidity Vibration Shock, operating Shock, nonoperating Emissions ESD immunity Radiated RF immunity EFT/B immunity
Surge transient immunity Conducted RF immunity

Value IEC 60068-2-1 (Test Ad, operating cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-2-14 (Test Nb, operating thermal shock) -20 °C  Ta  +55 °C (-4 °F  Ta  +131 °F) IEC60068-2-1 (Test Ab, unpackaged nonoperating cold) IEC60068-2-2 (Test Bb, unpackaged nonoperating dry heat) IEC60068-2-14 (Test Na, unpackaged nonoperating thermal shock) -40...+85 °C (-40...+185 °F) 55 °C (131 °F) IEC60068-2-30 (Test Db, unpackaged damp heat) 5...95% noncondensing IEC 60068-2-6 (Test Fc, operating): 5 g @ 10...500 Hz IEC60068-2-27 (Test Ea, unpackaged shock): 30 g IEC60068-2-27 (Test Ea, unpackaged shock): 50 g IEC 61000-6-4 IEC6100-4-2: 6 kV contact discharges 8 kV air discharges IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80...6000 MHz IEC 61000-4-4: ±4 kV at 2.5 kHz on power ports ±2 kV at 5 kHz on communications ports IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports ±2 kV line-earth(CM) on communications ports IEC61000-4-6 10V rms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz

10

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

POINT I/O ControlNet Adapter Installation Instructions

Certifications

Certification (when product is marked)(1) c-UL-us
UK and CE

Value UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. UK Statutory Instrument 2016 No. 1091 and European Union 2014/30/EU EMC Directive, compliant with: EN 61326-1; Measurement/Control/Laboratory use, Industrial requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

UK Statutory Instrument 2012 No. 3032 and European Union 2011/65/EU RoHS, compliant with: EN IEC 63000; Technical documentation

RCM

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

UK Statutory Instrument 2016 No. 1107 and European Union 2014/34/EU ATEX Directive, compliant with:

EN IEC 60079-0; General Requirements

Ex

EN IEC 60079-7; Explosive Atmospheres, Protection "e" II 3 G Ex ec IIC T4 Gc

DEMKO 04 ATEX 0330347X

UL22UKEX2478X

IECEx System, compliant with:

IEC 60079-0; General Requirements

IECEx

IEC 60079-7; Explosive Atmospheres, Protection "e"

II 3 G Ex ec IIC T4 Gc

IECEx UL 20.0072X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

Morocco

Arrêté ministériel n° 6404-15 du 29 ramadan 1436

CNCA-C23-01

CCC

CNCA-C23-01 CCC Implementation Rule Explosion-Proof Electrical Products

CCC: 2020122309111607

ControlNet

ControlNet International conformance tested to ControlNet specifications

(1) See the Product Certifications link at rok.auto/certifications for Declaration of Conformity, Certificates, and other certification details.

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation. You can view or download publications at rok.auto/literature.

Resource
POINT I/O Modules Selection Guide, publication 1734-SG001
POINT I/O ControlNet Adapter User Manual, publication 1734-UM008 Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, rok.auto/certifications

Description Provides information to help you select POINT I/O adapters, I/O modules, wiring base assemblies, power supplies, and accessories, based on your requirements. Describes how to install, configure, and operate the POINT I/O ControlNet adapter. Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details.

Rockwell Automation Publication 1734-IN582D-EN-P - September 2024

11

Rockwell Automation Support

Use these resources to access support information.

Technical Support Center Local Technical Support Phone Numbers Technical Documentation Center Literature Library Product Compatibility and Download Center (PCDC)

Find help with how-to videos, FAQs, chat, user forums, Knowledgebase, and product notification updates. Locate the telephone number for your country. Quickly access and download technical specifications, installation instructions, and user manuals. Find installation instructions, manuals, brochures, and technical data publications. Download firmware, associated files (such as AOP, EDS, and DTM), and access product release notes.

rok.auto/support rok.auto/phonesupport rok.auto/techdocs rok.auto/literature rok.auto/pcdc

Documentation Feedback

Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Rockwell Otomasyon Ticaret A.. Kar Plaza  Merkezi E Blok Kat:6 34752 çerenköy, stanbul, Tel: +90 (216) 5698400 EEE Yönetmeliine Uygundur

Allen-Bradley, expanding human possibility, POINT I/O, POINTBus, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. ControlNet is a trademark of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1734-IN582D-EN-P - September 2024 | Supersedes Publication 1734-IN582C-EN-P - June 2023
Copyright © 2024 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.